Approval/Certificate/Document of Conformity

SCHEDULE
EU-TYPE EXAMINATION CERTIFICATE Sira 05ATEX1287X
Issue 5
This certificate and its schedules may only be
reproduced in its entirety and without change
CSA Group Netherlands B.V.
Utrechseweg 310,
6812 AR, Arnhem Netherlands
DQD 544.11 Rev 2018-04-20 Page 5 of 5
Issue
Date
Report number
Comment
4
04 June 2018
R70144815B
This Variation introduced the following changes:
EC-Type Examination Certificate in accordance
with 94/9/EC updated to EU-Type Examination
Certificate in accordance with Directive
2014/34/EU.
(In accordance with Article 41 of
Directive 2014/34/EU, EC-Type Examination
Certificates referring to 94/9/EC that were in
existence prior to the date of application of
2014/34/EU (20 April 2016) may be referenced
as if they were issued in accordance with
Directive 2014/34/EU. Variations to such EC-
Type Examination Certificates may continue to
bear the original certificate number issued prior
to 20 April 2016.)]
The introduction of Sira Variation 6
5
15th October 2019
0464
Transfer of certificate Sira 05ATEX1287X from
Sira Certification Service to CSA Group
Netherlands B.V..
14.3 Certificate number Sira 01ATEX1272X Issue 12
15 SPECIFIC CONDITIONS OF USE (denoted by X after the certificate number)
15.1 The KSG, KSGDS and KCG Range of Cable Glands shall not be used in enclosures where the temperature
at the point of entry/mounting exceeds the following.
-35°C to +90°C for the Neoprene seal variants
-60°C to +180°C for the Silicone seal variants
15.2 The cable entries are only suitable for fixed installations. Cables must be effectively clamped to prevent
pulling or twisting.
15.3 The KSG, KSGDS and KCG range of cable glands, when installed in accordance with the manufacturer’s
instructions and with an appropriate enclosure on which they are fixed, are capable of providing an
ingress protection of IP66 and IP68 (50 metres, 7 days).
15.4 The threaded entry component threads without interface O-ring seals installed in an explosive dust
atmosphere, within threaded entries, shall only be fitted into enclosures that have either:
parallel entries that will ensure that a minimum of 5 full threads of contact will be maintained, this
is in accordance with clause 5.1.2 of EN 60079-31:2014,
tapered entries that will ensure that a minimum of 3 ½ full threads of contact will be maintained,
this is in accordance with clause 5.1.2 of EN 60079-31:2014
16 ESSENTIAL HEALTH AND SAFETY REQUIREMENTS OF ANNEX II (EHSRs)
The relevant EHSRs that are not addressed by the standards listed in this certificate have been identified
and individually assessed in the reports listed in Section 14.2.