Battery Powered Smoke & Heat Alarms EiA600 Series EiA605 Smoke Alarm Series EiA603 Heat Alarm Series Instructions Read and retain for as long as the product is being used. It contains vital information on the operation and installation of your Alarm. The leaflet should be regarded as part of the product. If you are just installing the unit, the leaflet must be given to the householder. The leaflet is to be given to any subsequent user.
CONTENTS Page 1 Quick Start Guide ..................................................................................... 4 2 Location & Positioning ........................................................................... 7 3 Installation ................................................................................................. 15 4 Testing, Maintenance & Power Supply Monitoring ..................... 19 5 Fire Safety Advice .................................................................
Table 1 9V Replaceable Battery Model RF Capability Supplied Optional RF Module Model No.
1.
Quick Start Guide PLACE ALARM & TWIST ON TO BASE TEST ALARM PRESS THE TEST BUTTON TEST ALARM AT LEAST WEEKLY 5
EiA605 INDICATOR SUMMARY Normal Operation Power Up Standby Sensing Fire Sensing fire through interconnect RED LED HORN / SOUNDER 1 Flash 1 Flash every 45 seconds Rapid Flashing (every 0.5 sec) Off Off Off Full sound Full sound 1 Flash every 45 sec Off 1 beep every 45 sec 1 beep every 45 sec Rapid Flashing (every 0.
2. Location & Positioning Introduction Congratulations on purchasing an EiA600 Series Alarm. You can easily install these alarms throughout the property on escape routes, on each storey, in corridors & in closed rooms to give warning of fire. The Heat Alarms can be installed in kitchens and other areas where Smoke Alarms are unsuitable.
- crawl spaces and unfinished attics” - “In the living area(s) of a guest suite” - “In the living area(s) of a residential board and care occupancy” “Are More Smoke Detectors Desirable? The required number of smoke detectors might not provide reliable early warning protection for those areas separated by a door for the areas protected by the required smoke detector. For this reason, it is recommended that householder consider the use of additional smoke detectors for those areas or increased protection.
SMOKE ALARMS - EiA605 Series Sufficient smoke must enter your Smoke Alarm before it will respond. Your Smoke Alarm needs to be within 6.4 metres of the fire to respond quickly. Smoke Alarms also need to be in positions where they can be heard throughout the property, so they can wake you and your family in time for everyone to escape.
However, a fire in a closed room (e.g. kitchen) adjoining the escape route, can eventually cause the corridor to become smoke-logged due to smoke leaking out from around the door before adequate warning can be given by detectors in the corridor. (Smoke leaking out from a room is often cool and slow moving so it can take a long time to rise to the ceiling, and travel to a detector which could be some distance away).
In houses with more than one sleeping area, Smoke Alarms should be placed between each sleeping area and the living area and it is recommended that Heat Alarms should be placed in the kitchen & garage. Recommended Protection Fire authorities recommend you put individual Smoke Alarms in or near all rooms where fire is most likely to break out (apart from the locations to avoid e.g bathrooms - see Section 3).
Figure 1 Bathroom Bedroom For minimum protection - Smoke Alarm on each storey - in each sleeping area - every 6.4 metres of hallways and rooms - within 3 metres of all bedroom doors - all units interconnected (where feature is present) Bath Bedroom Laundry Room Bedroom For recommended protection Kitchen (in addition to the above): - Smoke Alarms in every room (except kitchens and bathrooms) Living Room - Heat Alarms located in kitchens, garages etc. within 5.
Positioning Ceiling Mounting Hot smoke rises and spreads out, so a central ceiling position is the recommended location. The air is “dead” and does not move in corners, therefore Smoke & Heat Alarms must be mounted away from corners. Keep at least 0.3m from walls and corners (see Figure 3). Additionally, mount the unit at least 0.3m from any light fitting or decorative object which might prevent smoke or heat entering the Smoke/Heat Alarm.
Locations to avoid DON’T place Smoke Alarms in any of the following areas: • Bathrooms, kitchens, shower rooms, garages or other rooms where the smoke alarm may be triggered by steam, condensation, normal smoke or fumes. Keep at least 6 metres away from sources of normal smoke/fumes. • Locate away from very dusty or dirty areas as dust build-up in the chamber can impair performance. It can also block the insect screen mesh and prevent smoke from entering the smoke detector chamber.
• In very high or awkward areas (e.g. over stairwells) where it may be difficult to reach the alarm (for testing, hushing or battery replacement). • Locate the unit at least 1m from dimmer controlled lights and wiring as some dimmers can cause interference. • Locate unit at least 1.5m and route wiring at least 1m away from fluorescent light fittings as electrical “noise” and/or flickering may affect the unit. 3. Installation Installation Procedure ROTATE UNIT ANIT-CLOCKWISE 1.
If using RadioLINK Smoke/Heat Alarms then they should be mounted with antennas in the same orientation (i.e. essentially parallel). This means picking a part of the building, say the front wall of the building and then installing all mounting plates in the same orientation with respect to this (see figure 6). 5. Connect the battery to the battery snaps as shown in the Quick Start Guide (for 9V Replaceable Battery models only). 6. Carefully line up the unit on the base, gentle press home & twist on.
7. Press the Test button on each alarm to ensure that the Alarm works (see Figure 7a for Smoke Alarm & 7b for Heat Alarm). 8. If using RadioLINK interconnection, see booklet ‘RF Modules for Battery Powered Smoke & Heat Alarms. Install all the other Alarms similarly. Tamperproofing the Alarms The Alarm can be made tamperproof to prevent unauthorised removal of the Alarm. Smoke Alarm Heat Alarm Figure 7a Figure 7b Break off the small pillar on the base as shown in figure 8a.
PUSH UP CATCH & TWIST ALARM ANTI-CLOCKWISE TO REMOVE BREAK OFF SMALL PILLAR How to Tamperproof How to Remove Figure 8a Figure 8b 6 to 8 mm SELF TAPPING SCREW TAMPERPROOF SCREW 2 to 3 mm Figure 8c Figure 8d 18 Line up the screw (not supplied) on the “U” shaped recessed area shown in figure 8c and screw firmly home. To remove the Alarm from the ceiling, remove the screw first, and then twist off anti-clockwise.
4. Testing, Maintenance & Power Supply Monitoring Your Alarm is a life saving device and should be checked periodically. Regularly check that the red light on the Alarm flashes approx once a minute to show the units are powered. Replace the Alarm if the flashing stops. 4.1 Manually Testing your Alarms It is recommended that you test your Alarms after installation and then at least weekly to ensure the units are working. It will also help you and your family to become familiar with the sound of the Alarms.
If, when the Alarm sounds, there is no sign of smoke or noise to indicate that there is a fire, it should be assumed that it is due to an actual fire and the dwelling should be evacuated immediately. Check the house carefully in case there is a small fire smouldering somewhere. Check whether there is some source of smoke or fumes, for example cooking fumes being drawn past the Alarm by an extractor.
4.3 Power Supply Monitoring 4.3.1 What to do when an Alarm is beeping: 1. A Smoke Alarm is beeping about every 40 seconds with the red light flashing at the same time: - If it is a 9V Replaceable Battery model then replace the battery. 2. A Heat Alarm is beeping about every 40 seconds. - If it is a 9V Replaceable Battery model then replace the battery. 4.3.2 Battery Replacement - ( 9V Replaceable Battery models only) A fresh Alkaline Battery should last for over a year.
4.3.3 RadioLINK Module Units If all the RadioLINK Alarms sound for 2 seconds every 4 hours, it means at least one of the Alarms in the system has a depleted battery. Locate the depleted battery(ies) as above. 4.4 Cleaning your Alarm Clean your Alarm regularly. Use a soft bristle brush or the brush attachment of your vacuum cleaner to remove dust and cobwebs from the side slots where the smoke/heat enters. To clean the cover, wipe with a damp cloth and dry thoroughly. WARNING: Do not paint your Alarm.
excess dust does not build up. Any insects or cobwebs in the vicinity of the Smoke Alarm should be promptly removed. In certain circumstances even with regular cleaning, contamination can build up in the smoke sensing chamber causing the alarm to sound. If this happens the Smoke Alarm must be returned for servicing or replacement. Contamination is beyond our control, it is totally unpredictable and is considered normal wear and tear.
5. Fire Safety Advice When using household protective devices, basic safety precautions should always be followed, including those listed below • Please read all instructions. • Rehearse emergency escape plans so everyone at home knows what to do in case the alarm sounds. • Use the Alarm Test Button to familiarise your family with the Alarm sound and to practice fire drills regularly with all family members.
• This appliance is intended ONLY for premises having a residential type environment. • This is not a portable product. It must be mounted following the instructions in this instruction leaflet. • Smoke/Heat Alarms are not a substitute for insurance. The supplier or manufacturer is not your insurer. Fire Safety Hints Store petrol and other flammable materials in proper containers. Discard oily or flammable rags. Always use a metal fireplace screen and have chimneys cleaned regularly.
Planning Your Escape Route For When The Alarms Sound 1. Check room doors for heat or smoke. Do not open a hot door. Use an alternate escape route. Close doors behind you as you leave. 2. If smoke is heavy, crawl out, staying close to floor. Take short breaths, if possible, through a wet cloth or hold your breath. More people die from smoke inhalation than from flames. 3. Get out as fast as you can. Do not stop for packing. Have a prearranged meeting place outside for all family members.
6. Alarm Limitations Limitations of Smoke/Heat Alarms Smoke/Heat Alarms have significantly helped to reduce the number of fire fatalities in countries where they are widely installed. However independent authorities have stated that they may be ineffective in some circumstances. There are a number of reasons for this: • Smoke/Heat Alarms will not work if the batteries are depleted or if they are not connected. Test regularly and replace the entire Alarm when it fails to operate.
7. RadioLINK Accessories EiA605MRF RadioLINK Interconnect module is used for the 9V Replaceable Battery models. It plugs into the rear of the Alarm. This ensures that when one Alarm senses fire, all units sound to give an alarm through-out the house - (see Table 1).
8. Getting Your Alarm Serviced If your Alarm fails to work after you have read the sections on “Installation”, “Testing and Maintenance” and “Troubleshooting”, then contact Customer Assistance at the nearest address given at the end of this leaflet. If it needs to be returned for repair or replacement put it in a padded box with the battery disconnected. Send it to “Customer Assistance” at the nearest address given on the Alarm or in this leaflet.
Some states or jurisdictions do not allow the limitation or exclusion of incidental or consequential damages, or limitations on how long an implied warranty last so the above limitation may not apply to you. Do not interfere with the Alarm or attempt to tamper with it. This will invalidate the guarantee, but more importantly may expose the user to shock or fire hazards. This guarantee is in addition to your statutory rights as a consumer.
10. Troubleshooting Alarms sound for no apparent reason • House Code your Alarms - see booklet ‘RF Modules for Battery Powered Smoke & Heat Alarms’. If the Alarms are in the default factory settings, neighbouring units may cause them to alarm. • Check for fumes, steam, etc. from the kitchen or bathroom. Paint and other fumes can cause nuisance alarms. • Check for any sign of contamination such as cobwebs or dust. Clean the alarm as described in Section 5 if necessary.
11. Technical Specification Power : 9V Alkaline type battery (replaceable) Smoke Sensitivity : Meets UL217 Electromagnetic Compatibility : Complies with UL217 / FCC Part 15 Test/Hush Button : Checks electronics and horn Sensor Type : Photoelectric Operating Temperature : 0°C to 40°C Humidity Range : 15% to 95% R.H.
MODEL TYPE EiA605 Photoelectric Smoke Alarm EiA605W Photoelectric Smoke Alarm EiA603 Heat Alarm EiA603W Heat Alarm The Smoke Alarms are tested and Approved to UL217 Standards.
34
12. Contact Us Please return to: Customer Service Ei Electronics Shannon, Co Clare, Ireland Phone: +353 61 471277 email: sales@eielectronics.ie web: www.eielectronics.