Datasheet

24V 0V
++
——
PE PE
01 02
750-323
RUN
BF
DIA
I/O RUN
I/O ERR
PROFIBUS-DP
x1
0
1
2
3
4
5
6
7
8
9
x10
0
1
2
3
4
5
6
7
8
9
ADDRESS
C
D
B
A
WAGO Kontakttechnik GmbH Postfach 2880 D-32385 Minden Tel.: 05 71/887-0 E-Mail: info@wago.com
Hansastr. 27 D-32423 Minden Fax.: 0571/887-169 Web: http://www.wago.com
PROFIBUS DP
Fieldbus Coupler
; EN 50170; 12 MBaud; digital signals
Max. no. of nodes 96 with repeater
Max. no. of I/O points ca. 6000 (depends on master)
Transmission medium Cu cable acc. to EN 50170
Max. length of fieldbus segment 100 m ... 1200m
(depends on the baud rate/on the cable)
Baud rate 9.6kBaud ... 12MBaud
Transmission time typ. 1 ms (10 nodes; 32 Is, 32 Os per node)
max. 3.3 ms
Buscoupler connection 1 x D-SUB 9; socket
This buscoupler allows connection of the
WAGO I/OSYSTEM as a slave to the PROFIBUS DP
fieldbus.
The buscoupler is capable of supporting all digital bus
modules and automatically configures, creating a local
process image.
The local process image is divided into two data zones
containing the data received and the data to be sent.
The process data can be sent via the PROFIBUS DP field-
bus to the PLC, PC or NC for further processing, and
received from the field via PROFIBUS DP.
The data of the analog modules is stored in the process
image which is created automatically according to the
order in which the modules are connected to the buscoup-
ler. The bits of the digital modules are sent byte by byte
and added to the analog data. If the amount of digital
information exceeds 8 bits, the buscoupler automatically
starts with a new byte.
Note: For PROFIBUS applications please also order
GSD files.
Item-No. 750-910.
or
download it from: www.wago.com
System Data
750-323 1
Item-No. Pack.-unit
pcs
PROFIBUS DP 12 MBd/Digital
Description
UL E175199, UL508
UL E198726, UL1604
Class I Div2 ABCD T4A
KEMA 01ATEX1024 X
EEx nA II T4
Standard EN 50170
Conformity marking 1
Standards and Approvals
GSD files 750-910
Miniature WSB quick marking system pages 1.166 /167
Accessories
Status
voltage supply
-Power jumper
contacts
-System
Data contacts
Supply
24 V
0 V
Supply via
power jumper
contacts
24 V
0 V
Power jumper
contacts
Fieldbus
connection
D-Sub
Address
Address
Configuration