User's Manual
Table Of Contents
- Viconics
- Part
- Numbers
- 1. (None): No function will be associated with the input
- 4. (Filter): a backlit flashing Filter alarm will be displayed on the thermostat LCD screen when the input is energized. It can be tied to a differential pressure switch that monitor filters
- 5. (Service): a backlit flashing Service alarm will be displayed on the thermostat LCD screen when the input is energized. It can be tied in to the AC unit control card, which provides an alarm in case of malfunction.
- 1. (None): No function will be associated with the input
- 2. (COC/NH) Change over dry contact. Normally Heat: Used for hot / cold water change over switching in 2 pipe systems.
- Contact closed = Cold water present
- Only used and valid if system is setup as 2 pipes. Parameter ( Pipe No ) set as 2 pipes.
- 3. (COC/NC) Change over dry contact. Normally Cool: Used for hot / cold water or air change over switching in 2 pipe systems.
- Contact closed = Hot water present
- Only used and valid if system is setup as 2 pipes. Parameter ( Pipe No ) set as 2 pipes.
- 4. (COS) Change over analog sensor: Used for hot / cold water or air change over switching in 2 pipe systems.
- Only used and valid if system is setup as 2 pipes. Parameter ( Pipe No ) set as 2 pipes.
- 5. (SS) Supply air sensor monitoring: Used for supply air temperature monitoring.
- Only used for network reporting of the supply air temperature. Has no internal function in the thermostat.
- Range is: 0 to 500
- This parameter (Personal Area Network Identification) is used to link specific thermostats to a single specific Viconics wireless gateway ( VWG ) For every thermostat reporting to a gateway ( maximum of 30 thermostats per gateway ), be sure you set the SAME PAN ID value both at the gateway and the thermostat(s).
- Range is: 10 to 26
- Viconics recommends using only the 2 last channels ( 25-2575MHz and 26-2580MHz )
- Range is: 0 to 254
- This parameter / function is not currently supported by the wireless thermostats.
- BI1
- Default value = None
- (None): No function will be associated with the input
- (Filter): a backlit flashing Filter alarm will be displayed on the thermostat LCD screen when the input is energized. It can be tied to a differential pressure switch that monitor filters
- (Service): a backlit flashing Service alarm will be displayed on the thermostat LCD screen when the input is energized. It can be tied in to the AC unit control card, which provides an alarm in case of malfunction.
- UI3
- Default value = None
- (None): No function will be associated with the input
- (COC/NH) Change over dry contact. Normally Heat: Used for hot / cold water or air change over switching in 2 pipe systems.
- Contact closed = Cold water or air present
- Only used and valid if system is setup as 2 pipes. Parameter ( Pipe No ) set as 2 pipes.
- (COC/NC) Change over dry contact. Normally Cool: Used for hot / cold water or air change over switching in 2 pipe systems.
- Contact closed = Hot water present
- Only used and valid if system is setup as 2 pipes. Parameter (Pipe No ) set as 2 pipes.
- (COS) Change over analog sensor: Used for hot / cold water or air change over switching in 2 pipe systems.
- Only used and valid if system is setup as 2 pipes. Parameter (Pipe No ) set as 2 pipes.
- (SS) Supply air sensor monitoring: Used for supply air temperature monitoring.
- 2.0 Pipes, will limit the number of sequences of operation available from 0 to 3
PIR Ready VT7300 Series
24 Vac Low Voltage Fan Coil Thermostats
For Commercial and Lodging HVAC Applications
(Issue Date: June 16, 2008 – 028-0183_R3)
Product overview
The VT7300 PI thermostat family is specifically designed for fan coil control. The product
features a backlit LCD display with dedicated function menu buttons for simple operation.
Accurate temperature control is achieved due to the product’s PI proportional control
algorithm, which virtually eliminates temperature offset associated with traditional,
differential-based thermostats.
Models are available for On/Off, 3 point floating and analog 0 to 10 Vdc control and can
control up to three fan speed. Three additional inputs are also provided for monitoring and /
or various advanced functions.
All models feature configurable System and Fan button functions to meet all possible applications. They all contain
an SPST auxiliary switch that can be used to control lighting or auxiliary reheat.
The thermostats are also compatible with the new Viconics PIR cover accessories. Thermostats equipped with a
PIR cover provide advanced active occupancy logic, which will automatically switch occupancy levels from
Occupied to Stand-By and Unoccupied as required by local activity being present or not. This advanced
occupancy functionality provides advantageous energy savings during occupied hours without sacrificing occupant
comfort. All thermostats can be ordered with or without a factory installed PIR cover ( see ordering notes below ).
The additional following documents are available at:
www.viconics.com
• PIR application information and examples, are available on document: APP-PIR-Guide-Exx
• PIR cover installation information is available on document: PIR Cover Installation-Exx
• Information on the LON models (VT73xxX5000E), is available on document ITG-VT7300-PIR-LON-Exx
• Information on the BACnet models (VT73xxX5000B), is available on document ITG-VT7300-PIR-BAC-Exx
• Information on the Wireless models (VT73xxX5000W), is available on documents: ITG-VWG-40-BAC-Exx and LIT-VWG-40-SETUP-Exx
Models available
Viconics
Part
Numbers
VT7300A5000(X)
VT7300C5000(X)
VT7350C5000(X)
VT7305A5000(X)
VT7305C5000(X)
VT7355C5000(X)
VT7300F5000(X)
VT7350F5000(X)
VT7305F5000(X)
VT7355F5000(X)
Application
2 & 4
Pipes
On/Off
2 & 4 Pipes
Floating & On/Off
2 & 4
Pipes
On/Off
2 & 4 Pipes
Floating & On/Off
2 & 4 Pipes
Analog 0-10 Vdc
RH sensor
No No Yes No No Yes No Yes No Yes
Market Commercial / Institution Hotels / Lodging
Commercial /
Institution
Hotels / Lodging
Ordering Information Notes:
- (X) model number represents available communication options: X=none for Stand-alone, X=B for BACnet MS-TP, X=E for Echelon and X=W for Wireless
- Thermostats can be ordered with a factory installed PIR cover. Please use (5500) extension instead of the (5000) only extension.: Ex. VT7300C5500E.
- Thermostats ordered without a PIR cover can be retrofitted with a separate PIR accessory cover afterwards when required
Features and benefits
Features Benefits
• Models available with internal humidity sensing ⇒ Increased occupant comfort through dehumidification
• Advanced occupancy functions ⇒ Through the network or smart local occupancy sensing
• Ready for PIR accessory cover
⇒ Fully integrated advanced occupancy functionality with a
PIR accessory cover
• 3 configurable inputs ⇒ Adds functionality
• Configurable sequences of operation ⇒ Single model meets more applications
• Configurable fan functions button ⇒ Meets more applications with a single model
• Unique configuration setup utility ⇒ Minimizes parameter tampering
• Multi level lockable keypad ⇒ Tamper proof, no need for thermostat guards
• Auto Fan speed mode
⇒ Increased occupant comfort in cooling mode by reducing
humidity and offer less fan noise in all mode of operation
• Available for 24 Vac On/Off, Floating or Analog control ⇒ Meet advanced applications requirements
• Auxiliary output ⇒ Can be used for lighting or reheat
028-0183 R3_LIT-VT7300-PIR-E03.doc