Brochure/Catalogue

RSMS multiple relay modules – Interfaces with 6,1mm relays (RCL)
RSMS 1CO – Relay interface
1 changeover
Interface from 8 to 16 electromechanical relays
1 changeover
Positive or negative switching or ac/dc
Flat-connector avaliable to make easy the connection
to PLC’S
Compatible with solid-state relays
With optional gold contact relay
Screw and tension clamp
General technical data
General features
Relay
RSS relay
LED status display per channel Green
LED status of the supply voltage
Yellow
Nominal output data
Contact material
AgNi 90/10 / AgNi 5μAu
Operative voltage 250 V AC
Max. AC continuous current 4.5 A
Minimum contact current standard / Gold 100 mA / 1 mA
Minimum contact voltage standard / Gold 5 V / 1 V
Mechanical service life (dc coil) 5 x 10
6
Switching cycles
Operating temperature -25...+50 °C
Storage temperature
-40...+60 °C
Insulation coordination (EN 50178)
Rated input insulation voltage
< 50 V AC
Rated output insulation voltage 250 V AC
Overvoltage category input/output III
Overvoltage category output/input II
Pollution severity level 2
Impulse voltage test (1.2/50µs) 6 kV
Insulation test voltage 1.2 kV AC
Clearance input/output
≥ 5.5 mm
Dimensions Screw connection Tension clamp
Clamping range, min. [Field]/ Clamping range, max. [Field]
0.13 mm
2
/ 6 mm
2
0.13 mm
2
/ 2.5 mm
2
Clamping range, min. [supply]/Clamping range, max. [supply] 0.13 mm
2
/ 6 mm
2
0.2 mm
2
/ 2.5 mm
2
Mounting rail TS 32 / TS 35 TS 32 / TS 35
Width / height mm
109 x 85 109 x 76
Note
Electromechanical relays:
5 V DC: Spare Relay RSS113005 4061580000;
12 V DC: Spare relay RSS113012 4061610000;
24 V DC: Spare relay RSS113024 4060120000;
24 V AC/DC: Spare relay RSS113024 4060120000;
48 V DC: Spare relay RSS113048 4061620000;
24 V DC Gold contact: Spare relay RSS112024 4061590000
Solid-state relays:
SSR 24 V DC/24 V DC 0.1 A 4061180000;
SSR 24 V DC/24 V DC 2 A 4061190000;
SSR 24 V DC/230 V AC 1 AC 4061210000.
E
Isolated Interfaces and solutions for general
applications
E.132690170000