Brochure/Catalogue

Klippon
®
KUB Cable Glands
Klippon
®
KUB Barrier glands T
The KUB gland provide an armour clamp for steel tape, steel
wire and braided cables. An electrical bond between the
cable armour and the gland is ensured. The gland can also
be used to terminate unarmoured cables. Additionally, the
gland provides a single pull resistant seal on the outer sheath
of any cable. After clamping the cable armour onto the cone,
the cable has to be lled with the provided compound to
seal the free spaces between the single conductors. The
gland maintains a temperature range from -60 °C to +85 °C.
When lled, the gland fullls an IP rating of IP 68 to 100
metres (30 Min. at 10 bar). The KUB gland is only suitable
for Ex d applications. To know when to use a barrier gland
and when to use a gland with sealing ring, please refer to the
selection guide shown on page 36.
Technical Data
Material Brass CuZnPb3 (CZ121)
Sealing ring Silikon
Class of protection IP68 (30 minutes at 100 metres water depth)
Thread ISO Metric
Plating Nickel-plated (NI); Self-coloured (SC)
Temperature range With silicone sealing: -60 ºC to +85 ºC
Desgin Standard EN 60079-0, EN 60079-1, EN 60079-7, EN 60079-31
IEC 60079-0, IEC 60079-1, IEC 60079-7
Certication ATEX: II 2 GD, Ex d IIC / Ex e IIC Gb / II 1D / Ex tb IIIC Db (Ta = –60 °C...135 °C) / Ex ta IIIC Da (Ta = –60 °C...135 °C)
IECEx: Ex d IIC / Ex d I
Certicates SIRA 05ATEX1288X
IECEx SIR 05.0067X
Application: Ex d Equipment The KUB glands will only maintain Flameproof Ex d integrity when used with a cable that is substantially round and compact with extruded bedding.
The cable shall be deemed to be effectively lled. The cable should fulll the IEC 60079-14 chapter 10.4.2 standard.
Ex d Applications Gas Group Internal Ignition Source Enclosure Volume Zone Use KUB
I, IIC, IIB, IIA YES Any Zone 1 or 2 YES
Other Applications Mining Applications Group I, M2
Ignitable Dust, Zone 21 and 22
211543550000