Installation Instructions Chapter 4

500-Watt VHF Low Band Transmitter Chapter 4, Installation and Setup Procedures
325A, Rev. 0 4-1
Chapter 4
Installation and Setup Procedures
There are special considerations that
need to be taken into account before the
325A can be installed. For example, if the
installation is completed during cool
weather, a heat-related problem may not
surface for many months, suddenly
appearing during the heat of summer.
This section provides planning
information for the installation and set up
of the transmitter.
4.1 Site Considerations
The transmitter requires an AC input line
of 220 VAC with a rating of 40 amps for
the exciter/amplifier cabinet. Make sure
that the proposed site for the transmitter
has the necessary voltage requirements.
The 325A is designed and built to provide
long life with a minimum of maintenance.
The environment in which it is placed is
important and certain precautions must
be taken. The three greatest dangers to
the transmitter are heat, dirt, and
moisture. Heat is usually the greatest
problem, followed by dirt, and then
moisture. Over-temperature can cause
heat-related problems such as thermal
runaway and component failure. Each
amplifier tray in the transmitter contains
a thermal interlock protection circuit that
will shut down that tray until the
temperature drops to an acceptable level.
A suitable environment for the
transmitter can enhance the overall
performance and reliability of the
transmitter and maximize revenues by
minimizing down time. A properly
designed facility will have an adequate
supply of cool, clean air, free of airborne
particulates of any kind, and no
excessive humidity. An ideal environment
will require temperature in the range of
40° F to 70° F throughout the year,
reasonably low humidity, and a dust-free
room. It should be noted that this is
rarely if ever attainable in the real world.
However, the closer the environment is
to this design, the greater the operating
capacity of the transmitter.
The fans and blowers designed and built
into the transmitter will remove the heat
from within the trays, but additional
means are required for removing this
heat from the building. To achieve this, a
few issues need to be resolved. The first
step is to determine the amount of heat
to be removed from the transmitter
room. There are generally three sources
of heat that must be considered. The first
and most obvious is the heat from the
transmitter itself. This can be determined
by subtracting the average power to the
antenna (350 watts) from the AC input
power (3500 watts). This number in
watts (3150) is then multiplied by 3.41,
which gives 10,741, the BTUs to be
removed every hour. 12,000 BTUs per
hour equals one ton, so a 1-ton air
conditioner will cool a 500-watt
transmitter.
The second source of heat is other
equipment in the same room. This
number is calculated in the same way as
the equation for BTUs. The third source
of heat is equally obvious but not as
simple to calculate. This is the heat
coming through the walls, roof, and
windows on a hot summer day. Unless
the underside is exposed, the floor is
usually not a problem. Determining this
number is usually best left up to a
qualified HVAC technician. There are far
too many variables to even estimate this
number without reviewing the detailed
drawings of the site that show all of the
construction details. The sum of these
three sources is the bulk of the heat that
must be removed. There may be other
sources of heat, such as personnel, and
all should be taken into account.
Now that the amount of heat that must
be removed is known, the next step is to

Summary of content (7 pages)