Datasheet

857-552
3
264
JUMPFLEX
®
Transducers
Rogowski Transducer
<_________ 94 mm/3.68 in _________> 6 mm/0.23 in
<_________ 96 mm/3.76 in _________>
____________
_>
_>
OUTIN
POWER
5
6
1
2
3
4
7
8
OUT+
GND 2
Us+
GND 3
RC1+
(GND 1)
RC2+
(GND 1)
DO
(GND 3)
GND 1
DO
Configuration via:
PC Configura-
tion Software
DIP Switches Smartphone
App
Short description:
The Rogowski transducer records RMS values from alternating currents via a Rogowski coil, con-
verting the input signal into a standard analog signal on the output side.
Features:
PC configuration interface
Supports different types of Rogowski coils
Digital switching output (configurable switching thresholds)
True RMS measurement (TRMS)
Configurable output signal
Configuration via DIP switch
Safe 3-way isolation with 2.5 kV test voltage acc. to EN 61140
No current bar interruption during installation
Measuring range overflow indication
Description
Item No.
Pack.
Unit
Height from upper-edge of DIN 35 rail 857-552 1
Rogowski-Messumformer
Technical Data
Configuration:
Configuration DIP switches, PC configuration software,
smartphone app
Input:
Input signal RC1 500 A: Sensitivity 10.05 mV *
RC2A 2000 A: Sensitivity 40.2 mV *
RC2B: Sensitivity 100 mV *
50/60 Hz sinusoidal and distorted
sinusoidal signals (e.g. leading edge and
Frequency range 16 Hz ... 1000 Hz
Response threshold < 1 % (of measuring range nominal value)
Output:
Output signal Voltage:
0 ... 5 V, 1 ... 5 V, 0 ... 10 V, 2 ... 10 V *
Current: 0 ... 10 mA, 2 ... 10 mA,
0 ... 20 mA, 4 ... 20 mA *
Overcurrent 0 % or +5 % (e. g. 10.5 V/21 mA)
Measuring range overflow/underflow 0 % or +2.5 %
Load impedance Current ≤ 600 Ω, Voltage ≥ 1000 Ω
Measuring procedure True RMS (TRMS)
Filter (T
10-90
) 600 ms (50 Hz)
Output - Digital
Max. switching voltage Supply voltage applied
Max. continuous current 500 mA
General specifications:
Voltage supply V
S
24 VDC
Supply voltage range 16.8 V ... 31.2 V
Current consumption at 24 V DC ≤ 40 mA
Resolution 500 A measuring range: 250 mA,
2000 A measuring range: 1000 mA
Measuring procedure True RMS (TRMS)
Response time 1.5 ms + signal cycle duration
Max. operating frequency < 2 kHz
Response time (T
10-90
) max. 60 ms
Technical Data
General specifications:
Linearity error ≤ 0,1 %
Temperature coefficient ≤ 0.01 %/K
Measurement error < 1 %
Line length < 3 m (to the Rogowski coil)
Environmental requirements:
Ambient operating temperature -25 °C ... +70 °C (at rated current)
Storage temperature -40 °C ... +85 °C
Safety and protection:
Test voltage
(input/output/supply) 2.5 kV AC, 50 Hz, 1 min.
Connection and type of mounting:
Wire connection CAGE CLAMP
®
S
Cross sections solid: 0.08 mm² ... 2.5 mm² / AWG 28 ...
14
fine-stranded: 0.34 mm² ... 2.5 mm² /
AWG 22 ... 14
Strip lengths 9 ... 10 mm / 0.37 in
Dimensions and weight:
Dimensions (mm) W x H x L 6 x 96 x 94
Height from upper-edge of DIN 35 rail
Weight 36.2 g
Standards and approvals:
Conformity marking 1
r UL 508 (pending)
r ANSI/ISA 12.12.01 (pending)
Shipbuilding g (pending)
Accessories Rogowski Coils:
RT 500 (1.5 m): 855-9100/500-0000
RT 500 (3 m): 855-9300/500-0000
RT 2000 (1.5 m): 855-9100/2000-0000
RT 2000 (3 m): 855-9300/2000-0000
( * Additional setting options via PC configuration software or smartphone app)