Brochure/Catalogue

C
C.64 2028840000
Lightning and surge protection
for low voltage supply
Type III with varistors / gas discharge tube
Type III surge protection
Suitable for protecting terminals
Installed in the vicinity of the equipment to be protected
For mounting on rail TS 35
Arrester with remote signalling contact
Tested in accordance with IEC 61643-11
Technical data
Rated voltage (AC)
Rated voltage (DC)
Max. continuous voltage, Uc (AC)
Max. continuous voltage, Uc (DC)
Combined pulse U
OC
Discharge current, max. (8/20 µs)
Rated current
Requirements class, acc. to EN 61643-11
Short-circuit current rating I
SCCR
Leakage current at U
n
Fuse
Temporary surge voltage (over-voltage) - TOV
Protection level wire-wire 8/20 µs, typically
Protection level wire-PE 8/20 µs, typically
Response time
Optical function display
Design
Colour
Ambient temperature (operational)
Storage temperature
Connection according to IEC 947-7-1
Solid
Stranded
Stripping length
Tightening torque
Approvals
Approvals
Standards
Dimensions / Signalling contact info
Clamping range (nominal / min. / max.) mm²
Height x width x depth mm
Signalling contact
Note
Ordering data
Screw connecion
with acoustic signal (A)
without acoustic signal
Note
Accessories
Note
VPU III R 12 V / 4 kV
For use as device protector
U
PE´
N
PE
U
12
11
FAULTOK
IN
protected
unprotected
12 V
16 V
20 V
28 V
4 kV
2 kA
16 A
T3
1.5 kA
30 µA
16 A
23 V
180 V
≤ 0.98 kV
≤ 100 ns
Green LED = OK, Red LED = arrester is defective, replace
Installation housing; 1TE, Insta IP 20
Red
-40 °C...70 °C
-40 °C...80 °C
0.5...2.5 mm²
0.5...2.5 mm²
7 mm
0.4...0.5 Nm
CE; EAC; OEVE
IEC61643-11, EN61643-11
Screw connection
2.5 / 0.5
102 / 18 / 71.5
250 V 10 A 1 NC
Type Qty. Order No.
VPU III R 12V/4KV AC/DC 1 1351550000
VPU III SO LD / +A
For use as device protector
L
N
PE
U
FAULT
230 V
275 V
3 kV
1.5 kA
16 A
T3
1.5 kA
10 µA
16 A
440 V
≤ 0.9 kV
≤ 1.5 kV
≤ 100 ns
Green LED = OK, Red LED = arrester is defective, replace
Flush mounting
Black
-25 °C...55 °C
-40 °C...80 °C
...
...
...
CE; EAC
IEC61643-11, EN61643-11
with acoustic signal (A)
Without audible signal
35 / 12 / 25 35 / 12 / 25
No No
Cable length approx. 118 mm
Type Qty. Order No.
VPU III SO LD+A 1 1351700000
VPU III SO LD 1 1351680000
Type III surge protection for terminal devices