User Documentation

11
Opening the lid
Open the quarter lock with a suitable tool (refer to diagram 1 below). After opening the
quarter lock, the lid can be opened up to approximately 130°. It’s not possible to remove
the Lid without a tool.
1 2
Removing gland plates
If gland plates are to be used remove them by loosening the gland plate screws with a
suitable tool. Afterwards the plates can be detached.
Closing the enclosure
Ensure that all lid, gland plate, earth stud screws are fully tightened in a crosswise
manor after installation.
Tightening Values
Lid, Gland plates & mounting screws for mounting plates (when present): 2.5 Nm
M10 earth stud (out-/inside): 15.0 Nm
M6 earth stud inside: 6.0 Nm