Datasheet

UK T 020 7241 8787 | F 020 7241 8700 | sales@elandcables.com | www.elandcables.com
International T +44 20 7241 8740 | F +44 20 7241 8700 | international@elandcables.com
technicalspecification |
Veriex
®
CY PVC (YSLYCY) Control Cable
1 of 3
F
ind this product online: elandcables.com | Cables & Accessories
Veriflex | Veriflex CY PVC YSLYCY Control Cable
APPLICATION
Veriex
®
screened flexible connecting cables for
instrumentation and control equipment, for tooling machinery
production lines and, in flexible applications for free movement
without tensile load. Suitable for use in dry, moist and wet
rooms. These cables are not used for outdoor or underground
installation.
CY control cables are not suitable for fixed wiring applications
requiring compliance with the regulations set out in BS7671.
CHARACTERISTICS
Voltage Rating
300/500V
Test Voltage
4kV
Temperature Rating
Fixed: -4C to +80°C
Flexed: -5°C to +70°C
Minimum Bending Radius
Fixed: 4 x overall diameter
Flexed: 12.5 x overall diameter
CONSTRUCTION
Conductor
Class 5 flexible plain copper wires
Insulation
PVC (Polyvinyl Chloride)
Separator
PET (Polyester Tape)
Screen
TCWB (Tinned Copper Wire Braid)
Sheath
PVC (Polyvinyl Chloride)
Core Identification
Black with white number
From 3 cores: Black with white number + Green/Yellow
Colour-coded cores available upon request
Sheath Colour
Grey
STANDARDS
VDE 0207-363-3, VDE 0285-525-2-51, VDE 0285-525-1,
VDE 0285-525-2-11, VDE 0482-332-1-2, VDE 819-102 (TM54)
Flame Retardant according to IEC 60332-1-2
UK LABORATORY TESTED
This product is subject to the Quality Assurance protocols of The Cable Lab
®
,
a UKAS accredited ISO 17025 cable testing laboratory. Testing includes
vertical flame, conductor resistance, tensile & elongation, and dimensional
consistency, verified to published standards and approved product drawings.
ISO
9001
Quality
Management
ISO
14001
Environmental
Management
ISO
17025
UKAS Accredited
Cable Testing
Laboratory
OHSAS
18001
Occupational
Health and Safety
Management
REGULATORY COMPLIANCE
This cable meets the requirements of the Low Voltage Directive 2014/35/EU
and the RoHS Directive 2011/65/EU. RoHS compliance has been tested and
confirmed by The Cable Lab
®
as meeting the requirements of the BSI RoHS
Trusted Kitemark
TM
.
RoHS Trusted
KITEMARK
KM 634267
Eland Product Group:
V03