Datasheet

750-465, 750-466 / 753-465, 753-466
1
229
1.5
2-Channel Analog Input Module 0/4-20 mA
Single-ended (S.E.)
Fig. 750 Series/Technical data see page 24/Delivered without miniature WSB markers
750/753 Series marking see pages 10 ... 11 / 12 ... 13
AI 2
Data contacts
Error AI 2
24 V
Shield
(screen)
Error AI 1
Function AI 1
AI 1
Shield
(screen)
0 V
Function AI 2
Power jumper contacts
E1 E2
13
14
C
D
B
A
+
+
0V 0V
S S
750-465
AI 2
AI 1
Shield
(screen)
AI
Shield
(screen)
Logic
A
D
Function
I
0 V
24 V
24 V
0 V
270pF 10nF 10nF
Error
10nF
750-465
1
2
3
4
5
6
7
8
The analog input module powers the transducers, receives transmitted analog
signals, and with electrical isolation, transmits the signals to the fieldbus.
The 24V supply for the field is derived from the module's power jumper
contacts.
The shield (screen) is directly connected to the DIN rail.
This input module can supply the voltage for 2-wire transducers.
Description
Item No.
Pack.
Unit
2AI 0-20mA S.E. 750-465 10
1)
2AI 0-20mA S.E. S5
2)
750-465/000-200 1
2AI 0-20mA S.E./T 750-465/025-000 1
(Operating temperature -20 °C ... +60 °C)
2AI 4-20mA S.E. 750-466 10
1)
2AI 4-20mA S.E. S5
2)
750-466/000-200 1
2AI 4-20mA S.E./T 750-466/025-000 1
(Operating temperature -20 °C ... +60 °C)
2AI 0-20mA S.E. (without connector) 753-465 1
2AI 4-20mA S.E. (without connector) 753-466 1
1)
Also available individually
2)
Data format for S5 control with FB 251
Accessories
Item No.
Pack.
Unit
753 Series Connectors
753-110 25
Coding elements 753-150 100
Miniature WSB Quick marking system
plain 248-501 5
with marking see pages 352 ... 353
Approvals
Also see "Approvals Overview" in Section 1
Conformity marking 1
r UL 508
r ANSI/ISA 12.12.01 Class I, Div. 2, Grp. ABCD, T4 75x-465, -466,
750-46x/000-200
4 EN 60079-0, -15
EN 61241-0, -1
I M2 / II 3 GD Ex nA IIC T4 75x-465, 753-466,
750-46x/000-200
4 EN 60079-0, -11, -15 I M2 Ex d I
II 3 G Ex nA IIC T4
750-466*
750-466*
EN 61241-0, -1, -11 II 3 D Ex tD A22 IP6X T135°C 750-466*
* Permissible operating temperature: 0°C ... +60°C
Technical Data
Number of inputs 2
Power supply via system voltage DC/DC
Current consumption (internal) 75 mA
Input voltage (max.) 10V
Signal current 0 - 20mA (750-465, 753-465)
4 - 20mA (750-466, 753-466)
Input resistance < 220Ω / 20mA
Resolution 12 bits
Conversion time (typ.) 2 ms
Measuring error (25°C) < ± 0.2 % of the full scale value
Temperature coefficient < ± 0.01 % / K of the full scale value
Isolation 500 V system/supply
Bit width 2 x 16 bits data
2 x 8 bits control/status (optional)
Wire connection CAGE CLAMP
®
Cross sections 0.08 mm² ... 2.5 mm² / AWG 28 ... 14
Stripped lengths, 750/753 Series 8 ... 9 mm / 0.33 in
9 ... 10 mm / 0.37 in
Width 12 mm
Weight 52.5 g
EMC: 1 - immunity to interference acc. to EN 61000-6-2 (2005)
EMC: 1 - emission of interference acc. to EN 61000-6-4 (2007)
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes 18.05.2012
Postfach 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Phone: +49(0)571/887-0 E-Mail: info@wago.com
Fax: +49(0)571/887-169 www.wago.com