Assembly Instructions Chapter 3

4-6 kW UHF Translator Chapter 3, Installation and Setup Procedures
837B, Rev. 0 3-1
Chapter 3
Installation and Setup Procedures
There are special considerations that
need to be taken into account before the
837B can be installed. For example, if the
installation is completed during cool
weather, a heat-related problem may not
surface for many months, suddenly
appearing during the heat of summer.
This section provides planning
information for the installation and set up
of the translator.
3.1 Site Considerations
The Translator consists of three cabinet
assemblies, the Exciter Cabinet Assembly
and two Amplifier Array Assemblies. The
Exciter Cabinet Assembly requires an AC
Input of 208/240 VAC, Single Phase with
a rating of 20 Amps. Each of the
Amplifier Array Assemblies requires an
AC Input of 208/240 VAC, three Phase
with a rating of 55 Amps or Single Phase
with a rating of 100 Amps. Check that
the site has the voltage requirement
needed.
The 837B is designed and built to provide
long life with a minimum of maintenance.
The environment in which it is placed is
important and certain precautions must
be taken. The three greatest dangers to
the translator are heat, dirt, and
moisture. Heat is usually the greatest
problem, followed by dirt, and then
moisture. Over-temperature can cause
heat-related problems such as thermal
runaway and component failure. Each
amplifier tray in the translator contains a
thermal interlock protection circuit that
will shut down that tray until the
temperature drops to an acceptable level.
A suitable environment for the translator
can enhance the overall performance and
reliability of the translator and maximize
revenues by minimizing downtime. A
properly designed facility will have an
adequate supply of cool, clean air, free of
airborne particulates of any kind, and no
excessive humidity. An ideal environment
will require temperature in the range of
40° F to 70° F throughout the year,
reasonably low humidity, and a dust-free
room. It should be noted that this is
rarely if ever attainable in the real world.
However, the closer the environment is
to this design, the greater the operating
capacity of the translator.
The fans and blowers designed and built
into the translator will remove the heat
from within the trays, but additional
means are required for removing this
heat from the building. To achieve this, a
few issues need to be resolved. The first
step is to determine the amount of heat
to be removed from the translator room.
There are generally three sources of heat
that must be considered. The first and
most obvious is the heat from the
translator itself. The following example is
for a 5000 Watt Transmitter. The heat
can be determined by subtracting the
average power to the antenna (3225
watts) from the AC input power (20,000
watts). This number in watts (16,775) is
then multiplied by 3.41, which gives
57,202.75, the BTUs to be removed
every hour. 12,000 BTUs per hour equals
one ton; as a result, a 5-ton air
conditioner will cool a 5-kW transmitter.
The second source of heat is other
equipment in the same room. This
number is calculated in the same way as
the equation for BTUs. The third source
of heat is equally obvious but not as
simple to calculate. This is the heat
coming through the walls, roof, and
windows on a hot summer day. Unless
the underside is exposed, the floor is
usually not a problem. Determining this
number is usually best left up to a
qualified HVAC technician. There are far
too many variables to even estimate this
number without reviewing the detailed
drawings of the site that show all of the
construction details. The sum of these

Summary of content (10 pages)