How-To Guide Chapter 3

100 Watt High Band VHF Transmitter Chapter 3, Installation and Setup Procedures
420A, Rev. 0 3-1
Chapter 3
Installation and Setup Procedures
There are special considerations that
need to be taken into account before the
420A transmitter can be installed. For
example, if the installation is completed
during cool weather, a heat-related
problem may not surface for many
months, suddenly appearing during the
heat of summer. This section provides
information that will assist in planning for
the installation and set up of the
transmitter.
3.1 Site Considerations
The transmitter requires an AC input line
of 115 or 230 VAC with a rating of 10
amps. Make sure that the proposed site
for the transmitter has the voltage
requirements that are needed.
The 420A is designed and built to provide
long life with a minimum of maintenance.
The environment in which it is placed is
important and certain precautions must
be taken. The three greatest dangers to
the transmitter are heat, dirt, and
moisture. Heat is usually the greatest
problem, followed by dirt, and then
moisture. Overtemperature can cause
heat-related problems such as thermal
runaway and component failure. Each
amplifier tray in the transmitter contains
a thermal interlock protection circuit that
will shut down that tray until the
temperature drops to an acceptable level.
A suitable environment for the
transmitter can enhance its overall
performance and reliability and maximize
revenues by minimizing down time. A
properly designed facility will have an
adequate supply of cool, clean air, free of
airborne particulates of any kind, and
without excessive humidity. An ideal
environment requires temperatures in
the range of 40° F to 70° F throughout
the year, reasonably low humidity, and a
dust-free room. It should be noted that
this is rarely if ever attainable in the real
world. However, the closer your
environment is to this design, the greater
the operating capacity of the transmitter.
Although the fans and blowers designed
and built into the transmitter will remove
the heat from within the cabinet,
additional means are required for
removing heat from the building. To
achieve this, a few considerations should
be taken into account. The first step is to
determine the amount of heat to be
removed. There are generally three
sources of heat that must be considered.
The first and most obvious is the heat
from the 100-watt transmitter itself. This
can be determined by subtracting the
average power to the antenna (69.5
watts) from the input power (750 watts).
This number in watts (680.5) is then
multiplied by 3.41, which gives 2320, the
BTUs to be removed every hour.
The second source of heat is other
equipment in the same room. This
number is calculated in the same way as
the equation for BTUs. The third source
of heat is equally obvious but not as
simple to calculate. This is the heat
coming through the walls, roof, and
windows on a hot summer day. Unless
the underside is exposed, the floor is
usually not a problem. Determining this
number is usually best left up to a
qualified HVAC technician. There are far
too many variables to even estimate this
number without detailed drawings of the
site showing all construction details. The
sum of these three sources is the total
amount of heat that must be removed.
There may be other sources of heat, such
as personnel, and all should be taken into
account.
Now that the amount of heat that must
be removed is known, the next step is to
determine how to accomplish this. The

Summary of content (7 pages)