User Documentation

Weidmüller Interface GmbH Co. KG; Klingenbergstraße 16, 32758 Detmold-Germany
A2C 35
A2C 35 DM
880 V
880 V with M5 hexagon
socket head cap screw
according to DIN 912 with
washer with a maximum
height of 6 mm and a
maximum Ø 8,5 mm as fixing
screw
105 A / ΔT
40 K 105 A / ΔT
40 K
105 A / ΔT
40 K
105 A / ΔT
40 K
1,8 m 2,5 m 1,8 m
35 mm² 35 mm² 35 mm²
2,5 - 16 mm²
2,5 - 16 mm²
2,5 - 16 mm²
10 - 35 mm²
10 - 35 mm²
10 - 35 mm²
10 - 35 mm²
10 - 35 mm²
10 - 35 mm²
12 - 2 AWG
12 - 2 AWG
12 - 2 AWG
25 mm 25 mm 25 mm
880 V
B - Continuous with 2 cross-connections
550 V
550 V
E - Next to a protective conductor terminal (earth)
Max voltage data according to IEC/EN 60079-7 in conjunction with
protective earth terminal blocks of the A-Series, (increased safety "eb"):
- Rated current with ZQV
- Rated current
Application Case
- Stripping length
IECEx / ATEX Terminal and Cross-Connection Arrangements:
- Conductor cross section solid
- Rated conductor cross section
- Conductor cross section flexible
- Contact resistance
with rated conductor, 16 mm²
- Conductor cross section stranded
- cross section, American Wire Gauge
Mounting instructions:
The Feed-through terminals and PE terminals of the A-series are suitable for application in enclosures in
atmospheres with flammable gases or combustible dust. For use in flammable gases these enclosures must
satisfy the requirements according to IEC/EN60079-0 and IEC/EN60079-7. For use in combustible dust these
enclosures must satisfy the requirements according to IEC/EN60079-0 and IEC/EN60079-31.
Regarding the use of accessories the instructions of the manufacturer must be followed.
Schedule of Limitations:
Note:
If smaller cross sections than the rated cross section are used, the belonging lower current has to be laid down
in the IECEx/EC-Type Examination Certificate of the complete apparatus.
Information for further cross-connector arrangements will be provided on request.
A - Continuous no difference between one or two cross connections
- Rated voltage
Technical data according to IEC/EN 60079-7 (increased safety "eb"):
Version: A2C 35; D1395326 Index: 00 Date: 10.2019