Datasheet

857-550
3
262
JUMPFLEX
®
Transducers
Current transducer AC/DC 0 ... 1 A, 0 ... 5 A
<_________ 94 mm/3.68 in _________> 6 mm/0.23 in
<_________ 96 mm/3.76 in _________>
____________
_>
_>
OUTIN
POWER
5
6
1
2
3
4
7
8
OUT+
GND 2
Us+
GND 3
IN 1A
(GND 1)
IN 5A
(GND 1)
DO
(GND 3)
GND 1
DO
Configuration via:
PC Configura-
tion Software
DIP Switches Smartphone
App
Short description:
The current transducer measures both 0–1 A and 0–5 A AC/DC currents, while conver-
ting the input signal to a standard analog signal at the output.
Features:
PC configuration interface
True RMS measurement or arithmetic mean value
Digital switching output (configurable switching thresholds)
Switchable filter function
Switching between measuring ranges is calibrated
Safe 3-way isolation with 2.5 kV test voltage acc. to EN 61140
Extremely fast response times
Measuring range overflow indication
Description
Item No.
Pack.
Unit
JUMPFLEX
®
Transducer, for DIN 35 rail 857-550 1
Current transducer
Technical Data
Configuration:
Configuration DIP switches, PC configuration software,
smartphone app
Input:
Input signal 0 ... 1 A AC/DC; 0 ... 5 A AC/DC *
Input resistance 10 mΩ (5 A); 47 mΩ (1 A)
Frequency range 16 Hz ... 400 Hz
Response threshold < 0.5 % (of measuring range nominal
Current carrying capacity 2 x I
N
(continuous)
Output:
Output signal Voltage:
0 ... 5 V, 1 ... 5 V, 0 ... 10 V, 2 ... 10 V *
Current:
0 ... 10 mA, 2 ... 10 mA,
0 ... 20 mA, 4 ... 20 mA *
Load impedance ≤ 600 Ω (I output) **
≥ 2 kΩ (U output)
** Temperature range restrictions may
occur.
Filter (T
10-90
) 260 ms (DC), 600 ms (AC 50 Hz)
Output - Digital
Max. switching voltage Supply voltage applied
Max. continuous current 500 mA (up to 60 °C)
100 mA (60 °C ... 70 °C)
General specifications:
Voltage supply V
S
24 VDC
Supply voltage range 16.8 V ... 31.2 V
Current consumption at 24 V DC ≤ 40 mA
Measuring procedure Arithmetic mean value *
True RMS measurement (TRMS)
Response time 1.5 ms + signal cycle duration
Max. response time 60 ms
Min. measuring span 2 mA ... 1 A; 4 mA ... 5 A
Technical Data
General specifications:
Transmission error ≤ 0.1 % typ. (≤ 0.4 % max.)
Temperature coefficient ≤ 0.01 % /K
Linearity error < 0,5 % (of measuring range nominal
Environmental requirements:
Ambient operating temperature -25 °C ... +70 °C (at nominal current)
Storage temperature -40 °C ... +85 °C
Safety and protection:
Test voltage (input/output/supply)
2.5 kV AC, 50 Hz, 1 min.
Connection and type of mounting:
Wire connection CAGE CLAMP
®
S
Cross sections solid:
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
fine-stranded:
0.34 mm² ... 2.5 mm² / AWG 22 ... 14
Strip lengths 9 ... 10 mm / 0.37 in
Dimensions and weight:
Dimensions (mm) W x H x L 6 x 96 x 94
Height from upper-edge of DIN 35 rail
Weight 50 g
Standards and approvals:
Conformity marking 1
r UL 508
r ANSI/ISA 12.12.01 (pending)
Shipbuilding g
Accessories Plug-in current transformers: 855 Series
see pages 268 ... 271
( * Additional setting options via PC configuration software or smartphone app)
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes 01.07.2013
Postfach 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Tel.: +49(0)571/887-0 E-Mail: info@wago.com
Fax: +49(0)571/887-169 www.wago.com