AVB32V02R Programmable Digital Thermostat Residential 7 Day Programmable • Up to 3-heat & 2-cool with Wi-Fi and Local API Owner’s Manual & Installation Instructions
CAUTION Follow the Installation Instructions before proceeding. Set the thermostat mode to “OFF” prior to changing settings in setup or restoring Factory Defaults. FCC Compliance Statement This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
Under Industry Canada regulations, this radio transmitter may only operate using an antenna of a type and maximum (or lesser) gain approved for the transmitter by Industry Canada. To reduce potential radio interference to other users, the antenna type and its gain should be so chosen that the equivalent isotropically radiated power (e.i.r.p.) is not more than that necessary for successful communication. Cet appareil est conforme avec Industrie Canada, exempts de licence standard RSS(s).
Fix at the end Table of Contents Installation Instructions..................................................................................1 Wire Connections.............................................................................................2 Thermostat Backplate.....................................................................................3 Dip Switch Settings.........................................................................................4 Connect to Wi-Fi.........................
Glossary of Terms Auto-Changeover: A mode in which the thermostat will turn on the heating or cooling based on room temperature demand. Cool Setpoint: The warmest temperature that the space should rise to before cooling is turned on (without regard to deadband). Deadband: The number of degrees the thermostat will wait, once a setpoint has been reached, before energizing heating or cooling. Differential: The forced temperature difference between the heat setpoint and the cool setpoint.
Installation Instructions Remove and Replace the old thermostat To install the thermostat properly, please follow these step by step instructions. If you are unsure about any of these steps, call a qualified technician for assistance. • Installation tools: Small flat blade screwdriver, Phillips screwdriver, wire cutters and wire strippers. • Make sure your Heater/Air Conditioner is working properly before beginning installation of the thermostat. • Carefully unpack the thermostat.
Installation Instructions Wire Connections If the terminal designations on your old thermostat do not match those on the new thermostat, refer to the chart below or the wiring diagrams that follow.
Installation Instructions The Thermostat Backplate CK1 D/H RS R G Y1 W O Y2 C To remove the thermostat backplate: Gently separate the display from the base by pulling from the center. IMPORTANT: This thermostat requires both R (24 VAC Return) and C (24 VAC Common) wires be connected to the backplate terminals to operate properly.
3 1 ELEC Ensure which switch is correct for your system. Dip switches are located on the back of the thermostat. ELEC HP B ELEC 3 2 HP B 1 3 ON O GAS 3 2 1 ON HP B ELEC GAS/EL O GAS ON B GAS/EL O GAS 2 O 1 GAS/EL HP This O dip switch B configures the thermostat to control a conventional gas/electric system or a heat pump.
Installation Instructions 1 Stage Heat, 1 stage Cool ELEC 3 2 HP B 1 GAS/EL ON O GAS 2 1 ON GAS/EL O GAS 3 Dip Switch Settings HP B ELEC CK1 D/H RS R G Y1 W O Y2 C Thermostat HVAC Equipment C W2 W1 O Y2 Condensate Switch (optional) Y1 G R 5
Installation Instructions 2 Stage Heat, 2 Stage Cool with wired remote sensor ELEC 3 2 HP B 1 GAS/EL ON O GAS 2 1 ON GAS/EL O GAS 3 Dip Switch Settings HP B ELEC CK1 D/H RS R G Y1 W O Y2 C Thermostat HVAC Equipment C Y2 W1 O W2 10KNTC Y1 G Remote Sensor (optional) R 6
Installation Instructions Single Stage Heat Pump with AUX Heat ELEC 3 2 HP B 1 GAS/EL ON O GAS HP B ELEC Thermostat D/H RS R G Y1 W O Y2 C Single Stage Unit, CXM Y W O G R C AL1 AL2 A SCALE 1 : 1 7 CK1 2 1 ON GAS/EL O GAS 3 Dip Switch Settings
Installation Instructions Dual Stage Heat Pump with AUX Heat and ClimaDry ELEC 3 2 HP B 1 GAS/EL ON O GAS HP B ELEC Two Stage Unit, DXM D/H RS R G Y1 W O Y2 C Thermostat DH Y Y2 W1 O/W2 G R C AL1 SCALE 1 : 1 8 CK1 2 1 ON GAS/EL O GAS 3 Dip Switch Settings
Connect to Wi-Fi Overview At minimum the first 3 tasks below must be completed to access your thermostat remotely from a browser. The 4th step is optional (highly recommended) and only is needed to access your thermostat(s) from a mobile device. These steps are: 1. Successful connection to a local Wi-Fi Access Point with internet access. 2. Confirm receipt of a Skyport generated verification email (this only occurs once during the Skyport account setup). 3.
Connect to Wi-Fi Overview Wi-Fi Setup The ClimateMaster Configurator App is needed to configure the Wi-Fi Settings of this thermostat • Download the ClimateMaster Configurator App from your mobile device’s App Store. • Open the ClimateMaster Configurator App - Choose the Mini thermostat picture. - Press and hold the FAN button of the thermostat for approximately 5 seconds to enter Wi-Fi setup screens. - Press the cooler button to setup Wi-Fi.
Connect to Wi-Fi Overview Join a Thermostat to Skyport If the thermostat is connected to the local Wi-Fi access point but not yet joined to an existing Skyport account, you may join the thermostat to the account by doing the following: 1. Log in to your Skyport account. 2. Select the “Location” you want to add a thermostat into or select the “Add a Location” link in the upper left-hand corner. 3. Select the “Add a New Thermostat” box. A screen will ‘pop-up’ asking for a six digit code. 4.
Front Panel 1 2 3 4 5 1 Backlit Display 2 Up/Warmer, Down/Cooler Buttons 3 MODE Button 4 FAN Button 5 Heat or Cool Indicator Heat = Red, Cool = Green 12
Display 4 2 1 1 1 4 3 1 Mode Indicators Selects the operational mode of the equipment. HEAT - Indicates the heating mode. COOL - Indicates the cooling mode. AUTO - Indicates the system will automatically changeover between heat and cool modes as the temperature varies. OFF - Indicates heating and cooling are turned off. 2 Clock with Day of the Week Indicates the current time and day. This clock is also used to program the time period schedules.
Display 6 8 5 7 5 5 Morning, Day, Evening & Night icons Indicates the part of the time period program. 6 Setup icon Indicates the thermostat is in the setup mode. 7 Fan icon When only the FAN icon is displayed, the fan is always on. If the FAN is not on the display, then the FAN is in Auto mode and will run only when necessary to heat or cool. 8 Locked icon Indicates the thermostat’s control buttons have been locked.
Basic Operation Selecting Your Desired Temperature (adjusting the setpoints) Auto-Changeover Mode Pressing the WARMER or COOLER buttons in Auto mode will adjust both the heat and cool setpoints simultaneously. To adjust the heat and cool setpoints individually, choose HEAT mode to adjust the heat setpoint, and COOL mode to adjust the cool setpoint, then return to AUTO mode.
Basic Operation Selecting Your Desired Humidity This thermostat is a perfect solution for reducing space humidity when using Climate Master two stage system with ClimaDry. To control dehumidification, be sure to set AUX USE (Setup Step 29) to ‘dehumidifier’. Conversely, you can control a humidifier by setting AUX USE (Setup Step 29) to humidifier’. You cannot control both. To adjust the humidify/dehumidify setpoint, first press/hold MODE for two seconds.
User Setup Table for button presses that are required for entering various menus TO ENTER MENUS Setup Steps Time Schedule Emergency Heat Lockout Buttons Calibration Wireless Setup Adjust Humidity BUTTON PRESS MODE & FAN for 5 seconds MODE & UP for 2 seconds UP & FAN for 2 seconds MODE, UP & DOWN for 2 seconds MODE & DOWN for 2 seconds, then MODE FAN for 5 seconds MODE for 2 seconds How to Change Settings in the Setup Screens To enter the setup screens, press the MODE button, and simultaneously press FAN
User Setup Setting the Clock and Day (setup step 1 & 2) When your thermostat is connected to Skyport Cloud Services, the time and day of the week are controlled by Skyport. There is no local adjustment, Skyport also adjusts the time for Daylight Savings Time as well. To set the time and day when not connected to Skyport; enter the setup screens by pressing the MODE button and simultaneously pressing the FAN button for 5 seconds. Clock (Setup Step 1) adjusts the clock.
User Setup: Backlight Operation Prog (Setup Step 4) Adjust to ON or OFF to allow the thermostat to be 7 day programmable Backlight (Setup Steps 5-8) Backlight (Setup Step 5) OFF - Backlight turns on only with a button press and turns off after 8 seconds. ON - Backlight is on continuously. Night Light (setup step 6) Selecting ON allows for turning off the backlight of the display during specific times of the day, usually at night.
User Setup: Fan Operation Display Fahrenheit or Celsius (Setup Step 9) This feature allows the thermostat to display temperature in Fahrenheit or Celsius. Minimum Heat/Cool Spread (Setup Step 10) This feature allows the user to set the minimum gap between Heat and Cool setpoints in AUTO mode. Select from 0 to 6 degrees.
User Setup: Setpoints Setpoint Limits (Setup Steps 11-13) When this feature is set to ON, the Heat and Cool Setpoints may be restricted to preset levels in Setup Steps 12 and 13. Maximum Heat Setpoint (Setup Step 12) Minimum Cool Setpoint (Setup Step 13) Available Modes (Setup Step 14) This setup step may restrict the use of this thermostat to: Heat only or, Cool only, or Heat and Cool, or Auto changeover operation.
User Setup Deadband Settings (Setup Steps 15-18) The Deadband is the number of degrees or minutes that the thermostat waits before it initiates the stages of heating or cooling. 1st Stage Deadband (Setup Step 15) Specifies the temperature difference between the room temperature and the desired setpoint before the first stage of heating or cooling is allowed to turn on.
User Setup Fan Off Delay (Setup Step 19) This feature allows the user to increase the cooling or electric strip heating efficiency of the system. The thermostat may be programmed to continue running the fan after a call for cooling or electric strip heating has been satisfied. This delay can be set for 0, 30, 60, 90, or 120 seconds. If set to 0, the fan will not run after a call for cooling or electric strip heating has been satisfied.
User Setup: Service Filter These setup steps allow the user to monitor FAN runtimes and program service alerts. Service alerts appear on the display. If the thermostat is joined to a Skyport account, then the user may be alerted by Skyport Cloud Services when to change the filter. Runtime hours or days appear in the clock display. FAN Press and hold FAN to clear reset runtime.
User Setup Comfort Recovery (Setup Step 24) With Comfort Recovery on, the thermostat will attempt to reach the Morning setpoint temperature at the exact time programmed into the thermostat. Comfort Recovery, only works when the thermostat enters the Morning period from the Night Period.
Dry Contact Operation Dry Contact Polarity (Setup Step 25) ‘Idle’ Dry Contact ‘Active’ Dry Contact ‘Idle’ Dry Contact Dry Contact Open (Normally Open) - The dry contact is open until the connected device closes the circuit. ‘Active’ ‘Idle’ Dry Contact Closed (Normally Closed) - The dry contact is closed until the connected device opens the circuit.
User Setup Wired Sensor Type (Setup Step 27) RETURN, OUTDOOR, SUPPLY = the sensor temperature is reported to Skyport to monitor only REMOTE = the sensor can be used for temperature control. Control to Sensor (Setup Step 28) Select LOCAL SENSOR ONLY to control to the temperature sensor inside the thermostat. Select WIRED SENSOR ONLY to control to a temperature sensor connected to the RS & R terminals of the thermostat backplate.
User Setup Aux Polarity (Setup Step 30) Select NORMAL OPENED or NORMAL CLOSED to specify the output voltage on D / H terminal when there is no dehumidify/humidify call. Cool to Dehum (Setup Step 31) For use with non-ClimaDry equipment. Set to ON to possibly allow cooling to turn on exclusively to lower the room humidity. Dehum Overcool Degrees Below Set Point (Setup Step 32) When Cool to Dehum set to ON, this step appears.
User Setup Dehum with Cool Only or Hum with Heat Only (Setup Step 34) Depending on how AUX USE (Setup Step 29) is configured, this step is used to control whether the equipment must be running before the D / H output can turn on. Humidifying for example, you might not want to turn on the humidifier unless the thermostat is calling for heat. Answering ON to this step will mean no dehumidifying unless cool is active or no humidifying unless heat is active.
User Setup Skyport (Setup Step 35) If set to ON, the thermostat may communicate and receive data from the Skyport Cloud Services. API (Setup Step 36) Turning on the local API allows 3rd party software to interface with the thermostat such as a home automation system. Time API (Setup Step 37) Only appears when prior step for Local API is set to ON. This step allows the internal clock to be altered using the API. NOTE: It is permissable to enable both Skyport and the local API at the same time.
User Setup Locking/Unlocking the Keypad To prevent unauthorized use of the thermostat, the front panel buttons may be disabled. To disable, or ‘lock’ the keypad, press and hold the MODE button. While holding the MODE button, press the WARMER and COOLER buttons together, for two seconds. The icon will appear on the display, then release the buttons. Press all three buttons in the order outlined for keypad lockout MODE COOLER WARMER MODE To unlock the keypad, press and hold the MODE button.
Programming a Daily Schedule Programming a Daily Schedule - To enter MODE Time Period Programming screens, Press and hold MODE and UP until the scrolling prompt appears. Select Day of Week to program - Press the WARMER or COOLER buttons to choose the day of the week. Press MODE to advance to the next step. This thermostat features four programmable time periods per 24 hour day: Morning, Day, Evening, and Night. The start time for each time period is adjustable.
Programming a Daily Schedule Continued Select Morning Cool Setpoint - Press the WARMER or COOLER buttons to adjust the cool setpoint desired. This step will appear if Cool or Auto Mode was selected in the step where the Morning mode is specified. Press MODE to advance to the next step. Select Morning Heat Setpoint - Press the WARMER or COOLER buttons to adjust the heat setpoint desired. This step will appear if Heat or Auto Mode was selected in the step where the Morning mode is specified.
About Advanced Features & Operation DEADBAND OPERATION - Controls heat pump up to three Heat and two Cool stages and heat/cool up to two heat and two cool stages. The 1st Stage of heat or cool is turned on when: (A) The temperature spread from the setpoint is equal to or greater than: the setpoint plus the 1st stage deadband (Setup Step 15). This 1st stage deadband is adjustable from 1-6 degrees and the default is two degrees.
About Advanced Features & Operation Cooling Heating Deadband db 3 (non-adj. 2˚) 3rd Stage strip heat turn on Deadband db 2 (adj. 0-10˚) 2nd Stage turn on Deadband db 1 (adj. 1-6˚ ) 1st Stage turn on DECREASE Deadband db 1 (adj. 1-6˚ ) Deadband db 2 (adj.
About Advanced Features & Operation Calibration Under normal circumstances it will not be necessary to adjust the calibration of the temperature sensor. If calibration is required, please contact a trained HVAC technician to correctly perform the following procedure. 1 MODE 2 MODE 3 MODE Place the thermostat in the OFF mode. Press and hold the MODE button. While holding the MODE button, press and hold the DOWN button for 5 seconds. All icons will appear on the display. Press the MODE button once.
About Advanced Features & Operation Factory Defaults If, for any reason, you desire to return all the stored settings back to the factory default settings, follow the instructions below. WARNING: This will reset all Time Period and Advanced Programming to the default settings. Any information entered prior to this reset will be permanently lost. 1 2 3 MODE MODE FAN Place the thermostat in the OFF mode. Press and hold the MODE button.
About Advanced Features & Operation (Continued) You now have the option of restoring the factory settings to just Wi-Fi (Wi-Fi), or just the thermostat (STAT), or both the thermostat and Wi-Fi (ALL). C. Select one of the above options using the Up or Down buttons. D. Press FAN for 2 seconds to restore the factory settings. FAN After factory settings are restored, the thermostat display will return to the “all icon” screen. 4 MODE To return to normal operation; Press the MODE button twice.
Advanced Setup Table FD = Factory Default Setting Step# Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Pg# Range CLOCK WEEKDAY SHOW CLOCK PROG BACKLIGHT NIGHTLT NIGHTLT START NIGHTLT STOP DISPLAY F/C MINIMUM HEAT/COOL SPREAD SETPOINT LIMITS MAX HEAT SETPOINT MIN COOL SETPOINT AVAILABLE MODES 1ST STAGE DEADBAND 2ND STAGE DEADBAND MINUTES BETWEEN 1st AND 2nd STAGE 2ND STAGE TURNOFF POINT FAN OFF DELAY FILTER RUNTIME FIL
Advanced Setup Table FD = Factory Default Setting Step# Description 32 33 34 35 36 37 Pg# Range DEHUM OVER-COOL 1 - 20 degrees FAN WITH DEHUM / FAN WITH HUM On, Off DEHUM WITH COOL ONLY / On, Off HUM WITH HEAT ONLY SKYPORT On, Off API On, Off TIME API On, Off TO ENTER MENUS...... BUTTON PRESS Setup Steps.................. MODE & OVERRIDE for 5 sec. Time Schedule............. MODE & UP for 2 seconds Emergency Heat.......... UP & OVERRIDE for 2 seconds Lockout Buttons...........
Warranty One-Year Warranty - This Product is warranted to be free from defects in material and workmanship.