Installation Instructions

Table Of Contents
PG9935(E)/PG8935/PG4935
PowerG 2-way Wireless Shock and Contact
Detector with Hardwired Input Installation
Instructions
Operation
The PGx935 series are 2-way shock detectors with an optional
shock accumulation feature and auxiliary input. The PGx935
fits windows, doors, walls or roofs and is ideal for residential or
commercial installations.
Features:
Optional shock accumulation / vibration sensor.
Built-in link quality indicators reduce installation time by
eliminating the need for the installer to physically approach
the control panel.
Reed switch with a magnetic anti-masking sensor.
Optional auxiliary input for connecting other hardwired
devices. Use only UL/ULC burglary listed devices.
Digital display enables fast and easy shock level adjustment
Full remote configuration eliminates the need to physically
access the shock detector.
Remote view of Low Battery, front and back Tamper,
Supervision.
An LED lights when alarm or tamper events are reported.
Low-Battery Detection
The PGx935 includes low-battery condition detection. When
this condition is detected a trouble message is transmitted to the
compatible receiver/control panel. This will provide visual
identification of the unit that requires a battery change. For UL
commercial burglary installations replace battery yearly.
Device Setup
CAUTION! This product uses Lithium Batteries. Improper
handling of lithium batteries may result in HEAT GENERA-
TION, EXPLOSION or FIRE, which may lead to personal inju-
ries.
Caution! To be installed by service personnel only.
WA RN I NG ! DANGER OF EXPLOSION IF BATTERIES ARE
INSTALLED INCORRECTLY. REPLACE ONLY WITH THE
SAME OR EQUIVALENT TYPE RECOMMENDED BY THE
MANUFACTURER. DISPOSE OF USED BATTERIES
ACCORDING TO THE MANUFACTURER'S INSTRUC-
TIONS. KEEP AWAY FROM SMALL CHILDREN. IF SWAL-
LOWED PROMPTLY SEE A DOCTOR.
Do not try to recharge these batteries.
Note: Battery replacement should be done by installer. For use
in indoor, non-hazardous locations only.
Note: To ensure the continued operation of all wireless devices
after performing a system default, a global upload of all wire-
less programming via DLS is recommended before defaulting
the system. After completing the system default, download the
wireless programming.
Legend
A. Auxiliary input terminals
B. Back tamper switch
C. Battery clips
D. Back tamper break-away segment
E. Digital display
F. Front tamper switch
G. Enroll button
H. LED
I. Reed switch
J. Up and down buttons
K. LED
L. Reed switch on underside of PC Board (in unit)
M.Symbol on side of the case indicates location of reed switch
N. Magnet
O. 1/4" space maximum (6mm)
P. 2.2 kΩ resistor
Q. N.C. switch
R. N.O. switch
Installing the battery
1. Insert a flat-edged screwdriver into
the slot and push upward to
remove cover.
2. Remove the screw and separate the
cover from the base.
3. Observe polarity and install bat-
tery.
4. Connect the sensor wire to the ter-
minal block.
Note: When manually programming
wireless devices, if a device has been
powered up for more than 48 hours it
cannot be enrolled into the system
until the device has been tampered
and restored. When programming the
panel using the Quick Enroll proce-
dure follow the steps detailed in
Enroll the Device into the System.
Note: After restoring a low battery
trouble the system may take up to 5 minutes to clear the trouble.
Enrolling the device into the system
Refer to the PowerSeries Neo Host Installation Manual or
iotega Reference Manual for the enrollment procedure.
Placement testing
Before permanently mounting any wireless device, temporarily
mount the device and perform a placement test.
1. Tamper the device by removing the cover.
2. Replace the cover to restore the tamper and the device will
stay in placement mode for 15 minutes.
3. Trip the device by opening the door or window and verify
the red LED blinks, indicating detection.
4. After 2 seconds the LED blinks 3 times.The following table
indicates received signal strength.
IMPORTANT! Only GOOD or STRONG signal strengths are
acceptable. If you receive a POOR signal from the device, re-
locate it and re-test until a GOOD or STRONG signal is
received.
Note: For UL/ULC installations, only STRONG signal levels
are acceptable. After installation verify the product functional-
ity in conjunction with the compatible receivers.
Note: For detailed placement instructions refer to the control
panel Reference Guide
Gap Separation
Mounting the Device
Assess the best mounting position for the device based on the
desired level of protection and considering locations where a
strong shock impact is expected. Install the device in accor-
dance with the guidelines presented in this manual. For UL/
ULC listed installations, use only the mounting screws pro-
vided. The device is intended to be installed on doors with or
without glass inserts and on window frames but not on the
actual glass surface. For magnetic contact detection, it is highly
recommended to attach the detector to the door/window on the
fixed frame and the magnet to the movable part (door or win-
dow). Locate the magnet not more than 6 mm (0.25 in.) from
the detector’s marked side. Adjust the shock sensitivity setting
at the final mounting position (refer to section "Shock Detector
Local Calibration"). Test the sensitivity of the unit by gently
hitting (using the palm of your hand) the surface on which the
device is installed. Gradually increase the pressure until the
desired response is obtained. Ensure that the device is not trig-
gered by accidental vibration (e.g., wind, birds, insects) hitting
the protected window or surface. Normal traffic or operation of
the door/window should not trip the shock sensor. When testing
the sensitivity of the unit, do not cause stress or damage to the
mounting surface or to the glass.
1. Secure the base to the mounting surface using the two sup-
plied screws.
CAUTION! Do not use double-sided tape, as this will insulate
the detector from vibrations.
2. Mount the magnet near its location mark with 2 screws.
WARNING: In order to avoid personal injury while testing
sensitivity, do not apply pressure to glass inserts or windows.
Note: Removing the cover transmits a tamper message to the
system. When removing the battery press the tamper switch or
after replacing the battery the Tamper Restore message will not
be transmitted to the system and the alert will not be cleared.
Attention! The unit has an optional back tamper switch under
the PCB. The switch lever will be pressed against a special
break-away base segment that must be fastened to the wall.
Forcibly removing the detector from the wall breaks the base
segment, opening the tamper switch. Note: For UL Commer-
cial burglary installations the back tamper is required.
Configuration
The following programmable options are available:
Selections
Shock Detector Local Calibration
The PGx935 can only be locally calibrated when the device is
in Local Diagnostics mode (first 15 minutes after opening the
cover). To calibrate when not in local diagnostics mode reset
the device by closing the tamper switch.
Note: Disable the accumulation parameter while testing the
threshold. If, after activating the display no buttons are pressed
within 20 seconds, the display turns off.
1. Turn on the digital display by pressing the Up or Down but-
ton. The letter “G” appears for 3 seconds, then a menu
allowing you to select the threshold from a range of 1-19. If
the letter “E” appears there is no communication link
between the unit and control panel and no changes shall be
performed.
2. Change the threshold by pressing the Up or Down button.
The lower the threshold, the higher the sensitivity. Use the
lowest thresholds for harder materials, such as concrete.
3. For aid in selecting a threshold, while the menu is active,
knock on the surface with the required force to trip the
detector. The power of the detected knock will be presented
on the display as a blinking number for 3 seconds. The num-
ber should be in the range of 1 to 19, where 1 is very weak
(requiring higher sensitivity) and 19 is very strong (requir-
ing less sensitivity). If no number displays, no shock was
detected from the knock. If a hyphen displays, the knock
exceeds the highest threshold of the detector.
4. Repeat the same test several times.
5. Once you have entered the desired value set the threshold by
pressing the Up and Down buttons simultaneously.
6. The detector now moves to the Accumulated menu, (shown
as “A” on the display). Press the Up or Down buttons to
Enable or Disable (“1” or “0” respectively on the display).
Set by pressing the Up and Down buttons simultaneously.
7. If the letter “E” appear on the display, then there is no com-
munication link between the unit and control panel.Verify
that the control panel has power.
Wiring the auxiliary input
1. Connect the auxiliary sensor contacts across the auxiliary
input terminals.
2. If the auxiliary input is defined as a Normally Closed (N.C.)
type, series connected N.C. sensor contacts must be used
exclusively. An E.O.L. resistor will not be required.
3. If the auxiliary input is defined as a Normally Open (N.O.)
type, parallel connected N.O. sensor contacts must be used
exclusively. An E.O.L. resistor will not be required.
4. For E.O.L. supervision: Normally Closed (N.C.) sensor con-
tacts can be used. A 2.2 KΩ E.O.L. resistor must be wired at
the far end of the zone loop.
Note: For UL installations, the device connected to the initiat-
ing circuit must be located in the same room as the transmitter.
The drawing below illustrates a N.O. and N.C. alarm circuit
with EOL resistor.
Note: An alarm message is transmitted once the loop is opened
or short circuited.
Note: For UL/ULC installations connect only UL/ULC listed
devices to the auxiliary wiring input
Event Indications
Specifications
Frequency Band (MHz) - CE Listed PG4935: 433MHz; CE
listed PG8935: 868MHz; FCC/IC/UL/ULC listed PG9935(E):
912-919MHz
Communication Protocol: PowerG
Alarm Input: One auxiliary
Supervision: Signaling at 4-min. intervals
Tamper Alert: Reported when a tamper event occurs
Battery type: 3V Lithium CR-123A type battery, consumer
grade.
Note: For UL installations use Gold Peak (GP) and Panasonic
CR-123A batteries only.
Battery Life Expectancy: up to 5 years only with all sensors
enabled (for typical use at room temperature). Not tested by
UL/ULC.
Door frame height: typical 7ft to 8ft (213 to 244 cm) 1/2
Door frame width: typical 1ft to 4ft (30.5 to 122 cm) 1/2
Door frame thickness: 11/2" to 13/4" (3.8 to 4.4 cm)
Window/glass insert size: any size that will fit within the door
frame listed above. Install the contact so that a door or window
cannot be opened more than 2" (5.1cm) without causing an
alarm condition.
Temperature range: -10°C to +55°C (UL/ULC verified 0°C to
+49°C)
Relative Humidity: max. 93%RH, non-condensing (UL/ULC
verified max 85%RH)
Auxiliary Input Cable Length: 10m max. AWG22
Auxiliary Input EOL Resistor: 2.2 K
Dimensions:(LxWxD) 118x27x30 mm (4-5/8 x 1-1/8 x 1-3/16
in.)
Weight (including battery): 130g (4.6 oz)
Compatible Receivers
This device can be used with DSC panels and receivers that use
PowerG technology.
For UL/ULC installations use this device only in conjunction
with compatible DSC wireless panels/receivers: WS900-19,
WS900-29, HSM2HOST9, HS2LCDRF(P)9, HS2ICNRF(P)9,
and PG9920.
UL/ULC Notes
The PG9935(E) has been listed by UL for commercial and resi-
dential burglary applications and by ULC for residential bur-
glary applications in accordance with the requirements in the
Standards UL 634 and ULC/ORDC634 for Door and Window
Contact.
SIMPLIFIED EU DECLARATION OF CONFORMITY
Hereby, Tyco Safety Products Canada Ltd declares that the
radio equipment type is in compliance with Directive 2014/53/
EU. The full text of the EU declarations of conformity for the
models mentioned below are available at the following internet
addresses:
PG4935 - http://dsc.com/pdf/1401014
PG8935 - http://dsc.com/pdf/1401037
Frequency Band / Maximum Power
g1 433.04MHz – 434.79MHz/10mW
h1.4 868.0MHz – 868.6MHz/10mW
h1.5 868.7MHz – 869.2MHz/10mW
European single point of contact: Tyco Safety Products, Volta-
weg 20, 6101 XK Echt, Netherlands
FCC COMPLIANCE STATEMENT
WARNING! Changes or modifications to this unit not
expressly approved by the party responsible for compliance
could void the user’s authority to operate the equipment.
This device has been tested and found to comply with the limits
for a Class B digital device, pursuant to Part 15 of the FCC
Rules. These limits are designed to provide reasonable protec-
tion against harmful interference in residential installations.
This equipment generates uses and can radiate radio frequency
energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio and tele-
vision reception.
However, there is no guarantee that interference will not occur
in a particular installation. If this device does cause such inter-
ference, which can be verified by turning the device off and on,
the user is encouraged to eliminate the interference by one or
more of the following measures:
– Re-orient or re-locate the receiving antenna.
– Increase the distance between the device and the receiver.
– Connect the device to an outlet on a circuit different from the
one that supplies power to the receiver.
– Consult the dealer or an experienced radio/TV technician.
This equipment complies with FCC and IC RF radiation expo-
sure limits set forth for an uncontrolled environment.
This device complies with FCC Rules Part 15 and with Industry
Canada licence-exempt RSS standard(s). Operation is subject
to the following two conditions: (1) This device may not cause
harmful interference, and (2) this device must accept any inter-
ference that may be received or that may cause undesired oper-
ation.
WARNING! To comply with FCC and ISED Canada RF expo-
sure compliance requirements, the PIR detector should be
located at a distance of at least 20 cm from all persons during
normal operation. The antennas used for this product must not
be co-located or operated in conjunction with any other antenna
or transmitter.
ATTENTION ! Pour des raisons de conformité aux normes
d'exposition aux fréquences radio FCC et ISED Canada, le
détecteur PIR doit être distant d'au moins 20 cm de toute per-
sonne, en conditions de fonctionnement normales. Les antennes
utilisées pour ce produit ne doivent pas être positionnées dans
un même espace, ni utilisées avec une autre antenne ou émet-
teur.
Le present appareil est conforme aux CNR d'Industrie Canada
applicables aux appareils radio exempts de licence. L'exploita-
tion est autorisee aux deux conditions suivantes :(1) l'appareil
ne doit pas produire de brouillage, et (2) l'utilisateur de l'appar-
eil doit accepter tout brouillage radioelectrique subi, meme si le
A B
C
D
E F
G
H
I
J
+-
LED response Signal Strength
Green LED blinks STRONG
Orange LED blinks GOOD
Red LED blinks POOR
No blinks No communication
Metallic (Ferrous)
Materials
Nonmetallic/Metallic
(nonferrous) Materials
Direction of
Movement of
the Magnet
Approach/
Make
Remove/
Break
Approach/
Make
Remove/
Break
Axis X 9 mm
(.35”)
11 mm
(.43”)
22 mm
(.86”)
25 mm
(.98”)
Axis Y 8 mm
(.31”)
13 mm
(.51”)
23 mm
(.90”)
7mm
(.28”)
Axis Z 25 mm
(.98”)
23 mm
(.90”)
27 mm
(1.06”)
30 mm
(1.18”)
Recommended maximum gap separation for installation (on
specified materials and axes of use) is 6 mm (0.24”).
+
-
K
}
L
N
M
O
Z
X
Y
Alarm LED - Default [ON]
Enables/disables the device LED to activate when an alarm
event occurs.
Reed Switch - Default [OFF]
Enables/disables the reed switch.
External Input - Default [OFF]
Enables/disables the external input on a shock sensor.
Supervision - Default [ON]
Enables/disables supervision of the device.
Shock Accumulation - Default [OFF]
Enables/disables the Shock Accumulation feature.
Zone EOL - Default [01]
Configures auxiliary input as one of the following options:
[00] Disabled [02] Normally Open
[01] Single EOL [03] Normally
Closed
Sensor Threshold - Default [08]
Enter the 2-digit threshold from 01 (very weak) - 19 (very
strong).
LED Indications Event
Red LED ON 0.2 sec. Tamper open / close
Red on 2 sec. Shock
Red on 2 sec. Open close door
Red on 2 sec. Open close Aux input
P
Q
R
D-304677

Summary of content (6 pages)