Photovoltaic application example
Air termination
PV generator
Generator terminal box
Consumers
Power inverter
> 0.5 m
to 1 m
> 0.5 m
to 1 m
32
1
1*
(example drawing: no liability taken)
1 VPU II 3 1000 V DC PV
Y-coupling
1* V PU II 3 1000 V DC PV
For long distances > 10 m between the PV generator
and inverter
2 VPU II 4 280 V / 40 kA
For long distances > 10 m between the inverter and
the house power feed
3 V PU-I-LCF-Serie
In the event of an existing lightning protection system
Modular use of our surge protection components
If a lightning protection system is already present on the
building, this must be at the highest point of the entire
system. All modules and cables of the photovoltaic
installation must be installed below the air terminations.
Separation distances of at least 0.5 m to 1 m must be
maintained (depending on risk analysis from IEC 62305-2).
The external Type I lightning protection (AC side) also
requires the installation of a Type I lightning arrester in the
electrical supply of the building. If no lightning protection
system is present, then Type II arresters (AC side) are
sufcient for use.