Assembly Instructions Chapter 3

3-kW UHF Transmitter Chapter 3, Installation and Setup Procedures
835-3, Rev. 0 3-1
Chapter 3
Installation and Setup Procedures
There are special considerations that need to be taken into account before the 835-3
can be installed. For example, if the installation is completed during cool weather, a
heat-related problem may not surface for many months, suddenly appearing during the
heat of summer. This section provides planning information for the installation and set
up of the transmitter.
3.1 Site Considerations
The 835-3 transmitter requires two main AC input lines, a 3-phase 208/240 VAC, 60 Hz
input of at least 100 amp rating that connects to the amplifier cabinet assembly and a
single-phase 208/240 VAC, 60 Hz input of at least 40 amp rating that connects to the
exciter/driver assembly. Make sure that the proposed site has the necessary voltage
requirements.
The 835-3 is designed and built to provide long life with a minimum of maintenance.
The environment in which it is placed is important and certain precautions must be
taken. The three greatest dangers to the transmitter are heat, dirt, and moisture. Heat
is usually the greatest problem, followed by dirt, and then moisture. Over-temperature
can cause heat-related problems such as thermal runaway and component failure. Each
amplifier tray in the transmitter contains a thermal interlock protection circuit that will
shut down that tray until the temperature drops to an acceptable level.
A suitable environment for the transmitter can enhance the overall performance and
reliability of the transmitter and maximize revenues by minimizing down time. A
properly designed facility will have an adequate supply of cool, clean air, free of
airborne particulates of any kind, and no excessive humidity. An ideal environment will
require temperature in the range of 40° F to 70° F throughout the year, reasonably low
humidity, and a dust-free room. It should be noted that this is rarely if ever attainable
in the real world. However, the closer the environment is to this design, the greater the
operating capacity of the transmitter.
The fans and blowers designed and built into the transmitter will remove the heat from
within the trays, but additional means are required for removing this heat from the
building. To achieve this, a few considerations should be taken into account. The first
step is to determine the amount of heat to be removed. There are generally three
sources of heat that must be considered. The first and most obvious is the heat from the
transmitter itself. This can be determined by subtracting the average power to the
antenna (2100 watts) from the AC input power (10,000 watts). This number in watts
(15,900) is then multiplied by 3.41, which gives 54,200, the BTUs to be removed every
hour. 12,000 BTUs per hour equals one ton, so a 5-ton air conditioner will cool a 3-kW
transmitter that is vented into the room. If the air exhaust will be vented externally, a
1-ton air conditioner will be needed to properly cool the transmitter.
The second source of heat is other equipment in the same room. This number is
calculated in the same way as the equation for BTUs. The third source of heat is equally
obvious but not as simple to calculate. This is the heat coming through the walls, roof,
and windows on a hot summer day. Unless the underside is exposed, the floor is usually
not a problem. Determining this number is usually best left up to a qualified HVAC
technician. There are far too many variables to even estimate this number without
detailed drawings of the site showing all construction details. The sum of these three

Summary of content (7 pages)