Uponor Smatrix Wave PULSE EN Installation and operation manual CD0000130
Table of contents 1 Copyright and disclaimer..................................................... 4 2 Preface................................................................................... 5 2.1 2.2 2.3 Safety instructions................................................................... 5 Limitations for radio transmission........................................... 5 Correct disposal of this product (Waste Electrical and Electronic Equipment).......................................................
13 Maintenance....................................................................... 67 13.1 13.2 13.3 Manual preventive maintenance.......................................... 67 Automatic preventive maintenance...................................... 67 Corrective maintenance....................................................... 67 14 Troubleshooting................................................................. 68 14.1 14.2 14.3 14.4 14.5 14.6 14.7 14.8 General.....................................
1 Copyright and disclaimer Uponor has prepared this installation and operation manual and all the content included solely for information purposes. The contents of the manual (including graphics, logos, icons, text, and images) are copyrighted and protected by worldwide copyright laws and treaty provisions. You agree to comply with all copyright laws worldwide in your use of the manual.
2 Preface This installation and operation manual describes how to install and operate the components of the system. Power Warning! 2.1 Safety instructions Warnings used in this manual The following symbols are used in Uponor ducumentation to indicate special precautions when installing andoperating any Uponor equipment: Warning! Risk of injury. Ignoring warnings can cause injury or damage components. Caution! Ignoring cautions can cause malfunctions.
3 Uponor Smatrix Wave PULSE system description Uponor Smatrix Wave is a control system designed for underfloor heating and cooling installations. Comfort, user friendliness and temperature control for each individual room of a home can be combined through the various components. 3.2 Example of a system The illustration below shows Uponor Smatrix Wave with installation and thermostats. 115v Power Supply 3.
3.3 Uponor Smatrix Wave PULSE components A C B D E 24V 24V 24V F Item G Part Number H Smatrix Part Description Uponor Smatrix Room Controller A3850050 Transformer module Main characteristics: A380265C Room controller with communication module • A380265A Room controller with antenna C A3801262 Expansion module D A3801265 Antenna, replacement part Integrated Dynamic Energy Management functions such as autobalancing (on by default).
Components of the room controller Integrate up to four room controller into one system. - The illustration below shows the room controller and its components. Options: • Cabinet or wall mounted (DIN rail or supplied screws). Components of the communication module The illustration below shows the communications module and its components.
Components of the thermostat: Expansion module The illustration below shows the thermostat and its components. B A C D The Uponor Smatrix Wave room controller can be expanded with six extra channels and actuator outputs using a Slave module.
Components of the relay module The illustration below shows the relay module and its components. A Item Description A Uponor Smatrix Wave M-161 B Mounting hardware B CD0000034 Uponor actuators Uponor actuators are mounted on top of the manifold valves and is operated using either on/off signals or pulse width modulation (PWM) signals.
Actuator management Cooling function Actuator management prevents too many actuators to be open at the same time in order to reduce the peak power need. Peak current can be reduced by delaying the opening of some actuators, as they use most current while being opened. The room controller operates the underfloor cooling installation according to customer needs.
Time delayed second stage cooling with relay module (requires communication module) Using the relay module (A3801263), and a digital thermostat, an optional second cooling stage can be connected to the Wave controller. Pump management (requires communication module) Caution! Changing status of the pump management and/or cooling allowed (in the Uponor Smatrix app, requires communication module) will set all relays to Not configured. Which will have to be configured again.
Room bypass (requires communication module) The system can use up to two rooms (per room controller), when in heating mode, as bypass to maintain minimum flow in the system. Rooms can be selected manually or by using the Time limit room bypass function. Time limit room bypass The time limit room bypass function prevents shorter run times than 30 minutes in the system.
4 Install Uponor Smatrix Wave PULSE 4.1 Installation procedure Uponor recommends following the process described below to guarantee the best possible installation results. 1. Prepare for installation, Page 16 2. Install Uponor Smatrix Wave PULSE room controller, Page 21 3. Install antenna or communication module (contains an antenna). • Install room controller antenna, Page 23 • Install communication module, Page 24 4. Connect optional expansion module, Page 22 5.
4.
Thermostats and actuators Option C • Thermostat #01 controls actuator channels 01a, 01b, 02a and 02b with the help of an option. • • Thermostat #03 controls actuator channels 03 to 05 with the help of an option. • Thermostat #06 controls actuator channels 06 and 07. • Thermostat #08 controls actuator channels 08 to 10 with the help of an option. Option D • External temperature sensor for heating/cooling switch. This option cannot be combined with a heating/cooling switch, in the same system.
Heating/cooling switch The heating/cooling switch is manually controlled through the Uponor Smatrix PULSE app (which controls the whole system), an external signal, the supply temperature, or depending on the indoor/outdoor temperature. It is used to switch the operation of the room controller between heating and cooling modes. 4.4 Network connectivity F API G A single external signal (if used) can be connected to up to four Wave room controllers at the same time, working in parallel.
Local Wi-Fi connection The Uponor Smatrix PULSE app (A) communicates with the room controller (C) via the local Wi-Fi network. • The mobile device connects to the same Wi-Fi router (E) as the communication module (B). • The communication module (B) and Wi-Fi router (E) are connected using either Wi-Fi or efternet. • The sub room controller (D) communicates via the master room controller (C). When is this method is used? • During normal operation when connected to the same local WiFi network.
5 Install Uponor Smatrix Wave PULSE room controller 5.1 Placement of room controller Attaching/detaching components Use the following guidelines when positioning the room controller: Caution! • The transformer module is heavy and might detach if the room controller is held upside down without the cover on. Position the room controller close to the manifold, just above if possible, and each manifold pair must have its own room controller.
5.2 Connect optional expansion module 5.3 Attach room controller to the wall Attach the room controller to the wall using a DIN-rail and/or screws and wall plugs. Using DIN rail 1 SI0000023 Note Only one expansion module extension is supported per room controller. 2 SI0000008 Snap the slave module to the room controller (recommended to do this on a flat surface or on a DIN-rail).
2. Connect the antenna cable Using screws and wall plugs mm 80 mm 110 SI0000009 Attach the room controller to the wall using screws and wall plugs. 5.4 Install room controller antenna SI0000004 Connect the antenna to the room controller. CD0000002 Caution! If the room controller is installed inside a metal cabinet, the entire antenna must be placed outside the cabinet. Caution! The antenna must be installed vertically for best coverage.
5.5 Install communication module 2. Attach removable back mount to the wall CD0000011 CD0000158 Caution! If the room controller is installed inside a metal cabinet, the entire communication module must be placed outside the cabinet. The communication module is delivered a kit with screws, wall plugs, and an optional back mount for DIN-rails, presenting several options of attaching the thermostat to the wall.
Using DIN-rail Using DIN-rail back mount 1 A SI0000163 Route cables to the communication module using the cable entries (A). 2 SI0000164 4. Connect the communication cable 1. Fasten the DIN rail to the wall using the screws and wall plugs. 2. Snap the optional communication module DIN-rail back mount to the DIN rail. Remove from DIN-rail 3 2 1 SI0000165 1. Use a screwdriver (or similar) and extend the springy plastic catcher from the communication module back mount. 2.
5.7 Connect electrical underfloor heating 6. Attach communication module 5 4 1 6 3 SI0000154 3 Attach the communication module to the removable back mount. 2 5.6 Connect actuators to room controller 24V AC A1 A2 230V 7 3 230V~ 50Hz 16(4)A L N 1 SI0000162 2 4 24V 1. 1 1 Connect the electrical underfloor heating mat/wire to a 24V AC relay dimensioned for the correct load. • SI0000029 Connect load and the electrical underfloor heating supply to a dry open contact. 2.
5.8 Connect input to room controller GPI Comfort/ECO switch (requires communication module) GPI GPI WD0000001 CD0000007 Note Note In systems with a communication module installed, the function of the GPI is selected in Installer settings during initial configuration, or in the System settings menu. If more than one room controller is available in the system, use the input on the master room controller. The room controller is equipped with a General Purpose Input (GPI) connection terminal.
General System Alarm (requires communication module) Caution! Changing status of the pump management and/or cooling allowed (in the Uponor Smatrix app, requires communication module) will set all relays to Not configured. Which will have to be configured again. Note In systems with multiple room controllers (master/sub configuration), all relays are initially set to Not configured. Which will have to be configured during installation. GPI Note The room controller cannot supply power for the output.
Circulation pump Relay function The room controller start the circulation pump (relay closed) when there is a demand for heating or cooling. If a communication module is connected and multiple room controllers are used the relay can be set to individal or common pump mode. Individual pump: Relay function is set on a room controller basis. One circulation pump per room controller is connected to relay 1.
Relay function 6. The boiler relay can be used to send a signal to either fire the heat source, or to power open a 2-port motorised zone valve positioned on the flow to the underfloor heating manifold. If the relay is used to power open a zone valve then, the volt free auxiliary contacts on the zone valve should be used to fire the heat source. Relay function Alternatively, the boiler relay can be used to send a demand signal to an electrically operated water temperature room controller.
Comfort/ECO (requires communication module) RELAY 2 (BOILER) Chiller (requires communication module) RELAY 1 (PUMP) WD0000007 WD0000015 Note Note This connection requires a dry contact sensing input in the chiller. This connection requires a dry contact sensing input in the other unit. Note Note This relay function requires a communication module, and must be set in Installer settings during initial configuration, or in the System settings menu.
Ventilation (requires communication module) 5.10 Connect room controller to AC power RELAY 2 (BOILER) 1. Check wiring WD0000006 SI0000037 Check that all wiring is complete and correct: Note This connection requires a dry contact sensing input in the ventilation unit. • Actuators • GPI connection (Heating/cooling switch) • Relay connections (Circulation pump) 2.
5.11 Test actuators 1. Enter forced mode SI0000048 Press the > button, while in run mode, to enter forced mode. The room controller is in run mode during regular operation. Otherwise press and hold the OK button for about 3 seconds to exit to run mode. 2. Select a channel 1 2 3 4 5 6 SI0000049 Use buttons < or > to move the pointer (LED flashes red) to a preferred channel. 3.
6 Install Uponor Smatrix Wave room thermostat 6.1 Uponor Smatrix Wave T-161 Connect external sensor to thermostat 1 Placement of thermostat 2 3 1.3–1.5 m SI0000045 Note For accurate temperature: attach the outdoor sensor to the north side of the building where it is unlikely to be exposed to direct sunlight. Do not place it close to doors, windows, or air outlets. SD0000002 • Select an indoor wall and a position 1.3 m to 1.5 m above the floor.
Start the thermostat Screw and wall plug 38 3 mm 1 2 SI0000022 SI0000104 Remove the plastic transportation strip from the battery to start the thermostat. Attach the thermostat to the wall using the screw and wall plug. Adhesive strip The thermostat use a single CR2032 3V button cell lithium battery which provides about 2 years of battery life, as long as it is positioned within radio range of the room controller. Ensure that the battery is correctly inserted in the thermostat.
3. Lock selected channel SI0000071 Note It is recommended to register all channels to the thermostat at the same time. Press the OK button to select the channel for registration. The LED for the selected channel starts flashing green. Select all channels to be registered to the thermostat and continue to the next step. 4. Register thermostat 5s SI0000077 Gently press and hold the registration button on the thermostat, release when the LED on the front of the thermostat starts flashing.
6.2 Uponor Smatrix Wave T-169 Placement of thermostat 1.3–1.5 m SD0000002 • Select an indoor wall and a position 1.3 m to 1.5 m above the floor. • Ensure that the thermostat is away from direct sunlight. • Ensure that the thermostat will not be heated through the wall by sunshine. • Ensure that the thermostat is away from any source of heat, for example television set, electronic equipment, fireplace, spotlights, and so on.
Connect external sensor to thermostat Start the thermostat 1 2 SI0000046 3 SI0000105 Note Remove the plastic transportation strip from the battery to start the thermostat. For accurate temperature: attach the outdoor sensor to the north side of the building where it is unlikely to be exposed to direct sunlight. Do not place it close to doors, windows, or air outlets.
Attach thermostat to the wall Adhesive strip 22 x 24 2 1 3 CD0000005 The thermostat is delivered in a kit with screws, wall plugs, and a wall bracket, presenting several options of attaching the thermostat to the wall. Wall bracket (recommended) V1 .0 38 mm SI0000010 1 3 Attach the thermostat to the wall using the wall bracket and adhesive strips. Register thermostat to room controller 2 1. Enter registration mode V1 .
5HJLVWHU WKHUPRVWDW V 6, 3UHVV DQG KROG ERWK DQG EXWWRQV RQ WKH WKHUPRVWDW XQWLO WKH WH[W &Q) FRQILJXUH DQG D FRPPXQLFDWLRQ LFRQ LV GLVSOD\HG 7KH VHOHFWHG FKDQQHO /(' LQ WKH URRP FRQWUROOHU WXUQV IL[HG JUHHQ DQG WKH UHJLVWUDWLRQ LV FRPSOHWH ([LW UHJLVWUDWLRQ PRGH V 6, 3UHVV DQG KROG WKH 2. EXWWRQ RQ WKH URRP FRQWUROOHU XQWLO WKH JUHHQ /('V WXUQ RII WR HQG UHJLVWUDWLRQ DQG UHWXUQ WR UXQ PRGH 7R XQUHJLVWHU DOUHDG\ UHJLVWHUHG WKHUPRVWDWV VHH Unregister room controller ch
7 Install Uponor Smatrix Wave relay module 7.1 Placement of relay module Use the following guidelines when positioning the relay module: • Position the relay module close to the remote component, just preferably above if possible (if water can drip from the component). Check the position of the 115 V AC power outlet, or if required by local regulations, the junction box. • Check that the relay module is protected from running or dripping water.
The relay module, registered to the sub room controller, can be set to one of the following combinations. A communication module is required for configuration. Relay 1 (PUMP) Relay 2 (BOILER) Circulation pump2) H/C Switch4) Circulation pump2) Dehumidifier5) Not configured Not configured Connect boiler 1) Function only available when Pump management is set to Individual or Common.
Connect dehumidifier (requires communication module) Connect chiller (requires communication module) WD0000014 WD0000013 Note Note This connection requires a dry contact sensing input in the dehumidifier. This connection requires a dry contact sensing input in the chiller. Note Note This relay function requires a communication module, and must be set in Installer settings during initial configuration, or in the System settings menu.
Connect Comfort/ECO (requires communication module) Connect ventilation unit (requires communication module) WD0000016 WD0000012 Note Note This connection requires a dry contact sensing input in the other unit. This connection requires a dry contact sensing input in the ventilation unit. Note Note This relay function requires a communication module, and must be set in Installer settings during initial configuration, or in the System settings menu.
6. Power up the relay module Note It is recommended to register at least one room thermostat before registering a system device. 1x Note Make sure all components are connected to the relay module before registering. 24VAC 2x 2. Move the channel pointer to the power LED SI0000040 Power up the relay module and count the number of flashes of LED 2 (blue) to ensure it is in normal run mode.
8. Exit registration mode Register fan coil connected relay module to thermostat Connect power 3s SI0000078 24VAC Press and hold the OK button on the room controller until the green LEDs turn off to end registration and return to run mode. 7.5 Use relay module to connect fan coils Caution! SI0000044 Uponor recommends connecting no more than 4 fancoils per room controller to maintain the regulating performance.
Register relay module to thermostat 4. ENTER PARAMETER EDIT MODE 09 NO SI0000124 SI0000092 Note If no button on the thermostat is pressed for about 8 seconds, while in a submenu, the current values will be saved and the software exits to the settings menu. About about 60 seconds later, it exits to run mode. Press OK to enter parameter edit mode (the parameter starts flashing). 5.
Connect power 8. EXIT SETTINGS MENU 24VAC 3s SI0000119 Press and hold the OK button for about 3 seconds to exit the settings menu. 7.6 Use relay module for time delayed two stage additional cooling (requires communication module) Ensure power is disconnected SI0000044 Connect the power cables from the relay module and cooling components to a 24 VAC power supply, or if required by local regulations, to a junction box.
Press and hold the OK button for about 3 seconds to exit the settings menu. 5. Register thermostat to relay module Register to a T-169 thermostat 1. Enter relay module registration mode 09 YES SI0000155 SI0000127 Press and hold the register button on the relay module until the LEDs on the module start flashing slowly. 2. Enter settings menu Use buttons or to change Int no to Int CNF. 6. Registration 09 09 NO 3s CNF SI0000125 SI0000114 Press and hold the OK button for about 3 seconds.
8 Install another Uponor Smatrix room controller in the system 8.1 Preparation Note 8.2 Register sub room controller to master room controller The room controller will time out after about 10 minutes of inactivity and revert to normal operation. The timer will be reset when a button is pressed or if a device has been registered to it. Note The room controller will time out after about 10 minutes of inactivity and revert to normal operation.
([LW UHJLVWUDWLRQ PRGH 6HOHFW FKDQQHO V 6, 6, 8VH EXWWRQV RU ! WR PRYH WKH SRLQWHU /(' IODVKHV UHG WR FKDQQHO 3UHVV DQG KROG WKH 2. EXWWRQ RQ WKH URRP FRQWUROOHU XQWLO WKH JUHHQ /('V WXUQ RII WR HQG UHJLVWUDWLRQ DQG UHWXUQ WR UXQ PRGH 7R XQUHJLVWHU DOUHDG\ UHJLVWHUHG VXE URRP FRQWUROOHU VHH Unregister room controller channels, Page 77 /RFN VHOHFWHG FKDQQHO 6, 3UHVV WKH 2.
9 Finishing installation 3 5 1 1 2 4 6 SI0000175 Make a complete check up of the installation: 1. Check that the thermostats, and thermostatic heads (if installed), are working correctly. Turn thermostat setpoints to maximum to obtain a heating demand and make sure that the actuators are running. 2. Set thermostats to the defined operating settings. 3. Close the covers of the room controller. 4. Attach thermostats to the wall. 5.
10 Operate Uponor Smatrix Wave PULSE room controller 10.1 Principle of operation The room controller operates the underfloor heating/cooling installation according to customer needs. Temperatures can be adjusted with thermostats located in each room, or if installed with the Uponor Smatrix PULSE app (requires communication module).
10.5 Room controller LEDs Registration mode If the Uponor Smatrix PULSE app (requires communication module) is not used, it is recommended to occasionally check the power LED on the room controller for alarms. The power LED flashes continuously for general alarms. Determine which thermostats are issuing alarms by removing the cover. If a channel LED is indicating an error, check the function and batteries of the registered thermostat. The room controller power LED is on (green) during normal operation.
5HVHW WKH FRQWUROOHU 8QUHJLVWHU D URRP FRQWUROOHU FKDQQHO (QWHU UHJLVWUDWLRQ PRGH V 6, 1RWH 0DNH VXUH WKH URRP FRQWUROOHU LV LQ UXQ PRGH ,I LW LV LQ UHJLVWUDWLRQ RU IRUFHG PRGH SUHVV DQG KROG WKH 2. EXWWRQ IRU DERXW VHFRQGV RU XQWLO WKH /('V WXUQ RII 1RWH V 6, 3UHVV DQG KROG WKH 2.
5. Unregister the channel 2. Move the channel pointer to the power LED 5s SI0000156 SI0000082 Use buttons < or > to move the pointer to the power LED (LED flashes red). Press the < and > buttons simultaneously until the LED for the selected channel starts flashing red (about 5 seconds). 6. Exit registration mode 3.
11 Operate Uponor Smatrix PULSE communication module 11.2 Communication module LEDs 11.1 Communication module layout The illustration below shows the parts of the thermostat.
12 Operate Uponor Smatrix Wave thermostats Uponor Smatrix Wave T-169 12.1 Thermostat type The illustration below shows the parts of the thermostat. Two types of thermostats, both analogue and digital, can be used in an Uponor Smatrix Wave system. A Analogue thermostats Uponor Smatrix Wave T‑161 Digital thermostats Uponor Smatrix Wave T-169 B The digital thermostats have a display relaying information to the user and buttons for control. 12.
Display layout Alarms The figure shows all possible symbols and characters that can be shown on the display: Run mode (default screen) The figure shows all possible symbols and characters that can be shown on the display: A B C D E B A CD0000080 Item C Item Icon B Faulty indoor temperature sensor CD0000078 Description B Alarm symbol C Temperature unit Faulty floor temperature sensor Faulty remote temperature sensor Faulty outdoor temperature sensor Change setpoint C Low battery indi
Control mode The figure shows all possible symbols and characters that can be shown on the display: A B C Button layout The figure below shows buttons used to operate the digital thermostats.
12.3 Start up 12.5 Digital thermostat functions Analogue thermostats Run mode The thermostat will perform a self test, for about 10 seconds, when starting up. The system will be blocked for input and the thermostat LED flashes during this period. During normal operation the thermostat is in run mode. While in run mode the display shows specific control mode information. Digital thermostats When starting up, the software version is shown in the display for about three seconds.
Room temperature sensor and outdoor temperature sensor 1. Room temperature (default) 2. Relative humidity 3. Outdoor temperature Uponor Smatrix Wave T-169 Uponor Smatrix Wave T-169 Thermostat function To enter the settings menu: Symbol Room temperature sensor Room temperature sensor and floor temperature sensor Remote sensor Room temperature sensor and outdoor temperature sensor Different types of information can be shown in the display when in a control mode.
CD0000100 Figure 3. Program P1 CD0000104 Figure 7. Program P5 CD0000101 Figure 4. Program P2 CD0000105 Figure 8. Program P6 Select scheduling program To select a scheduling program: 1. Press OK to enter parameter edit mode. 2. Use buttons - or + to select program. Select between: P1–P6, U (user defined program) and Off. 3. Press OK to confirm program selection and return to the settings menu.
Customise user defined program for a full week Note This method resets the current user defined program to factory defaults. To customise the user defined program: 1. Press OK to enter parameter edit mode. 2. Use buttons - or + to select program U. 3. Press and hold OK until day 1 and 00:00 appears on the display. 4. Press OK to switch the marked interval between Comfort ( and ECO mode ( ). 5. Use buttons - or + to move the marker (at the bottom of the display).
11 Room temperature calibration 07 Cooling allowed In this menu it is set whether cooling is allowed in the room or not. Default: 0.0 ˚C This menu is not visible if a communication module is connected to the system. The setting is then available in the Uponor Smatrix PULSE app. Setting range: -6.0 – 6.0 ˚C, 0.1 ˚C increments In this menu the room temperature shown in the thermostat display can be calibrated. See Change settings, Page 90, for how to change the setting.
14.7 Factory reset Uponor Smatrix Wave T-161 1 Note 2 Do not factory reset the thermostat if not absolutely needed. Note A factory reset removes the registration data from the thermostat. Factory reset sets all parameter values to default settings. 3 4 4.1 3.1 4.2 3.2 SI0000193 To factory reset the thermostat: 1. Remove the thermostat from the wall. 2. Remove the battery from the thermostat. 3. Press and hold the registration button on the thermostat while inserting the battery again. 4.
13 Maintenance 13.1 Manual preventive maintenance Warning! Do not use any detergents to clean the Uponor Smatrix components. The Uponor Smatrix room controller requires no preventive maintenance except cleaning: 1. Use a dry soft cloth to clean the components. 13.2 Automatic preventive maintenance The Uponor Smatrix room controller is equipped with an automatic exercise function. This function consists of a test run designed to prevent the pump and actuators from seizing up due to inactivity.
14 Troubleshooting 14.1 General This section describes general problems and alarms that can occur with the Uponor Smatrix system and describes solutions. A common cause of a problem though may be due to wrongly installed loops or mixed up thermostats.
All rooms are cold (or warm in cooling mode) ECO mode symbol shown • System in ECO mode Reduce the ECO setback value for the thermostat - - Reduce the General ECO setback value in the Uponor Smatrix PULSE app (requires communication module) - Check the registration status of the room controller - Check the room controller configuration Cancel temporary ECO The system is in cooling mode The system is in heating mode - • • Correct signal from external device needed Disturbing noise from the pum
The thermostat is faulty Uponor Smatrix Wave T-169 Channel LEDs in the room controller continue flashing Alarm symbols • The figure shows all possible symbols and characters that can be shown on the display: The thermostat is not correctly positioned - Check the placement of the thermostat so the signal is not shielded by another object • The room controller antenna is not correctly installed or positioned • The room controller antenna is installed inside a metal cabinet, or too close to other sh
• Force the thermostat to transmit by changing the temperature setpoint - Replace thermostat Try to find a new position for the thermostat and/or the antenna, or, if possible, move the shielding object RH control is activated in the Uponor Smatrix PULSE app (requires communication module).
No floor temperature limit settings available for the room where the thermostat is registered • Low radio signal • No floor temperature sensor is connected to the thermostat Low radio signal detected (sporadic communication with the connected unit). 1. Connect the floor temperature sensor to the thermostat This may be due to one of the following probable causes: 2. Remove the battery from the thermostat - The thermostat/thermostatic head is out of range 3. Wait about 30 seconds - 4.
The communication module has lost communication with Uponor cloud services Faulty external temperature sensor • This alarm will only be received as a push notification and/or SMS (if activated) to the mobile phone number registered to the customer account in Uponor cloud services. • Make sure the communication module is connected to an internet connected router, via either Wi-Fi or ethernet. - Make sure the communication module is connected to the room controller. - Restart the router if needed.
Faulty heating/cooling supply sensor Low average temperature • • An error has been detected with the heating/cooling supply sensor connected to the public thermostat. Average temperature in the system is lower than set limit (se Installer settings). - Check the connection of the heating/cooling supply sensor. The average temperature is calculated using selected rooms (activated in room settings). - Disconnect the external sensor and check it with an ohmmeter.
14.7 Contact the installer For installer contact information, see the installation report in the end of this document. Prepare the following information before contacting an installer: • Installation report • Drawings of the underfloor heating system (if available) • List of all alarms, including time and date 14.
15 Technical data 15.1 Technical data Thermostat T-161 and T-169 IP IP20, class III (IP: degree of inaccessibility to active parts of the product and degree of water) Max. ambient RH (relative humidity) 85% at 20 °C CE marking ERP IV Low voltage tests EN 60730-1* and EN 60730-2-9*** EMC (electromagnetic compatibility requirements) tests EN 60730-1 and EN 301-489-3 ERM (electromagnetic compatibility and radio spectrum matters) tests EN 300 220-3 Power supply 1 x CR2032 3V Voltage 2.4 V to 3.
Communication module R-208 Pollution degree 2 Software class A Operating temperature 0 °C to +45 °C Storage temperature -20 °C to +70 °C Wi-Fi connectivity 802.11 b/g/n @2.4Ghz Wi-Fi security WPA & WPA2 Radio frequency 912 MHz Transmitter duty cycle <1% Receiver class 2 Connection terminals RJ45 Ethernet connection (10/100BaseT) Room controller X-265 IP IP20, class II (IP: degree of inaccessibility to active parts of the product and degree of water) Max.
Cables Standard cable length Maximum cable length Wire gauge Floor sensor cable to thermostat 5m 5m 0.75 mm² Outdoor sensor cable to thermostat - 5m Twisted pair Cable from relay switch to room controller GPI input 2m 20 m Room controller: Up to 4.0 mm² solid, or 2.5 mm² flexible with ferrules Relay: 1.0 mm² to 4.0 mm² 15.3 Uponor Smatrix Wave PULSE room controller layout A B E C D Item Description A Transformer, 115 V AC 50 Hz power module F B Fuse (T5 F3.
15.4 Wiring diagram Uponor Smatrix Wave PULSE room controller GPI 2 GPI GPI > 40 cm RELAY 2 (BOILER) GPI 1 RELAY 1 (PUMP) GPI 3 WD0000019 Uponor Smatrix Wave PULSE slave module WD0000020 15.
Uponor Smatrix Wave PULSE room controller and slave module 476 mm 245 mm 140 mm 110 mm 110 mm 80 mm 72,5 mm 19 mm Communication module 19 mm 55 mm 48 mm 10 mm 110 mm 55 mm 60 mm 110 mm CD0000128 Thermostats Uponor Smatrix Wave T-161 56 mm 38 mm 56 mm 9 mm CD0000121 Uponor Smatrix Wave T-169 80 mm 38 mm 80 mm 9 mm 80 | Uponor Smatrix Wave PULSE | Installation and operation manual 110 mm 84 mm 55 mm
Uponor GmbH Industriestraße 56, D-97437 Hassfurt, Germany 1095344 04_2019_EN Production: Uponor/MRY Uponor reserves the right to make changes, without prior notification, to the specification of incorporated components in line with its policy of continuous improvement and development. www.uponor.