Brochure/Catalogue

B
B.160 2028840000
Lightning and surge protection
for control and instrumentation signals
VSSC 4 GDT EX - protection with sparkover gap(GDT)
UNPROTECTED PROTECTED
1
TS
2
3
4
Dielectric strength at FG against PE ≥ 500 V
Volume resistance < 0.1
Ω
Overload - failure mode Modus 2
Requirements category acc. to IEC 61643-21 C2, C3, D1
Surge current-carrying capacity C1
Surge current-carrying capacity C2 5 kA 8/20 μs
Surge current-carrying capacity C3 100 A 10/1000 μs
Surge current-carrying capacity D1 2.5 kA 10/350 μs
Discharge current I
n
(8/20 µs) wire-wire/wire-PE/GND-PE / 5 kA
Discharge I
max
(8/20 μs) wire-wire/wire-PE/GND-PE / 20 kA
Lightning test I
imp
(10/350 µs) wire-wire/wire-PE/GND-PE /
Type of connection Screw connection, Torx
®
T15, Slotted 0.8 x 4
Storage temperature -40 °C...80 °C
Ambient temperature (operational) -40 °C...70 °C
Protection degree IP20
UL 94 flammability rating V-0
Connection data
Type of connection Screw connection, Torx
®
T15, Slotted 0.8 x 4
Tightening torque 0.5 Nm
Wire connection cross section, finely stranded, max. 4 mm²
Wire connection cross-section, finely stranded, min. 0.5 mm²
Wire cross-section, solid, max. 6 mm²
Wire cross-section, solid, min. 0.5 mm²
Wire cross-section, stranded, max. 4 mm²
Wire cross-section, stranded, min. 0.5 mm²
Stripping length 10 mm
Mounting rail TS 35
Approvals
Approvals CE; CSAEX; DEKRAATEX; EAC; GOSTEX; IECEXDEK; TUEV
Standards IEC61643-21:2009, DIN EN 60079-0.2009, DIN EN 60079-
26:2007, DIN EN 61241-11:2006
ATEX - dust labelling II 1 D Ex ia IIIC T135 °C …T85 °C Da
ATEX - gas labelling II 1 G Ex ia IIC T4… T6 Ga
IECEx - dust labelling II 1 D Ex ia IIIC T135 °C …T85 °C Da
IECEx - gas labelling II 1 G Ex ia IIC T4… T6 Ga
Note
Dimensions Dimensions
Height x width x depth mm 76 / 12.2 / 58.5
ATEX approval: II 1 G EX ia IIC T4...T6 Ga II 1 D EX ia IIIC T135°C...T85°C
DEKRA No: 11ATEX0023 X
Technical data
One-stage surge protection with screw connection for measurement
and control signals
Surge protection in terminal block design
Modular width of only 12.4mm
Space-saving design for one signal
Torx
®
slotted screw connection
Can be used in compliance with installation standard IEC 62305
Tested in accordance with IEC 61643-21: C1, C2, C3
Integrated PE foot, safely discharges up to 20kA (8/20 μs) and
2.5kA (10/350 μs) to PE
VARITECTOR SSC EX