u-remote Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens 1200 PLC and TIA Portal V14 Ordering data: 2500890000
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 Revisions Version Date Changes 01 04.2018 First edition Contact Weidmüller Interface GmbH & Co. KG Klingenbergstraße 16 32758 Detmold, Germany Phone +49 5231 14-0 Fax +49 5231 14-292083 info@weidmueller.com www.weidmueller.
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 Contents 1. Disclaimer 4 2. Warning 4 3. Note 4 4. Security notes 5 5. Preamble 5 6. Downloading and installing the required files (GSDML) 6 7. Creating a new project with Siemens TIA-Portal V14 9 8.
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 1. Disclaimer This Application Note does not relieve you of the obligation to handle it safely during use, installation, operation and maintenance. Each user is responsible for the correct operation of his control system. By using this program application note prepared by Weidmüller, you accept that Weidmüller cannot be held liable for any damage to property and / or personal injury that may occur because of the use. 2.
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 4. Security notes In order to protect equipment, systems, machines and networks against cyber threats, it is necessary to implement (and maintain) a complete state-of-the-art industrial security concept. The customer is responsible for preventing unauthorized access to his equipment, systems, machines and networks.
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 6. Downloading and installing the required files (GSDML) 1. Follow the link to the Weidmueller Website. http://catalog.weidmueller.com/catalog/Start.do?localeId=de&ObjectID=2500890000 2. Download the marked files. 3. You need the GSDML file for your Siemens TIA V14 engineering tool. With this file you can make a device configuration as shown in chapter 7. 4. Start TIA Portal V14 from the desktop.
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 5. Go to the “Project view” Window. 6. Open the Options tab and start the “Manage general station description files (GSD)”.
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 7. Choose the downloaded GSDML file and click “Install”. This takes a few moments.
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 7. Creating a new project with Siemens TIA-Portal V14 1. Go to the Portal view. 2. Choose “create new project”. 3. Label the project with a name, for example “Test” and click “Create”.
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 4. Configure a device. Click “Configure a device”. 5. “Add new device” and choose the CPU. Take care you select the correct version.
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 6. Device configuration and Ethernet settings. 1. Go to “Device configuration”. 2. Go to “PROFINET interface [X1]”. Check if all components are in the same Subnet as your PC. 3. Check if your CPU PROFINET device name is correct (plc_1).
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 7. Add an ENERGY-METER 700-PN-230. 1. Go to “Devices & networks” (Double-click on it). 2. Open Catalog and choose ENERGY-METER 700-PN-230. 3. Paste it next to the CPU (Double-click on “EM700-PN”). 8. Connecting the Energy Meter with the CPU. 1. Draw the line (green) from Port to Port. Click therefore on the first green Port hold the left mouse button till the second green Port from your Energy Meter. 2.
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 9. Download the settings to the device. 1. Click on PLC_1 [CPU_1212FC_DC/DC/DC] 2. Download settings to device. 3. Start searching for devices. 4. Select the CPU. 5. Click “Load” to load the settings into the CPU.
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 6. Click on “Continue without synchronization”. 7. “Load” the settings. 8. Click “Finish” to close the window.
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 10. Assign PROFINET device name. 1. Select EM700-PN. (Double-click on it) 2. Go to Online & diagnostics with right mouse button. 3. Functions -> Assign PROFINET device name 4. Update list. 5. Click “Assign name” to give correct device name to the Energy Meter.
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 11. Settings of the ENERGY METER 700-PN-230. 1. Go to “Devices & networks” (Double-click on it.) 2. Double-click 2 times on the EM700-PN. 3. Go to “PROFINET interface [X1]”. 4. Energy Meter needs the same Subnet as the CPU. 5. The device name must be adapted to the existing name. 6. Click on “PLC_1[CPU 1212FC DC/DC/DC]”. 7. Compile it now. 8. Download all settings to the device.
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 8. Add Parameters to the watch_table 1. Open Catalog/Module and choose for example parameter “Frequency”. Double-click to add it to your device. 2. Go to “IO tags”. 3. Name the Parameter definitely. 4. Double-click on “Default tag table [38]”. 5. Choose Data type “Real” for the Frequency.
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 6. Double click on “Add new watch table”. 7. Search for the parameter name. 8. Click on “Hardware (rebuild all)”.
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 9. Click on “Software (rebuild all)”. 10. Click on “Hardware configuration”.
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 11. Download settings to the device. 1. Use “PN/IE_1” for the Connection to interface/subnet. 2. Click “Start search”. 3. Select your current CPU. 4. Click “Load” to load the settings into the CPU. 5. “Load” the settings. 6. Click “Finish” to close the window.
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 12. Download the Software to the device. 1. Click “Load” to load the Software. 2. Click “Finish” to close the window.
Commissioning Weidmüller ENERGY METER 700-PN-230 with Siemens TIA V14 13. Set CPU to RUN mode. 1. Click “Go online”. 2. Start the CPU. 3. Accept the run with “OK”. 14. Watch the parameter value. 1. Double-click “Watch_table_1”. 2. Click “Monitor all” to see current value in the orange box.