Specifications

Installation
1061 S OUTH 800 E AST O REM, U TAH 84097 T ELEPHONE 801.229.2800 F ACSIMILE 801.224.0355 www.vantagecontrols.com
Overview
The Vantage ScenePoint with RadioLink is a wall box dimmer
that communicates to the Vantage Control System via a radio
transceiver. It is available in 1-4 load configurations that can be
mounted respectively in 1-4 gang back boxes. It is powered via
the local line feed. Before the dimmer is programmed, or if
communication is lost, the dimmer functions in default mode as
an independent dimmer. Once a button is programmed it can
perform any operation that a standard station supports
controlling its own or other loads. Any load on the dimmer may
be controlled by any other keypad, IR input, RS-232 or timed
event. It supports up to eight keypad buttons on a four gang
station, and an optional internal IR receiver.
Specifications
Description Specification
Station Dimensions
All Gangs Height = 4.3” -or- 109mm
All Gangs Depth = 1.38” -or- 35mm
One Gang Width = 2.5” -or- 63.5mm
Two Gang Width = 4.3” -or- 109mm
Three Gang Width = 6” -or- 154mm
Four Gang Width = 7.9” -or- 200mm
Faceplate Dimensions
All Gangs Height = 4.7” -or- 119.3mm
One Gang Width = 2.95” -or- 75mm
Two Gang Width = 4.68” -or- 118.8mm
Three Gang Width = 6.5” -or- 165mm
Four Gang Width = 8.31” -or- 211mm
Weight 2.9oz. -or- 82g (1-gang)
Voltage 120/240V ~ 60/50Hz
Max. Load Using
Default Power Profile
Single Gang = 5A (600W @ 120V)
- or -
Single Gang = 5A (1200W @ 240V)
See Load Ratings and Types below for
multi-gang
Max. Load Using
Relay Power Profile
All Gangs = 4A (480W @ 120V)
- or -
All Gangs = 4A (960W @ 240V)
Built-in Protection MOV surge suppression
Arc Suppression Zero Cross Built-in arc suppression
Lightning / Surge
Protection
High Voltage meets IEEE C62.41 (6000V &
3000A)
Low Voltage meets IEU-T K.20
Ambient Operating
Temperature
32 - 95°F -or- 0 - 35°C
Ambient Operating
Humidity
5 - 95% non-condensing
Cooling None required
Safety Off Switch Load by Load selectable
Status Indicator Microprocessor Status
Load Types
Incandescent, Magnetic Low Voltage,
forward phase Fluorescent dimming ballasts,
non-dimmable fluorescent ballasts (relay
mode only), Neon, Cold Cathode (lpf), and
HID
UL and CUL Listed Yes
FCC Yes
System Requirements
This station is compatible with InFusion Design Center software
or QLink software version 3.2 with Controller firmware version
6.2 or higher. For new projects it is recommended that firmware
and software be kept to the most current release.
Load Ratings and Types
In multiple gang stations no single load may exceed 5 amps, i.e.,
a two gang station may have one load at 400 Watts (3.3 amps)
and the second load at 600 Watts (5 amps) for a total of 1000
Watts. (See Removing Metal Tabs below.)
Number of
Gangs
Maximum Rating at
120V 50/60Hz
Maximum Rating at 240V
50/60Hz
1 5A, 600W 5A, 1200W
2 8.3A, 1000W 8.3A, 2000W
3 12.5A, 1500W 12.5A, 3000W
4 16.7A, 2000W 16.7A, 4000W
Minimum Load Required
Neutral Station No Neutral Station
15W 50W
*CAUTION: To reduce the risk of overheating and possible
damage to other equipment, do not install to control a
receptacle. The station is shipped in “DIMMING MODE”. To
change the default mode to RELAY change the Power Profile to
Relay in the Software. The Relay Mode change will not take
place until the system is programmed and the RF station is on
line.
Installation
Installation of Vantage products should be performed or
supervised by a Certified Vantage Installer. Turn the circuit
breaker off and make sure no voltage is present where the
ScenePoint Dimmer is mounted. Damage caused by failure to
disconnect power may void warranty and is a risk to the installer.
Connect the wires as follows: Black to LINE, White to NEUTRAL,
Red to LOAD, Green to structure’s safety GROUND. Before
turning the circuit breaker on, check to see that all connections
are correct (In particular, check to see that the correct wires have
been connected to “Line In” and “Load Out”).
Minimum Back Box Dimensions
Number of Gangs Minimum Back Box Dimensions
1 2.80”h x 1.80”w x 2.5”d
2 2.80”h x 3.60”w x 2.5”d
3 2.80”h x 5.40”w x 2.5”d
4 2.80”h x 7.20”w x 2.5”d
With these dimensions most standard back boxes that have the
receiving threads for the Dimmer mounting screw inside the box
will be adequate. Most back boxes where the receiving threads
are outside the box will be too small.
Mud Rings
If mud rings are specified on a job it is important to test the mud
rings for proper fit. Two gang mud rings, in particular, run
substantially smaller than back boxes and some brands are not
large enough for the station. The only solution is to test the fit
first.
No Neutral Installation
In its standard configuration, ScenePoint with RadioLink requires
a Neutral connection to operate. If operation without Neutral is
required, a “NO NEUTRAL” station must be specified when
designing the project in QLink. “NO NEUTRAL” stations are
configured to operate without a neutral connection and are
shipped from the factory without a neutral connection. When
installing a “NO NEUTRAL” station, a minimum 50 Watt load
must be connected to the first gang. “NO NEUTRAL” stations are
pre-programmed to allow the load on the first gang to be dimmed
from 0% to a maximum of 93% of full on. Relay mode must not
be used in the first gang of a “NO NEUTRAL” station.
RadioLink ScenePoint Dimmer