Brochure/Catalogue

Klippon
®
KUB Cable Glands
Structure of the part description
Order key
[Type] [a] [b] [c] [d] [e] [f] [ggg]
Example article description
KUB M20 B S O SC 1 G16
Meaning [Type] = Gland type (KUB)
[a] = Entry thread (M20-M75)
[b] = Material (B = brass)
[c] = Seal material (S = Silicone)
[d] = Continuity for lead sheath (L = yes, O = no)
[e] = Plating (SC = self-coloured, NI = Nickel)
[f] = Cable outer sheath (1 = Reduced, 2 = Standard)
[ggg] = Gland size (G16-G75)
A
D
C
B
Note Refer to page 36 Selection Guide Klippon
®
Cable Glands to determine the suitable order number
Dimensions
Gland Seal Range
Gland Size Entry thread
Entry
thread
Length
Max
Outer
Diameter
Max
Length
Cable
Inner Sheath
[C]
Cable
Outer Sheath
[D]
Armour
Acceptance
Range
Shroud
Size
Standard
[f] = 2
Reduced
[f] = 1
[ggg] [a] [B] [A]
X Y Z Min Max Min Max
G16 M20 16
28.0 72.0
7
9.0 11.7 9.0 13.5 6.7 10.3 0.15 - 1.25
L24
G20S M20 16
28.0 72.0
8
10.4 11.7 11.5 16.0 9.4 12.5 0.15 - 1.25
L24
G20 M20 16
33.0 73.0
14
12.5 14.0 15.5 21.1 12.0 17.6 0.15 - 1.25
EL30
G25 M25 16
41.4 83.0
25
17.8 20.0 20.3 27.4 16.8 23.9 0.15 - 1.60
EL38
G32 M32 16
50.6 103.0
50
23.5 26.3 26.7 34.0 23.2 30.5 0.15 - 2.00
EL46
G40 M40 16
60.5 105.0
80
28.8 32.2 33.0 40.6 28.6 36.2 0.20 - 2.00
EL55
G50S M50 16
71.5 115.0
100
34.2 38.2 39.4 46.7 34.8 42.4 0.30 - 2.50
EL65
G50 M50 16
71.5 115.0
100
39.4 44.1 45.7 53.2 41.1 48.5 0.30 - 2.50
EL65
G63S M63 19
88.0 115.0
120
44.8 50.1 52.1 59.5 47.5 54.8 0.30 - 2.50
EL80
G63 M63 19
88.0 115.0
120
50.0 56.0 58.4 65.8 53.8 61.2 0.30 - 2.50
EL80
G75S M75 19
99.0 122.0
140
55.4 62.0 64.8 72.2 60.2 68.0 0.30 - 2.50
EL90
G75 M75 19
99.0 122.0
140
60.8 68.0 71.1 78.0 66.5 73.4 0.30 - 2.50
EL90
Dimensions in mm
Important Notes
The gland size does not necessarily equate to the entry thread size.
In some cases several gland sizes can be chosen due to overlaping inner as well as outer cable diameters. Due to the wide range of armoured cables available, it is necessary to select the correct clamping range. This is
achieved by taking the inner and outer clamping range values to determine the best t (as close as possible to the Min/Max values average).
X = Maximum numbers of cores
Y = Maximum over cores (The remaining space around the wires must be large enough for the sealing compound)
Z = Maximum inner sheath
All cable glands have a 1.5 mm pitch.
For Flameproof Ex d applications the female thread into which the gland is to be tted must achieve an engagement of at least 5 full threads in compliance with clause 5.3 of EN/IEC 60079-1.
Where KUB glands are tted into non-metallic Increased Safety Ex e enclosures they must be included within the earth circuit of the system.
Fully assembly instructions are supplied with the glands. The instructions must be read prior to installation and adhered to in full.
When the gland is used to terminate un-armoured cables, the gland is suitable only for xed installation.