Brochure/Catalogue

D
D.192028840000
Lightning and surge protection
for data interfaces
Coax surge protection
Surge protection for COAX data networks
Metal housings
Surge protection using gas discharge tube
Easy handling using socket-adapter function, with
minimal attenuation
Technical data
Transmission capacity, max.
Max. continuous voltage, Uc (DC)
Characteristic impedance
Frequency range
Operating current, I
max.
Insertion loss
Return loss (attenuation)
Standing wave ratio, VSWR
Requirements category acc. to IEC 61643-21
Lightning test current I
imp
(10/350 µs)
Discharge current, max. (8/20 µs)
Response time
Protection level U
P
(typ.)
Earthing
Type of connection
Version
Ambient temperature (operational)
Approvals
Approvals
Standards
Dimensions
Clamping range (nominal / min. / max.)
Height x width
Note
Ordering data
Note
Accessories
Note
F Connector / M-F
Protection for satellite systems
25 W
90 V ± 20 %
75 Ω
0...2 GHz
10 A
< 0.5 dB
> 20 dB
< 1.3
D1, C3, C2, C1
5 kA
20 kA
≤ 100 ns
< 700 V
Required with M6 screw
Plug / socket
Adapter plug
-40 °C...80 °C
Plug / socket
/ 26
Type Qty. Order No.
F Connector / M-F 1 8947840000
UHF Connector / M-F
Protection for terrestrial TV
75 Ω
0...1 GHz
4 A
< 0.5 dB
> 20 dB
C3, C2, C1, D1
20 kA
< 1 ns
< 600 V
Required with 1.5mm
2
connection cable
Plug / socket
Adapter plug
-40 °C...80 °C
Plug / socket
73.4 / 43
Type Qty. Order No.
UHF Connector / M-F 1 8947850000
Surge protection for data interfaces