Approval/Certificate/Document of Conformity

Page 7 of 28 Report No.: 2198607.50
IEC 61984
Clause Requirement + Test Result - Remark Verdict
b) free connectors in which the terminations are
protected against pull and twisting by mounting
provisions in the end-use product
P
DIMENSIONAL EXAMINATION: IEC 60512 P
6.19
Clearances and creepage distances according to
IEC 60664.
see table 0.2 P
Connector dimensions comply with the DS or
manufacturer’s specification.
P
A2 DURABILITY OF MARKING
7.3.2
Test liquid: water
Test piston size 1; force 5 N; 10 cycles
IEC 60068-2-70 Test Xb „Abrasion of marking“
Moulded Marking N/A
VISUAL EXAMINATION: IEC 60512 Test 1a
Visible with the naked eye P
A3 POLARISATION AND CODING: IEC 60512 / Test [13e] P
- For unenclosed connectors (internal connections)
20 N
P
- For enclosed connectors (external connections)
1,5 x mating force, but not higher than 80 N
N/A
6.3
Multipole connector: Contact between protective
earthing contacts and live contacts is not possible
by engagement.
N/A
6.9.1
Multipole connector: Polarisation prevents
improper connection of mating parts.
P
VISUAL EXAMINATION: IEC 60512 Test 1a
No damage likely to impair function P
A4 PROVISIONS FOR EARTHING N/A
6.5.1
For a CBC the earthing contact is a “first make -
last break” contact.
N/A
7.3.3
No electrical contact indication between earth
contact and the other contacts.
N/A
6.5.4 CONNECTION OF THE PROTECTIVE EARTH CONNECTOR
VISUAL EXAMINATION: IEC 60512 Test 1a
Remove any available covers if required. N/A