READ CAREFULLY AND RETAIN FOR FUTURE REFERENCES INSTALLER’S MANUAL Sensor Control BT WV-SCBT Wave Home Solutions 2421 Long Beach Road Oceanside, NY 11572 Tel: 1-800-293-9577 e-mail: info@wavehomesolutions.com Site: www.wavehomesolutions.com Nov2/2009 MP 100933 Rev.
DESCRIPTON OF UNITS MODEL NO. WV-SCBT BASEMENT 1800 sq. ft. SPECIFICATIONS Sensor Control BT Model No.: WV-SCBT Height: Variable, 85.5’’ to 97.5’’ (85 ½’’ to 97 ½’’) Width: 11.25’’ (11 ¼’’) Depth: 7.625’’ (7 5/8’’) Airflow: Low: 40 CFM Medium: 130 CFM High: 230 CFM 0.28 A / 115VAC /1 Phase / 60Hz UNIT MODEL WV-SCBT IS DESIGNED SOLELY FOR BASEMENT INSTALLATIONS PERFORMANCE RESULTS ARE MAXIMIZED WHEN THE BUILDING IS OCCUPIED.
INSTALLATION GUIDELINES SUMMARY OF KEY INSTALLATION FACTS – EXTREMELY IMPORTANT ! Unobstructed airflow and adequate replenishment air are essential for proper performance of the unit. • • • • • • Unit must be installed at floor level – no higher than 3” from floor. Replenishment air has to flow from upstairs into the basement or crawl space. (This does not apply for slab homes and condos). Do not allow the option of leaving the stairwell door open.
REPLENISHMENT AIR TO BASEMENT FROM UPSTAIRS OF HOME • The damp air exhausted by the Sensor Control BT must be replaced by the warmer/drier air from the upper levels. If there is no open stairwell, the airflow is restricted from coming down; then install a passive return grille with 100 sq. inches either in the door, in the wall, or in the floor to allow unobstructed air downstairs.
• Make sure that no pipes, studs or wires are in the way. • Duct has to be dedicated and not combined with any other existing ductwork in operation. Seal well around the outside opening. SENSOR CONTROL BT INSTALLATION: Before installing your Sensor Control BT, make sure that you have the right model and accessories. For example, a WV-SCBT model is needed for an eight foot high basement. Make sure that the total length of the unit is taller than your cement wall.
FACTORS TO CONSIDER WHEN SELECTING UNIT LOCATION: The installation must be done in the basement or the lowest, wettest, coldest level of your dwelling. Try to find an outside wall to accommodate a 6¼” exit to the exterior of the house where no electrical wires or pipes are present Minimum distance to any source of heat should be 8 feet. Make sure that you do not install the unit in a boiler room.
B.) Outside the building, find your pilot hole. Using a hole saw and the pilot hole as a guide, drill a 6¼” hole at the exterior of the building. Brick or Concrete Wall: There are two ways of going through brick. The first method consists of using a hammer drill. Make holes (approximately 5/8”) with the hammer drill 1” apart through the brick in a circular shape outlining the 6 ¼” hole. Finish cutting the outer edge of the hole using a chisel. If a hammer drill is not available, a chisel can be used.
NOTE: If the unit has to be shorter than 86.5” cut the top of the bottom part. ATTACH FLEX, PIPE AND VENT TOGETHER: Attach the flex to the pipe with 24” tie wrap. Attach the vent to the 6” pipe with the ½ in screws provided. Avoid pushing against the flaps. From the outside, slide the pipe through the 6 ¼” hole. Insert four 2 inch screws to secure vent to the outside wall. Make sure the vent is not twisted from inserting the screws too tight and that the flaps are working properly.
FASTEN UNIT TO THE WALL: Leaving a 1 inch gap between the top of the unit and the ceiling (In case of a finished ceiling, leave a 1/8 inch gap between the top of the unit and the ceiling, avoiding any contact between the two) drill ¼” pilot holes through the lips of the unit and the wall. Apply the four plastic anchors on the wall with the help of a hammer. Secure the Sensor Control BT to the wall using the four 1 ¼ inch screws provided.
SET HUMIDITY CONTROL AND EXHAUST CONTROL: Refer to the “Operating Instructions” Manual included with the unit to change speed and dehumidistat settings: Also refer to the “Quick Reference Guide” sticker on the side of the unit for a reminder of the Sensor Control BT’s basic functions. NOTE: After plugging unit in, advise customer to let it run uninterrupted for 2 hours. This will allow unit to read and adjust the settings to the air in basement.
PLUG IN THE UNIT: Plug the unit into any 115V outlet. Note: A grounded extension cord with a maximum length of 10 feet may be used if necessary.
SECTION B Installation situations to be aware of: PROTRUDING WALL OR BASEBOARD: In this situation, block or insert spacer on the back of the unit to be able to securely fasten it to the wall. It is essential to have the bottom of the unit no higher than 3 inches off the floor. NOTES ABOUT COLD SURFACES: • IMPORTANT: Lower temperature means higher relative humidity and lower dew point, when compared to the same amount of water molecules in the air at higher temperature.
NOTE ABOUT CRAWL SPACE & BASEMENT COMBINATION: Depending on the square footage, the Sensor Control BT will be able to reduce the problems in the crawl space and the basement. The unit should be installed in the basement , adjacent to the crawlspace. An opening of at least 100 sq. inches in the adjoining wall, not higher than 4 inches above ground level of the crawl space, will allow for the air to be drawn out of the crawl area into the Sensor Control BT.
FOR TECHNICAL ASSISTANCE Do not attempt to service the Sensor Control BT yourself. If you are not sure about certain functions, call our qualified representative at 1-800-293-9577. WHAT NOT TO DO WHEN INSTALLING A WV-SCBT DO NOT INSTALL WV-SCBT MORE THAN 3 INCHES OFF THE FLOOR NOT MORE THAN ONE TURN WITH DUCT AND DUCTWORK SHOULD NOT BE LONGER THAN 3 FEET IN TOTAL.
DO NOT INSTALL WV-SCBT NEXT TO REPLENISHMENT AIR SUPPLY. DO NOT DUCT INTO EXISTING EXHAUST DUCTS OR CHIMNEY. DO NOT PLACE WITHIN 8 FT OF COMBUSTION APPLIANCE.