Data Sheet

Continued on next page Version 11.03.2022 Page1/6
https://www.wago.com/787-872
Features:
Lead-acid, absorbed glass mat (AGM) battery module for uninterruptible power supply (UPS)
Can be connected to both 787-870 or 787-875 UPS Charger and Controller, as well as to the 787-1675 Power Supply with integrated UPS charger
and controller
Parallel operation provides higher buffer time
Built-in temperature sensor
Mounting plate installation via continuous DIN-rail
Battery control (from manufacturing no. 213987) detects both battery life and battery type
Lead-acid AGM battery module; 24 VDC input voltage; 40 A output current; 7 Ah ca
pacity; with battery control; 10,00 mm²
Data sheet | Item number: 787-872
Notes
NoteFor parallel connection, please switch battery capacity setting to “OFF” in the UPS char
ger and controller.
.
T echnical data
Input
Nominal input voltage U
i nom
DC 24 V
.
Output
Nominal output voltage U
o nom
DC 24 V
Nominal output current I
o nom
40 A
.