Datasheet

750-645
1
287
1.7
2-Channel Vibration Velocity/Bearing Condition Monitoring VIB I/O
Delivered without miniature WSB markers
DO1 DO2
13
14
750-645
+AI1
+AI2
-AI1
-AI2
S
S
Sys. ok
Alarm 1
Warn 1
Error 1
DO 1
(Sys. ok)
+AI 1
(LD)
Data contacts
Alarm 2
Warn 2
Error 2
DO 2
(Alarm)
-AI 1
(LD)
+AI 2
(LD)
-AI 2
(LD)
Power jumper contacts
DO 2
Alarm
DO 1
(Sys. ok)
0 V
24 V
+AI 1(LD)
-AI 1(LD)
-AI 2(LD)
+AI 2(LD)
750-645
1
2
3
4
5
6
7
8
The VIB I/O module is used for online monitoring of machine vibration.
The module collects the two most important parameters for machine condition
analysis: Vibration velocity and shock pulse.
Vibration velocity is a measure of the energy of the machine vibration and thus
a good indicator of the vibration force which affects the machine.
ISO 10816-3 gives guidelines for evaluation. The actual value of the measured
vibration velocity is divided into four different quality categories.
Evaluation of the bearing condition is based on high frequency shock pulses.
Shock pulses are short pulses that are induced by mechanical damage to the
rolling element or the contact surface.
The measured shock pulses are divided into three different categories that
describe the bearing condition: “good“, “restricted“, “bad“. Registration and
evaluation of the measurement results in a trend curve which allows detection
of damage at an early stage.
The use of a special Tandem-Piezo sensor allows measurement of machine
vibration and high frequency shock pulses at the same time.
Description
Item No.
Pack.
Unit
2AI/2DO VIB VRMS/SPM Multi 750-645 1
Accessories
Item No.
Pack.
Unit
Tandem-Piezo sensor 750-925 1
Miniature WSB Quick marking system
plain 248-501 5
with marking see pages 352 ... 353
Approvals
Conformity marking 1
r UL 508
Technical Data
Sensor inputs +AI1, -AI1, +AI2, -AI2
Number of inputs 2
Input ranges
Vibration velocity 0 ... 100 mm/s
Shock pulse -10 ... +80 db
SV
No. of outputs 2 (Alarm and System ok)
Configuration Alarm and warning threshold via process
image and I/O Check
Outputs 24 V DC 0.5 A short-circuit protected
Voltage via power jumper contacts 24 V DC (-15 % ... +20 %)
Current consumption typ. (KBUS) 30 mA
Isolation 500 V system/supply
Wire connection CAGE CLAMP
®
Cross sections 0.08 mm² ... 2.5 mm² / AWG 28 ... 14
Stripped lengths 8 ... 9 mm / 0.33 in
Width 12 mm
Weight 52 g
EMC 1-Immunity to interference acc. to EN 61000-6-2 (2001)
EMC 1-Emission of interference acc. to EN 61000-6-3 (2001)
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes 18.05.2012
Postfach 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Phone: +49(0)571/887-0 E-Mail: info@wago.com
Fax: +49(0)571/887-169 www.wago.com

Summary of content (1 pages)