Approval/Certificate/Document of Conformity

Attachment to Certificate
IECEx PTB 11.0071, Issue No. 1
Physikalisch-Technische Bundesanstalt (PTB)
Bundesallee 100, 38116 Braunschweig, Germany
Postfach 33 45, 38023 Braunschweig, Germany
Telephone +49 531 592-0, Telefax +49 531 592-3605
Page 3 of 3
Controlgear and
distribution enclo-
sure, type
max. number
Rosemount Inc.
model 644R
Ex ia/ib/ic
Tempera-
ture class
Permissible
ambient
temperature
P
i
= 1 W
max. number
Rosemount Inc.
model 644R
Ex nA
Tempera-
ture class
Permissible
ambient
temperature
Klippon TB..262615
5
T4
- 60 °C … + 40 °C
without clearance
5
T5
- 60 °C … + 35 °C
without clearance
Klippon TB..262620
Klippon TB..303015
8
T4
- 60 °C … + 43 °C
clearance 8 mm
8
T5
- 60 °C … + 38 °C
clearance 8 mm
Klippon TB..303020
Klippon TB..352615
Klippon TB..352620
Klippon TB..403015
Klippon TB..403020
Klippon TB..453815
14
T4
- 60 °C … + 40 °C
clearance 8 mm
14
T5
- 60 °C … + 35 °C
clearance 8 mm
Klippon TB..453820
Klippon TB..484815
Klippon TB..484820
Klippon TB..553515
Klippon TB..553520
Klippon TB..624515
Klippon TB..624520
Klippon TB..765015
Klippon TB..765020
Klippon TB..916115
Klippon TB..916120
Klippon TB..987420
Electrical data
The electrical data depend on type and number of the separately certified devices installed
and shall be taken from the respective certificates and operating instructions manuals.
Notes for manufacture and operation
1. The explosion protected power distribution, switchgear and controlgear-combinations
shall be electrically connected to the equipotential bonding system of the hazardous area.
2. When intrinsically safe circuits are used which provide different protection levels
(ia, ib or ic), the marking and the field of application of the equipment is determined by that
intrinsically safe circuit having the lowest protection level.
3. The specifications and notes given in the certificates as well as the operating instructions
of the built-in, separately certified apparatus shall be considered accordingly.
4. Only certified cable glands shall be used. Non-used openings shall be sealed by
appropriate blind plugs.