Datasheet

857-810
3
242
JUMPFLEX
®
Transducers
Temperature transducer for thermocouples of types J and K
<_________ 94 mm/3.68 in _________> 6 mm/0.23 in
<_________ 96 mm/3.76 in _________>
____________
_>
_>
OUT
IN
POWER
5
6
1
2
3
4
7
8
OUT+
GND 1
Us+
GND 2
TC+
TC
Configuration via:
DIP Switches
Short description:
The 857-810 Thermocouple Temperature Transducer is suitable for the connection of type
J and K thermocouples. On the output side, the thermocouple temperature transducer
converts the temperature signal into an analog standard signal.
Characteristics:
For thermocouples of type J and K
Cold junction compensation (on/off)
Calibrated scale switching
Sensor's wire break
Measuring range underflow/overflow
Clipping capability allows analog standard signal limitation to upper range values
Safe 3-way isolation with 2.5kV test voltage to EN 61140
Description
Item No.
Pack.
Unit
JUMPFLEX
®
transducers, for DIN 35 rail 857-810 1
Temperature transducer for thermocouples of types J and K
Technical Data
Configuration:
Configuration DIP switches
Input:
Input signal Thermocouples
Sensor types Thermocouples of types J and K
Temperature range Type J: -150 °C ... +1200 °C
Type K: -150 °C ... +1350 °C
Output:
Output signal 0 ... 20 mA, 4 ... 20 mA,
0 ... 10 V, 2 ... 10 V,
0... 5 V, 1 ... 5 V,
0 ... 10 mA, 2 ... 10 mA
Load impedance ≤ 600 Ω (Out = mA)
≥ 2 kΩ (Out = V)
Cold junction compensation on / off (default: on)
Cold junction error 3 K (typ. 2 K )
Step response 60 ms without cold junction compensation/
120 ms with cold junction compensation
General specifications:
Voltage supply V
S
24 V DC
Supply voltage range 16.8 V ... 31.2 V
Current consumption at 24 V DC ≤ 40 mA
Min. measuring span 100 K (configurable)
Transmission error ≤ 0.1 % at max. measuring span (Typ J, K)
Transmission error of set
measuring span (150 K / set measuring span [K]) %
Temperature coefficient ≤ 0.04 % /K
Technical Data
Environmental requirements:
Ambient operating temperature -25 °C ... +70 °C
Storage temperature -40 °C ... +85 °C
Safety and protection:
Test voltage (input/output/supply) 2.5 kV AC, 50 Hz, 1 min
Connection and type of mounting:
Wire connection CAGE CLAMP
®
S
Cross sections solid:
0.08 mm² ... 2.5 mm² / AWG 24 ... 14
fine-stranded:
0.34 mm² ... 2.5 mm² / AWG 22 ... 14
Strip lengths 9 ... 10 mm / 0.37 in
Dimensions and weight:
Dimensions (mm) W x H x L 6 x 96 x 94
Height from upper-edge of DIN 35 rail
Weight 44.7 g
Standards and approvals:
Conformity marking 1
r UL 508
r ANSI/ISA 12.12.01 Class I, Div. 2, Grp. ABCD, T4
Shipbuilding g
Accessories see pages 268 ... 271
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes 01.07.2013
Postfach 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Tel.: +49(0)571/887-0 E-Mail: info@wago.com
Fax: +49(0)571/887-169 www.wago.com

Summary of content (2 pages)