Installation and Operating Instructions

HTD-432 PG2 (915-0:025)/HTD-432 PG2
(868-0:025) /HTD-432 ME PG2 (868-
0:025) wireless heat detector
Installation and operating instructions
Read this instruction sheet thoroughly before installation and use of the HTD-432/HTD-432 ME PG2
Note: The reference to HTD-432 PG2 throughout this manual is also applicable to the other
models unless stated differently.
Introduction
The HTD-432 PG2 is a wireless heat detector with a fixed temperature, a rate of rise heat
sensor, and an internal piezoelectric alarm. The following versions are available:
Frequency (MHz)
Version
915
HTD-432 PG2 (915-0:025)
868
HTD-432 PG2 (868-0:025)
868
HTD-432 ME PG2 (868-0:025)
Compatible devices
This detector is compatible with UL/ULC Listed DSC
Control Panels and Qolsys IQ Panel 2+. For UL/ULC
installations use this device only in conjunction with
compatible IQ2 wireless receivers and PowerG
receivers. Transmissions occur at approximately 915
MHz (912 MHz to 919 MHz).
Operation
During normal operation, the green LED flashes every 12 seconds.
The detector goes into alarm when the heat level exceeds 135 ºF / 57.5 ºC and automatically
restores when the heat level falls below the threshold. The detector also goes into alarm
when the temperature rapidly increases over a short period of time. During an alarm, the
LED flashes once per second and the sounder emits the evacuation temporal pattern.
Detector trouble
If the detector has a general fault, the yellow LED blinks once every four seconds and
emits a chirp every 48 seconds. After four hours, the panel displays a fire trouble message.
Table: Detector and Status Indication
Status
LEDs
Sounder
Normal
Green flash every 12 seconds
Off
Heat Alarm
Red flash every 1 second
ANSI S3.41 temporal 3
Heat Test
Red flash every 1 second
ANSI S3.41 temporal 3
Test Alarm
(button
press)
Red flash every 1 second
ANSI S3.41 temporal 3
Detector
Trouble
Yellow flash every 4 seconds
One chirp every 48 seconds
Low Battery
Yellow flash every 12 seconds
One chirp every 48 seconds
(press button to hush for 12 hours)
Power-up
Red, yellow, green, flash sequence
One chirp at the end of the power-up
sequence
Tamper
Red, yellow, green flash sequence every
12 seconds
Off

Summary of content (10 pages)