Cut Sheet

Fortsetzung nächste Seite ›› Stand: 14.10.2022 Seite1/6
https://www.wago.com/788-701
Solid-state relay module; Nominal input voltage: 24 VDC; Output voltage range: 3 …
30 VDC; Limiting continuous current: 5 A; 2-wire connection; Red status indicator;
Module width: 15 mm; gray
| : 788-701
:gray
Dimensions in mm
Current-carrying capacity curve
Notes
NoteOptocouplers and solid state relays are designed for use in signal processing networks,
which are not supplied by the low-voltage power supply networks.
.
T echnical data
Control circuit
Nominal input voltage U
N
DC 24 V
Input voltage range (low level)DC 0 … 2.5 V
Input voltage range (high level)DC 15 … 30 V
Nominal input current at U
N
9.3 mA
.
Load circuit
Circuit type2-wire connection
Limiting continuous current5 A
Nominal output voltageDC 24 V
Output voltage rangeDC 0 … 30 V
Voltage drop≤ 0.3 VDC
Turn-on time≤ 50 µs
Turn-off time≤ 600 µs
Switching frequency≤ 100 Hz
.