Approval/Certificate/Document of Conformity

Page 18 of 28 Report No.: 2198607.50
IEC 61984
Clause Requirement + Test Result - Remark Verdict
C1
TABLE: Temperature rise test
P
Ambient temperature C)..................................: 22,7 °C
Thermocouple Locations
Test current
(A)
Upper temperature
limit (ULT) (°C)
Temperature
measured (°C)
Terminals on female part 17,5 100 59,5 P
Terminals on male part 24 100 87,4 P
supplementary information:
D1
TABLE: Initial measurements (Contact resistance)
P
Test current .......................................................: 1 A
Test sample
Contact 1 2 3 PE
1
U1 [mV]
0,71 0,75 0,70 P
R1 [m]
0,71 0,75 0,70
supplementary information:
D5
TABLE: Final measurements (Contact resistance)
P
Test current.....................................................................: 1 A
Condition ........................................................................:
R2max 1,5R1 or
R2max 5 m + R1
Test sample
Contact 1 2 3 PE
1
R2max [m]
5,71 5,75 5,70 P
U2 [mV]
0,87 0,84 0,80
R2 [m]
0,87 0,84 0,80
supplementary information: