RM2-4000-PI26 Reader RM2L-4000-PI26 Reader Installation Guide T Version A0 Document Part Number 8200- 1179-01 September 2015 OVERVIEW This guide provides installation and connection information for RM2-4000-PI26 and NOTE AF RM2L-4000-PI26 Readers. The RM2-4000-PI26 reader model is UL294 approved and not UL1076 approved. The RM2L-4000-PI26 reader model is both UL294 and UL1076 approved. Reader Models D R The RM readers provide an enclosed RM-4 board with multiple read heads.
Overview TABLE 1. Part Numbers RM2-4000-PI26 With keypad and LCD; built-in RM-4 DS interface board RM2L-4000-PI26 The RM Multi-Technology reader can read three major card technologies – HID prox, Indala prox, and 13.56 MHz smart card. Specific card formats supported include ISO 14443 A/B serial number, ISO 15693 serial number, iCLASS® serial number, MIFARE encrypted sector, DESFire serial number, FIPS 201 PIV-II, and most 125 KHz formats (HID, Indala 26-bit and CASI ProxLite).
Features Smart Card (13.56 MHz) Formats Supported TABLE 3. Smart Card (13.
Features Controller Communications Wiegand Locally Flashable via RS485 Open Standards Compliance ISO 14443A ISO 14443B ISO 15693 Configure Using Program Card Pass-through - Default setting that allows the reader to send all data on the card. Fixed length - Reader can be configured to output a fixed length by padding or truncating data on the card.
Specifications SPECIFICATIONS Specification Requirement Data Cable Recommended data cable is Belden #9841or equivalent. The maximum length is 4000 feet (1212 meters) between the controller and the reader. Power Wiring Recommended power wiring is Belden #8461/8442 twisted pair. Maximum length depends on the wire gauge. Readers can be powered from a local power supply.
Installation INSTALLATION To Install the Reader: 1. Install the reader mount plate. 2. Wire the components. 3. Connect and ground the cable shields on the reader bus. (Refer to TAB 2010-15 “RM Reader ESD Protection Guidelines.”) 4. Set the reader address. 5. Install the ARM-1 relay boards (optional). 6. Install the heater kit (optional). 7. Mount the reader standard housing on the reader mount plate using the Software House security screwdriver (Part number 132-183).
Installation FIGURE 3. Mount Plate Dimensions 5.45" Wiring access 4.11" 3.66" 4.94" 2.47" 1.29" .83" 1.54" 1.82" 8 mounting holes 2.73" 3.64" .0.156" Thru, 0.280” Countersink T 3.92" AF This device has been approved for outdoor use when properly installed with the RM Heater Kit Installation (P.N. 130-915) and the supplied gasket material. Position the gasket with the RM mount plate so that the mounting holes are properly aligned.
Installation Figure 4 shows reader connections. FIGURE 4. Reader Connection UL has not evaluated the ARM-1.
Setting up the reader Figure 5 shows RM-4 P1 and P5 wiring. FIGURE 5. RM-4 Wiring Requirements R AF T Wiring the Inputs, Outputs, Reader Bus SW3-7 and SW3-8 refer to the Beeper on the RM-4. P3 BEEP refers to the Beeper on the read head, if it exists. There is no Beeper on the reader read heads. Some third-party readers that are connected to a standalone reader have beepers. D NOTES SETTING UP THE To Set Up the Reader: READER 1.
Setting up the reader Grounding and Shielding Single RM Reader When connecting a single RM reader to the reader bus, use twisted pair, shielded minimum 24 AWG cable. Attach the shield at the controller end. (Refer to TAB 2010-15 “RM Reader ESD Protection Guidelines.”) Attach a local earth ground (18 or 22 gauge) wire to the J5 component on the RM reader.
Setting up the reader Figure 7 shows how to connect ARM-1 relay modules to the reader outputs and how to wire NO (Normally Open) and NC (Normally Closed) supervised inputs. R AF T FIGURE 7. Reader Input/Output Connections Two ARM-1 relay components can be connected to the reader through the P5 connector (Table 5 ). D Installing the ARM-1 Relay Module RM P5-1 is the common (+12 VDC) pin for either ARM-1. RM P5-2 is the output drive (GND) for the first relay.
Setting up the reader Installing the Heater (optional) The readers require a heater kit (Model C130-915) when installed outdoors in an environment where temperatures may drop below 40° F (5° C). The Model C130-915 heater kit contains the following parts: TABLE 6. Heater Parts Description 1 Transformer 12 VAC 40VA 2 Heater Strips 1 Thermostat (turns on at 40 ° F) 3 Wire nuts 2 6-32 x 1/4” screws to mount thermostat to RM plate.
Setting up the reader FIGURE 9. RM Installation . To Apply Heater Strips: T Applying Heater Strips AF 1. Clean the attachment surface of the RM mount plate with a solvent such as alcohol (use all required precautions when handling solvents). 2. Carefully remove the release film from the adhesive. 3. Locate the heater on the clean surface of the RM mount plate exactly as shown in Figure 9. 4. Gently roll the heater strip in place to remove air bubbles. R 5.
Testing Readers TESTING READERS To Test the Readers: 1. Properly configure Readers, Inputs, and Outputs using the C•CURE Administration application and put the reader Online. 2. Measure the supply voltage to the reader. The voltage can be measured between pin 1 (+12 VDC supply) and pin 4 (ground) on the P4 connector. The voltage must be +12 VDC (+/-5%). 3. Check the reader address setting. The reader must be set to an unused address, between 1 and 8, when connected to the apC or iSTAR.
Configuration Notes 4. If there are more program cards, repeat steps 2 and 3 until you have presented the necessary number of program cards. 5. The reader is configured for the specified option(s) and is ready for use. AF For information about upgrading the firmware revision, refer to the PDF document entitled SWH Readers Download Firmware to Reader posted on the Software House Member Center.
Compliance Compliance Specification Description UL294 5th Edition Access Control System USA UL1076 5th Edition Proprietary Alarm Units USA IEC60950-1 ITE – Safety International EN60950 ITE – Safety EU EN55022-:2010 ITE – Radio Disturbance Characteristics EU EN55024 ITE – Immunity Characteristics EU EN50130-4:2011 Alarm systems – Electromagnetic Compatibility EU RoHS Restriction of hazardous substances EU FCC 47 CFR part 15 FCC – unintentional transmitter USA - Class A ICES-003/
Important Safety Information UL Listing The following requirements must be adhered to: RM2L-4000-PI26 and RM2-4000-PI26 readers are Underwriters Laboratories Inc. (UL) Listed to Standard UL 294, Access Control System Units. RM2L-4000-PI26 reader is Underwriters Laboratories Inc. (UL1076). The RM2-4000-PI26 and the RM2L-4000-PI26 readers installed in accordance with the National Electric Code (ANSI/NFPA 70) or the Canadian Electric Code as required by local authorities.