6 F 2 S 0 8 5 7 INSTRUCTION MANUAL TRANSFORMER PROTECTION RELAY GRT100 - ∗∗∗D © TOSHIBA Corporation 2007 All Rights Reserved. ( Ver. 4.
6 F 2 S 0 8 5 7 Safety Precautions Before using this product, be sure to read this chapter carefully. This chapter describes safety precautions when using the GRT100. Before installing and using the equipment, read and understand this chapter thoroughly. Explanation of symbols used Signal words such as DANGER, WARNING, and two kinds of CAUTION, will be followed by important safety information that must be carefully reviewed.
6 F 2 S 0 8 5 7 DANGER • Current transformer circuit Never allow the current transformer (CT) secondary circuit connected to this equipment to be opened while the primary system is live. Opening the CT circuit will produce a dangerous high voltage. WARNING • Exposed terminals Do not touch the terminals of this equipment while the power is on, as the high voltage generated is dangerous. • Residual voltage Hazardous voltage can be present in the DC circuit just after switching off the DC power supply.
6 F 2 S 0 8 5 7 shipment, as this may cause the performance of this equipment such as withstand voltage, etc., to reduce. • Disposal When disposing of this product, do so in a safe manner according to local regulations. This product contains a lithium-ion battery, which should be removed at the end-of-life of the product. The battery must be recycled or disposed of in accordance with local regulations.
6 F 2 S 0 8 5 7 Contents Safety Precautions 1 1. Introduction 8 2. Application Notes 10 2.1 2.2 Protection Scheme Current Differential Protection 2.2.1 Differential Scheme 2.2.2 Stability for CT Saturation during Through-fault Conditions 2.2.3 Matching of CT Secondary Currents 2.2.4 Connection between CT Secondary Circuit and the GRT100 2.2.5 Setting 2.3 Restricted Earth Fault Protection 2.4 Overcurrent Protection 2.5 Thermal Overload Protection 2.6 Frequency Protection 2.
F 2 S 0 8 5 7 3.4 3.5 4. User Interface 4.1 4.2 4.3 4.4 4.5 5. 6. 3.3.4 IEC61850 Communication Monitoring 3.3.5 Failure Alarms 3.3.6 Trip Blocking 3.3.7 Setting Recording Function 3.4.1 Fault Recording 3.4.2 Event Recording 3.4.3 Disturbance Recording Metering Function 73 73 74 74 75 75 76 76 78 79 Outline of User Interface 4.1.1 Front Panel 4.1.2 Communication Ports Operation of the User Interface 4.2.1 LCD and LED Displays 4.2.2 Relay Menu 4.2.3 Displaying Records 4.2.
6 F 2 S 0 8 5 7 6.5 6.6 6.7 7. Function Test 6.5.1 Measuring Element 6.5.2 Timer Test 6.5.3 Protection Scheme 6.5.4 Metering and Recording Conjunctive Tests 6.6.1 On Load Test 6.6.2 Tripping Circuit Test Maintenance 6.7.1 Regular Testing 6.7.2 Failure Tracing and Repair 6.7.3 Replacing Failed Modules 6.7.4 Resumption of Service 6.7.
6 F 2 S 0 8 5 7 Appendix A Block Diagram 157 Appendix B Signal List 159 Appendix C Variable Timer List 179 Appendix D Binary Output Default Setting List 181 Appendix E Details of Relay Menu and LCD & Button Operation 185 Appendix F Case Outline 193 Appendix G External Connections 199 Appendix H Relay Setting Sheet 207 Appendix I 241 Commissioning Test Sheet (sample) Appendix J Return Repair Form 247 Appendix K Technical Data 253 Appendix L Setting of REF Element 261 Appendix M Symbo
6 F 2 S 0 8 5 7 1. Introduction GRT100 provides high-speed transformer and reactor protection, and realises high dependability and security for diverse faults such as single-phase faults, multi-phase faults, overload and over-excitation. GRT100 is used as a main protection and backup protection of the following transformers and reactors.
6 F 2 S 0 8 5 7 - Configurable binary inputs and outputs - Programmable logic for I/O configuration, alarms, indications, recording, etc.
6 F 2 S 0 8 5 7 2. Application Notes GRT100 is applied to both main protection and backup protection for the following transformers and reactors: • Two-winding or three-winding power transformers • Auto-transformers • Generator-transformer units • Shunt reactors 2.1 Protection Scheme GRT100 provides the following protection schemes with measuring elements in parentheses. Appendix A shows the block diagrams of the GRT100 series.
6 F 2 S 0 8 5 7 GRT100 1OC/1OCI 1CT THR VT FRQ V/F Calculate 3I0 HV 1nCT 1EF/1EFI LV 1REF DIFT 2nCT 2CT 2OC/2OCI Calculate 3I0 2REF 2EF/2EFI Figure 2.1.1 Measuring Elements of Model 100 series GRT100 1CT 1OC/1OCI THR VT FRQ HV Calculate 3I0 V/F 1REF LV MV 3CT 2nCT 1nCT 1EF/1EFI 3nCT DIFT 2OC/2OCI 2CT Calculate 3I0 2REF 2EF/2EFI 3OC/3OCI Calculate 3I0 3EF/3EFI Figure 2.1.
6 F 2 S 0 8 5 7 2.2 Current Differential Protection 2.2.1 Differential Scheme Current differential protection DIFT provides an overall transformer protection deriving phase current from each transformer winding, calculating the differential current on a per phase basis and detecting phase-to-phase and phase-to-earth faults. The current differential protection is based on Kirchhoff’s first law that the vector summation of all currents flowing into a protected zone must be zero. Figure 2.2.1.
6 F 2 S 0 8 5 7 “2PAND” is recommended for a transformer with small or midium capacity whose second harmonic component in inrush current is genarally higher than that of transformer with large capacity. This mode is applicable if [Phase matching] is set to “Beta”. Protection by DIF and HOC can perform instantaneous three-phase tripping of up to five breakers. Any of the five breaker tripping signals DIFT-1 to DIFT-5 are enabled or disabled by the scheme switch [DIF1] to [DIF5] settings.
6 F 2 S 0 8 5 7 Display mode following differential tripping Following a trip output, GRT100 can display either the operating phase or the faulted phase according to the user’s requirements as shown in Table 2.2.1.1. The operating phase or faulted phase display is selectable by a setting in the Record menu. Table 2.2.1.
6 F 2 S 0 8 5 7 DIFT HOC-A HOC-B HOC-C [Operating phase] 41 42 43 DIF DIF-A & DIF-B & 2F-B & 2F-C & 95 97 5F-A & 5F-B & 5F-C & 5F-Lock 45 & 46 & 1REF ≥1 1 ≥1 1 1REF1 + ≥1 1 1REF5 + 96 + & ≥1 Phase B ≥1 Phase C ≥1 & 2F-A 2F-Lock 44 Phase A & Phase N & DIF-C + 121 ≥1 98 2REF 99 2REF1 + 100 2REF5 + & ≥1 [Faulted phase] & ≥1 3REF 3REF1 + ≥1 Faulted phase selection logic & ≥1 3REF5 + Note: Models 203 and 204 are not provided with 1REF-4, 1REF-5, 2RE
6 F 2 S 0 8 5 7 2.2.2 Stability for CT Saturation during Through-fault Conditions For current differential protection of transformers, GRT100 has a strong restraint characteristic in the large current region for erroneous differential current due to CT saturation. Further, GRT100 provides a CT saturation countermeasure function.
6 F 2 S 0 8 5 7 and also the differential current at the time of an external fault with outgoing terminal CT saturation. Incoming terminal current Outgoing terminal current Differential current No change period Figure 2.2.2.
6 F 2 S 0 8 5 7 2.2.3 Matching of CT Secondary Currents The currents supplied to the differential elements must be matched in phase displacement and amplitude under through-load and through-fault conditions. Generally, it is difficult to completely match the incoming current with the outgoing current for the relay input because the CT ratios at the primary, secondary and tertiary sides of a transformer are not matched in terms of the CT ratio, phase angle and cancelling of zero-sequence current.
6 F 2 S 0 8 5 7 2 I&pb − I&pc − I&pa I&sb − I&sa , I&s 2 = (2) I&p 2 = 3 3 2 I&pc − I&pa − I&pb I&sc − I&sb , I&s3 = (3) I&p3 = 3 3 where, I&pa, I&pb, I&pc : Primary side terminal current of transformer I&sa, I&sb, I&sc : Secondary side terminal current of transformer Further, zero-sequence current is eliminated from the relay input current (Ip∗) for the calculation of the differential current as follows: 2 I&pa − I&pb − I&pc 3Ipa − ( Ipa + Ipb + Ipc) I&p1 = = = Ipa − Ipo 3 3 2 I&pb − I&pc − I&pa 3Ipb − (
6 F 2 S 0 8 5 7 2.2.3.3 Zero-sequence current elimination In addition to compensating for the phase angle between the primary and secondary currents of the transforemer, also phase angle matching prevents unnecessary operation due to zero-sequence current during an external earth fault, such as in the following cases. Case 1: When an external fault occurs at the star-connected side of the transformer shown in Figure 2.2.3.
6 F 2 S 0 8 5 7 In α-method phase matching, since the DIFT provides a function to eliminate the zero-sequence current by software, the DIFT is insensitive to the fault described. In β-method phase matching, however, since the zero-sequence current is not eliminated because of Star connection on the Delta-winding side, the DIFT may operate unnecessary. In case the GRT100 is applied to a transformer with in-zone earthing transformer, the [Phase matching] = “Alpha” setting is recommended. 2.2.3.
6 F 2 S 0 8 5 7 2.2.4 Connection between CT Secondary Circuit and the GRT100 GRT100 is provided with 2 or 3 three-phase current input terminals depending on the relay model.
6 F 2 S 0 8 5 7 2.2.5 Setting The following shows the setting elements necessary for the current differential protection and their setting ranges. Setting can be performed on the LCD screen or PC screen. Element Range Step Default Remarks ik 0.10 − 1.00 (∗) 0.01 0.30 Minimum operating current p1 10 − 100% 1% 100% % slope of small current region p2 10 − 200% 1% 200% % slope of large current region kp 1.00 − 20.00(*) 0.01 1.
6 F 2 S 0 8 5 7 Setting of ik ik determines the minimum operation sensitivity of the DIF element. ik is set as a ratio to the CT secondary rated current. The minimum sensitivity setting ik is determined from the maximum erroneous differential current under normal operating conditions.
6 F 2 S 0 8 5 7 Calculation steps Primary Secondary Tertiary 40 × 103 (1) Transformer capacity (kVA) (2) Voltage(kV) 154 66 11 (3) Rated line current(A) 150 350 2100 (4) CT ratio 60 120 240 (5) Secondary rated line current(A) =(3)/(4) 2.50 2.92 8.75 (6) CT secondary rating(A) 5 5 5 (7) Setting =(6)/(5) Kct1=2.00 Kct2=1.71 Kct3=0.57 =(1)/( 3 × (2)) Note: kct1 to kct3 should be set to 2.00 or less. If more, the CT ratio matching of relay input current may be not stable.
6 F 2 S 0 8 5 7 Setting for phase angle matching The phase angle difference between line currents on either side of the power transformer are corrected by setting according to the hands of a clock and the transformer connections described in IEC60076-1 as follows: (When α-method is selected for [Phase matching]) If a winding is star-connected, set 1 (=star) for winding setting yd_p, yd_s, and yd_t. If delta-connected, set 2 (=delta).
6 F 2 S 0 8 5 7 Table 2.2.5.2 Setting for Phase Angle Matching (for α-method) (a) Settings for typical connections of 2-windings transformer Transformer connections Settings for phase angle correction Remarks described in IEC60076-1 Primary, Secondary, Phase angle Diff. Phase angle matching Primary, Secondary (yd_p) (yd_s) (vec_s) calculation (Table 2.2.5.
6 F 2 S 0 8 5 7 (b) Settings for typical connections of 3-windings transformer Transformer connections described in IEC60076-1 Primary , Secondary, Tertiary (P) (S) (T) Yy0d1 Yy0d11 Yd1d1 Yd11d11 Dy11d0 Dy1d0 Dd0d0 Yy0y0 Settings for phase angle correction Primary, Secondary, PA Diff., Tertiary, PA Diff. (yd_p) (yd_s) (vec_s) (yd_t) (vec_t) Remarks Phase angle matching calculation (Table 2.2.5.
6 F 2 S 0 8 5 7 Table 2.2.5.
6 F 2 S 0 8 5 7 (When β-method is selected for [Phase matching]) The phase angle differences between line currents on each side of the power transformer are corrected by setting according to the hands of a clock as follows: Rule 1: If all the windings are star-connected, then take one of the windings as a reference winding and set 1 (= one o’clock) for it. For other winding(s), set the phase angle difference from the reference winding by the expression of the leading angle.
6 F 2 S 0 8 5 7 Note: The following calculation is performed in the relay for phase angle correction.
6 F 2 S 0 8 5 7 Table 2.2.5.5 Setting for Phase Angle Matching (for β-method) (a) Settings for typical connections of 2-windings transformer Transformer connections described in IEC60076-1 Settings for phase angle correction Remarks Primary , Secondary (d1) (d2) Yy0 1 , 1 Dd0 0 , 0 Yd1 1 , 0 Dy1 0 , 11 Dd2 0 , 10 Based on primary winding. or 2 , 0 Based on secondary winding. 0 , 8 Based on primary winding. or 4 , 0 Based on secondary winding.
6 F 2 S 0 8 5 7 (b) Settings for typical connections of 3-windings transformer Transformer connections described in IEC60076-1 Settings for phase angle correction Primary, Secondary, Tertiary (d1) Yy0d1 Yy0d11 Yd1d1 Yd11d11 Dy11d0 Dy1d0 Dd0d0 Yy0y0 (d2) Remarks (d3) 1 , 1 , 0 11 , 11 , 0 1 , 0 , 0 11 , 0 , 0 0 , 1 , 0 0 , 11 , 0 0 , 0 , 0 1 , 1 , 1 Note : 1.
6 F 2 S 0 8 5 7 2.3 Restricted Earth Fault Protection Restricted earth fault protection (REF) is a zero-phase current differential scheme applied to a star-connected winding whose neutral is earthed directly or through a low impedance. It gives highly sensitive protection for internal earth faults.
6 F 2 S 0 8 5 7 3REF-5. T1REF 1REF 71 t 0 0.00 - 10.00s + & 1REF-1 & 1REF-2 & 1REF-3 & 1REF-4 & 1REF-5 [1REF1] “ON” + [1REF2] “ON” + [1REF3] “ON” + [1REF4] “ON” + [1REF5] “ON” 2REF 332 ≥1 1REF TRIP 2REF-1 74 Same as above 2REF-2 2REF-3 2REF-4 2REF-5 333 2REF TRIP ≥1 3REF 3REF-1 77 Same as above 3REF-2 3REF-3 3REF-4 3REF-5 334 ≥1 3REF TRIP Note: Models 203 and 204 are not provided with 1REF-4, 1REF-5, 2REF-4, 2REF-5, 3REF-4 and 3REF-5. Figure 2.3.
6 F 2 S 0 8 5 7 Setting The following shows the setting elements for the restricted earth fault protection and their setting ranges. Element Range Step Default Remarks 1ik 0.05 − 0.50(*) 0.01 0.50 Minimum operating current 1kct1 1.00 − 50.00 0.01 1.00 1kct2 1.00 − 50.00 0.01 1.00 1kct3 1.00 − 50.00 0.01 1.00 1p2 50 − 100% 1% 100% % slope of DF2 1kp 0.50 − 2.00(*) 0.01 1.00 DF2 restraining current section of large current characteristic 2ik 0.05 − 0.50(*) 0.01 0.
6 F 2 S 0 8 5 7 Setting of kct (1kct1-1kct3, 2kct1-2kct3 and 3kct1-3kct3) CT ratio matching is performed between the line CT(s) and the neutral CT by setting 1kct1-1kct3 for 1REF element, 2kct1-2kct3 for 2REF element and 3kct1-3kct3 for 3REF element. The settings are obtained as a ratio of the line CTs ratio to the neutral CT ratio and the line CTs have the notations shown in Appendix L according to 1REF to 3REF applications.
6 F 2 S 0 8 5 7 2.4 Overcurrent Protection GRT100 provides definite time and inverse time overcurrent elements for both phase faults and earth faults, separately for each transformer winding. Three phase currents from each set of line CTs are used for the phase fault protection elements, while the earth fault protection is based on the neutral CT input.
6 F 2 S 0 8 5 7 A 1OC B C T1OC 47 48 ≥1 370 t 0 0.00 - 10.00s 49 + [1OC1] + [1OC2] + [1OC3] + [1OC4] + [1OC5] & 1OC-1 & 1OC-2 & 1OC-3 & 1OC-4 & 1OC-5 335 1OC TRIP ≥1 A 1OCI B C 50 51 52 ≥1 225 + [1OCI1] + [1OCI2] + [1OCI3] + [1OCI4] + [1OCI5] & 1OCI-1 & 1OCI-2 & 1OCI-3 & 1OCI-4 & 1OCI-5 339 1OIC TRIP ≥1 Note: 2OC and 3OC provide the same logic as 1OC. 2OCI and 3OCI provide the same logic as 1OCI.
6 F 2 S 0 8 5 7 T1EF 1EF 72 t 0 0.00 - 10.00s + [1EF1] + [1EF2] + [1EF3] + [1EF4] + [1EF5] & 1EF-1 & 1EF-2 & 1EF-3 & 1EF-4 & 1EF-5 343 1EF TRIP ≥1 1EFI 73 + [1EFI1] + [1EFI2] + [1EFI3] + [1EFI4] + [1EFI5] & 1EFI-1 & 1EFI-2 & 1EFI-3 & 1EFI-4 & 1EFI-5 346 1EFI TRIP ≥1 Note: 2EF and 3EF provide the same logic as 1EF. 2EFI and 3EFI provide the same logic as 1EFI.
6 F 2 S 0 8 5 7 Setting The following shows the setting elements for the overcurrent protection and their setting ranges. Element Range Step Default Remarks 1OC 0.10 − 20.0(*) 0.01 2.00 Definite time overcurrent (line) 2OC 0.10 − 20.0(*) 0.01 2.00 Definite time overcurrent (line) 3OC 0.10 − 20.0(*) 0.01 2.00 Definite time overcurrent (line) T1OC 0.00 − 10.00s 0.01s 1.00s Delayed tripping for 1OC T2OC 0.00 − 10.00s 0.01s 1.00s Delayed tripping for 2OC T3OC 0.00 − 10.00s 0.
6 F 2 S 0 8 5 7 differential protection and the restricted earth fault protection. When choosing settings, the following relationships between the overcurrent elements and the connected windings must be taken into account.
6 F 2 S 0 8 5 7 2.5 Thermal Overload Protection The thermal overload protection is applied to protect transformers from electrical thermal damage. A-phase current is used to detect the thermal overload of a transformer. The characteristics are exponential functions according to the IEC 60255-8 standard and take into account the I2R losses due to the particular operational current and the simultaneous cooling due to the coolant.
6 F 2 S 0 8 5 7 2.6 Frequency Protection GRT100 provides underfrequency or overfrequency protection and/or alarms for load shedding or for detecting such an overfrequency condition caused by disconnecting load from a particular generation location. The frequency element FRQ comprises two frequency elements 81-1 and 81-2, the former is used for tripping and the latter for alarms. Figure 2.6.1 shows the scheme logic of the frequency protection.
6 F 2 S 0 8 5 7 Setting The following shows the setting elements for the frequency protection and their setting ranges. Element Range Step Default Remarks 81-1 (L1, H1) 45.00 − 55.00Hz (54.00 − 66.00Hz 0.01Hz 0.01Hz 49.00Hz 59.00Hz) (*) Trip 81-2 (L2, H2) 45.00 − 55.00Hz (54.00 − 66.00Hz 0.01Hz 0.01Hz 48.00Hz 58.00Hz) Alarms UV 40 − 100V 1V 40V Undervoltage block TFRQL 0.00 − 60.00s 0.01s 10.00s Underfrequency trip time delay TFRQH 0.00 − 60.00s 0.01s 10.
6 F 2 S 0 8 5 7 2.7 Overexcitation Protection Overexcitation protection is applied to protect transformers from overvoltage and overfluxing conditions. Any single phase-to-phase connected voltage is used to detect overexcitation. Trip and alarm characteristics, which are based on a measurement of the voltage/frequency ratio, are provided. Figure 2.7.1 shows the scheme logic of overexcitation protection. Overexcitation element V/F responds to voltage/frequency and outputs three signals.
6 F 2 S 0 8 5 7 Setting The following shows the setting elements for the overexcitation protection and their setting ranges. Element Range V 100.0 − 120.0V 1.30(∗) Step Default Remarks 0.1V 100.0V Transformer rated voltage / VT ratio 0.01 1.03 Alarm A 1.03 − L 1.05 − 1.30 0.01 1.05 Low level H 1.10 − 1.40 0.01 1.
6 F 2 S 0 8 5 7 2.8 Trip by External Devices Up to four binary signals EXT. MECHANICAL TRIP1 to EXT. MECHANICAL TRIP4 can be used for tripping external devices. Figure 2.8.1 shows the scheme logic for the signal EXT_MEC.TP1. The signal can trip up to five breakers. Any of the tripping signals EXT_MEC.TP1-1 to EXT_MEC.TP4-5 can be blocked by the scheme switches [M.T1-1] to [M.T1-5] setting. Note: Models 203 and 204 are not provided with EXT_MEC.TP1-4 and EXT_MEC.TP1-5, and [M.T1-4] and [M.T1-5].
6 F 2 S 0 8 5 7 2.9 Tripping Output Figure 2.9.1 shows the tripping logic. Each protection can output five tripping signals to enable tripping for five breakers. The tripping signals are set according to the number of breakers to be tripped and drive the heavy duty, high-speed tripping output relays TRIP-1 to TRIP-5. Note: Models 203 and 204 are not provided with TRIP-4 and TRIP-5.
6 F 2 S 0 8 5 7 TRIP-1 + [L/O] Tripping output relay “ON” DIFT-1 ≥1 1OC-1 1OCI-1 1REF-1 1EF-1 1EFI-1 ≥1 1 [RESET] 2OC-1 2OCI-1 2REF-1 2EF-1 2EFI-1 ≥1 0 t 284 TRIP-1 291 TRIP-2 298 TRIP-3 305 TRIP-4 312 TRIP-5 0.2s & ≥1 ≥1 3OC-1 3OCI-1 3REF-1 3EF-1 3EFI-1 ≥1 FRQ-1 V/F-1 THR-1 MECHANICAL MECHANICAL MECHANICAL MECHANICAL S Q F/F R & ≥1 ≥1 TRIP1-1 TRIP2-1 TRIP3-1 TRIP4-1 ≥1 TRIP-2 0 Same as TRIP-1 t 0.2s TRIP-3 0 Same as TRIP-1 t 0.2s TRIP-4 0 Same as TRIP-1 t 0.
6 F 2 S 0 8 5 7 2.10 Characteristics of Measuring Elements 2.10.1 Percentage Current Differential Element DIF The segregated-phase current differential element DIF has dual percentage restraining characteristics. Figure 2.10.1 shows the characteristics of DF1 and DF2 on the differential current (Id) and restraining current (Ir) plane. Id is a vector summation of phase current of all windings and Ir is a scalar summation of phase current of all windings.
6 F 2 S 0 8 5 7 2.10.2 High-set Overcurrent Element HOC High-set overcurrent element HOC is an instantaneous overcurrent characteristic, and is applied in the differential circuit. The characteristic is expressed by the following equation: Id ≥ kh Id is defined as follows for three-winding transformer.
6 F 2 S 0 8 5 7 Ir = max.
6 F 2 S 0 8 5 7 (Example) Primary Secondary CT ratio: 2400/1 kct1=2 I01 CT ratio: 3600/1 kct2=3 I02 max-kct = 3 Therefore, REF is blocked at IBLK=3×2.0=6A (CT secondary) If the maximum of phase currents of both primary and secondary windings is 7200A (=6x1200A), the REF is blocked. Reference current: 1200A (Rated current of neutral CT) CT ratio: 1200/1 IN 1REF 2.10.
6 F 2 S 0 8 5 7 2.10.5 Definite Time Overcurrent element OC and EF The OC and EF elements measure the phase currents and the residual current respectively. 2.10.6 Thermal Overload Element THR Thermal overload element THR has a characteristic based on thermal replica according to the IEC 60255-8 standard (see Appendix N), which evaluates the phase current (A-phase) of the CT secondary circuits. Figure 2.10.5 shows the characteristic of THR element. The element has trip and alarm stages.
6 F 2 S 0 8 5 7 t TA Alarm Trip TA K ⋅ IB 0 I Figure 2.10.5 Characteristic of Thermal Overload Element Thermal Curves (Cold Curve - no prior load) 10000 Operate Time (minutes) 1000 100 τ 10 500 100 1 50 20 10 0.1 5 2 1 0.01 1 10 Overload Current (Multiple of kIB) Figure 2.10.
6 F 2 S 0 8 5 7 2.10.7 Frequency Element FRQ GRT100 has two elements for trip or alarm. Each element operates either in overfrequency or underfrequency. 2.10.8 Overexcitation Element V/F The characteristic is based on the ratio of voltage to frequency. The alarm is definite time delayed, while the tripping characteristic is either definite time or inverse time, as shown in Figure 2.10.7.
6 F 2 S 0 8 5 7 3. Technical Description 3.1 Hardware Description 3.1.1 Outline of Hardware Modules The case outline of GRT100 is shown in Appendix F. The hardware structures of the models are shown in Figure 3.1.1 and Figure 3.1.2. The front view shows the equipment without the human machine interface module. The GRT100 consists of the following hardware modules. The human machine interface module is provided with the front panel.
6 F 2 S 0 8 5 7 VCT IO3 IO2 SPM IO1 or IO8 Figure 3.1.2 Hardware Structure (Model: 102, 202, 204) The correspondence between each model and module used is as follows: Models 101 102 201 202 203 204 VCT × × × × × × SPM × × × × × × IO1 × × × × IO2 × × × × × × Module × IO3 × IO8 HMI × × × × × × × × × Note: The VCT and SPM modules are not interchangeable among different models. The hardware block diagram of the GRT100 using these moduls is shown in Figure 3.1.
6 F 2 S 0 8 5 7 Binary I/O Module (IO1 or IO8) DC/DC Converter Transformer Module (VCT) Signal Processing Module (SPM) Binary input ×13 or 12 I CT×8 or CT×12 AC input DC supply Analogue A/D filter Converter or CT×15 Binary output (High speed) MPU1 ×5 or 3 V Trip command VT×1 Binary I/O Module (IO2) Opt.
6 F 2 S 0 8 5 7 3.1.2 Transformer Module The transformer module (VCT module) provides isolation between the internal and external circuits through auxiliary transformers and transforms the magnitude of the AC input signals to suit the electronic circuits. The AC input signals are as follows: • three-phase currents (Ia, Ib and Ic) for each winding • neutral current (IN) for each winding • phase-to-phase voltage Figure 3.1.4 shows a block diagram of the transformer module.
6 F 2 S 0 8 5 7 3.1.3 Signal Processing Module The signal processing and communication module (SPM) incorporates a signal processing circuit and a communication control circuit. Figure 3.1.3.1 shows the block diagram. The signal processing circuit consists of an analog filter, multiplexer, analog to digital (A/D) converter, main processing unit (MPU) and memories (RAM and ROM), and executes all kinds of processing including protection, measurement, recording and display.
6 F 2 S 0 8 5 7 3.1.4 Binary Input and Output Module There are four types of binary input and output module (IO module): These modules are fitted according to the model (see Section 3.1.1). 3.1.4.1 IO1 and IO8 Module IO1 and IO8 provide a DC/DC converter, binary inputs and binary outputs for tripping. As shown in Figure 3.1.4.
6 F 2 S 0 8 5 7 IO8 module DC supply (+) (−) Line filter DC/DC converter FG Photo-coupler BI Binary input signals (× 12) Auxiliary relay (high speed) BI -TP-1 BI TP-2 TP-3 BI BI Figure 3.1.4.
6 F 2 S 0 8 5 7 3.1.4.2 IO2 Module As shown in Figure 3.1.4.3, the IO2 module incorporates 3 photo-coupler circuits (BI14-BI16) for binary input signals, 14 auxiliary relays (BO1-BO13 and FAIL) for binary output signals and an RS-485 transceiver. The auxiliary relay FAIL has one normally closed contact, and operates when a relay failure or abnormality in the DC circuit is detected. BO1 to BO13 each have one normally open contact. BO12 and BO13 are the high-speed operation type.
6 F 2 S 0 8 5 7 3.1.4.3 IO3 Module The IO3 module is used to increase the number of binary outputs. The IO3 module incorporates 10 auxiliary relays (BO1-BO10) for binary outputs. All auxiliary relays each have one normally open contact. IO3 module Auxiliary relay BO1 BO2 BO9 BO10 Figure 3.1.4.
6 F 2 S 0 8 5 7 3.1.5 Human Machine Interface (HMI) Module The operator can access the GRT100 via the human machine interface (HMI) module. As shown in Figure 3.1.5, the HMI module has a liquid crystal display (LCD), light emitting diodes (LED), view and reset keys, operation keys, testing jacks and an RS-232C connector on the front panel. The LCD consists of 40 columns by 4 rows with a backlight and displays record, status and setting data.
6 F 2 S 0 8 5 7 TRANSFORMER PROTECTION GRT100 101D-21-11 Operation keys Figure 3.1.
6 F 2 S 0 8 5 7 3.2 Input and Output Signals 3.2.1 Input Signals AC input signals Table 3.2.1 shows the AC input signals necessary for each of the GRT100 models and their respective input terminal numbers. See Appendix G for external connections. Winding 1, 2 and 3 in the Table correspond to high-voltage or primary, medium-voltage or secondary, and low-voltage or tertiary winding respectively. Table 3.2.1 Terminal No. GRT100-101, 102 Terminal No.
6 F 2 S 0 8 5 7 Table 3.2.2 Binary Input Signals Signal Names Driving Contact Condition / Function Enabled External Mechanical trip (EXT_MEC.TP1) External Mechanical trip (EXT_MEC.TP2) External Mechanical trip (EXT_MEC.TP3) External Mechanical trip (EXT_MEC.TP4) Indication reset Protection block Signal for event record Signal for event record Signal for event record Closed when external device operated. / Initiate trip command from operation of external device. Closed when external device operated.
6 F 2 S 0 8 5 7 Signal List +(ON) BOTD −(OFF) & Appendix C 0 6 GATES OR t 0.2s Auxiliary relay & ≧1 ≧1 6 GATES Figure 3.2.2 Configurable Output 3.2.3 PLC (Programmable Logic Controller) Function GRT100 is provided with a PLC function allowing user-configurable sequence logics on binary signals. The sequence logics with timers, flip-flops, AND, OR, NOT logics, etc. can be produced by using the PC software “PLC tool” and linked to signals corresponding to relay elements or binary circuits.
6 F 2 S 0 8 5 7 3.3 Automatic Supervision 3.3.1 Basic Concept of Supervision Though the protection system is in a non-operating state under normal conditions, it is waiting for a power system fault to occur at any time and must operate for the fault without fail. Therefore, the automatic supervision function, which checks the health of the protection system during normal operation by itself, plays an important role.
6 F 2 S 0 8 5 7 DC Supply monitoring The secondary voltage level of the built-in DC/DC converter is monitored and checked that the DC voltage is within a prescribed range. 3.3.3 PLC Data and IEC61850 Mapping Data Monitoring If there is a failure in PLC data and IEC61850 mapping data, the function may be stopped. Therefore, the PLC data and IEC61850 mapping data are monitored and an alarm of "PLC stop" or "MAP stop" is issued if any failure detected. 3.3.
6 F 2 S 0 8 5 7 Supervision Item LCD Message LED "IN SERVICE" Ping err on Ping response check (1): (2): (3): (4): 3.3.6 LED "ALARM" on Ext. alarm (4) Event record Message Relay fail-A Diverse messages are provided as expressed with "---fail" in the Table in Section 6.7.2. The LED is on when the scheme switch [SVCNT] is set to "ALM" and off when set to "ALM & BLK" (refer to Section 3.3.4). Whether the LED is lit or not depends on the degree of the voltage drops.
6 F 2 S 0 8 5 7 3.4 Recording Function GRT100 is provided with the following recording functions: Fault recording Event recording Disturbance recording These records are displayed on the LCD of the relay front panel or on the local or remote PC. 3.4.1 Fault Recording Fault recording is started by a tripping command of the GRT100 or PLC command by user-setting (max.
6 F 2 S 0 8 5 7 - Magnitude of phase differential current (Ida, Idb, Idc) - Magnitude of residual differential current for REF protection (Id01 up to Id03) - Percentage of thermal capacity (THM%) Phase angles above are expressed taking that of the voltage as a reference phase angle. If the voltage input is not provided, then the positive sequence current of the primary winding is used as a reference phase angle. 3.4.
6 F 2 S 0 8 5 7 The number of records stored depends on the post-fault recording time. The approximate relationship between the post-fault recording time and the number of records stored is shown in Table 3.4.2. Note: If the recording time setting is changed, all previously recorded data is deleted. Table 3.4.2 Post Fault Recording Time and Number of Disturbance Records Stored Recording time Model 0.1s 0.5s 1.0s 1.5s 2.0s 2.5s 3.
6 F 2 S 0 8 5 7 3.5 Metering Function The GRT100 performs continuous measurement of the analogue input quantities. The measurement data shown below are displayed on the LCD of the relay front panel or on the local or remote PC.
6 F 2 S 0 8 5 7 4. User Interface 4.1 Outline of User Interface The user can access the relay from the front panel. Local communication with the relay is also possible using a personal computer (PC) via an RS232C port. Furthermore, remote communication is also possible using RSM (Relay Setting and Monitoring), IEC103 communication via an RS485, optical fibre or Ethernet LAN etc.
6 F 2 S 0 8 5 7 Operation keys The operation keys are used to display records, status, and set values on the LCD, as well as to input or change set values. The function of each key is as follows: c 0-9, −: d , Used to enter a selected number, numerical values and text strings. : Used to move between lines displayed on a screen Keys 2, 4, 6 and 8 marked with strings. , , and are also used to enter text e CANCEL : Used to cancel entries and return to the upper screen.
6 F 2 S 0 8 5 7 4.1.2 Communication Ports The following 3 individual interfaces are mounted as the communication ports: • RS232C port • Serial communication port (RS485 port, optional Fibre optic or Ethernet LAN etc.) • IRIG-B port (1) RS232C port This connector is a standard 9-way D-type connector for serial port RS232C transmission and mounted on the front panel.
6 F 2 S 0 8 5 7 4.2 Operation of the User Interface The user can access such functions as recording, measurement, relay setting and testing with the LCD display and operation keys. 4.2.1 LCD and LED Displays Displays during normal operation When the GRT100 is operating normally, the green "IN SERVICE" LED is lit and the LCD is off. Press the VIEW key when the LCD is off to display the digest screens which are "Metering", "Latest fault" and "Auto-supervision" screens in turn.
6 F 2 S 0 8 5 7 off the "TRIP" LED. Refer to Table 4.2.1 Step 2. 3) When only the "TRIP" LED is go off by pressing the RESET key in short period, press the RESET key again to reset remained LEDs in the manner 1) on the "Latest fault" screen or other digest screens. LED1 through LED4 will remain lit in case the assigned signals are still active state. Table 4.2.
6 F 2 S 0 8 5 7 1) When configurable LEDs (LED1 through LED4) are assigned to latch signals by issuing an alarm, press the RESET key more than 3s until all LEDs reset except "IN SERVICE" LED. 2) When configurable LED is still lit by pressing RESET key in short period, press RESET key again to reset remained LED in the above manner. 3) LED1 through LED4 will remain lit in case the assigned signals are still active state. While any of the menu screens is displayed, the VIEW and RESET keys do not function.
6 F 2 S 0 8 5 7 Menu Record Fault record Event record Disturbance record Status Metering Binary input & output Relay element Time synchronization source Clock adjustment Setting (view) Relay version Description Communication Record Status Protection Binary input Binary output LED Setting (change) Password Description Communication Record Status Protection Binary input Binary output LED Test Switch Binary output Timer Logic circuit Figure 4.2.
6 F 2 S 0 8 5 7 Record In the "Record" menu, the fault records, event records and disturbance records are displayed or erased. Status The "Status" menu displays the power system quantities, binary input and output status, relay measuring element status, signal source for time synchronization (IRIG-B, RSM or IEC) and adjusts the clock.
6 F 2 S 0 8 5 7 /6 VT & 1CT ( 2CT ( CT ratio 1- 20O00): 1- 20O00): 1/ 2000 1000 3CT ( 1- 20O00): 400 1 2 3 V ( ( ( ( 1111- 2 2 2 2 1 1 1 4 nCT nCT nCT T 0 0 0 0 O00 O00 O00 O00 7 ): ): ): ): 00 00 00 00 To move to the lower screen or move from the left-side screen to the right-side screen in Appendix E, select the appropriate number on the screen. To return to the higher screen or move from the right-side screen to the left-side screen, press the END key.
6 F 2 S 0 8 5 7 Date and Time Fault phase Tripping mode Power system quantities /4 Fault Record #1 16/Oct/1997 18:13:57.031 Phase BC Trip DIFT Prefault values Ia1 **.**kA ***.*° Ib1 **.**kA ***.*° Ic1 **.**kA ***.*° I11 **.**kA ***.*° I21 **.**kA ***.*° I01 **.**kA ***.*° In1 **.**kA ***.*° Ia3 **.**kA ***.*° Ib3 **.**kA ***.*° Ic3 **.**kA ***.*° I13 **.**kA ***.*° I23 **.**kA ***.*° I03 **.**kA ***.*° In3 **.**kA ***.*° V ***.*kV ***.*° Ida ***.**pu la2 lb2 lc2 l12 l22 l02 ln2 3/42 1-2-3-4-5 **.**kA *
6 F 2 S 0 8 5 7 /2 Fault record Clear all fault records? ENTER=Yes CANCEL=No • Press the ENTER (= Yes) key to clear all the fault records stored in non-volatile memory. If all fault records have been cleared, the "Latest fault" screen of the digest screens is not displayed. 4.2.3.2 Displaying Event Records To display events records, do the following: • Open the top "MENU" screen by pressing any keys other than the VIEW and RESET keys. • Select 1 (= Record) to display the "Record" sub-menu.
6 F 2 S 0 8 5 7 • Select 1 (= Record) to display the "Record" sub-menu. • Select 3 (= Disturbance record) to display the "Disturbance record" screen. / 2 Dis t u rba n c e reco rd 2=Clear 1 = D i s p l ay • Select 1 (= Display) to display the date and time of the disturbance records from the top in new-to-old sequence. /3 #1 #2 #3 Dis 16 20 04 t / / / ur Oc Se Ju ba t/ p/ l/ nc 19 19 19 e reco 97 18: 97 15: 97 11: rd 13:57.031 29 :22 .463 54:53.
6 F 2 S 0 8 5 7 /1 Sta 1=Mete 3=Rela 5=Cloc tus ring y element k a d j u s t m ent 2=Binary I/O 4=Time sync source • Select 1 (= Metering) to display the "Metering" screen. /2 Metering Ia1 ∗∗.∗∗kA 16/Oct/1997 18:13 3/20 ∗∗∗.∗° Ia2 ∗∗.∗∗kA ∗∗∗.∗° Ib1 ∗∗.∗∗kA ∗∗∗.∗° Ib2 ∗∗.∗∗kA ∗∗∗.∗° Ic1 ∗∗.∗∗kA ∗∗∗.∗° Ic2 ∗∗.∗∗kA ∗∗∗.∗° I11 I21 ∗∗.∗∗kA ∗∗.∗∗kA ∗∗∗.∗° ∗∗∗.∗° I12 I22 ∗∗.∗∗kA ∗∗.∗∗kA ∗∗∗.∗° ∗∗∗.∗° I01 In1 ∗∗.∗∗kA ∗∗.∗∗kA ∗∗∗.∗° ∗∗∗.∗° I02 In2 ∗∗.∗∗kA ∗∗.∗∗kA ∗∗∗.∗° ∗∗∗.∗° Ia3 ∗∗.
6 F 2 S 0 8 5 7 4.2.4.2 Displaying the Status of Binary Inputs and Outputs To display the binary input and output status, do the following: • Select 2 (= Status) on the top "MENU" screen to display the "Status" screen. • Select 2 (= Binary I/O) to display the binary input and output status. (Binary inputs and outputs depend oh the relay model.
6 F 2 S 0 8 5 7 4.2.4.3 Displaying the Status of Measuring Elements To display the status of the measuring elements on the LCD, do the following: • Select 2 (= Status) on the top "MENU" screen to display the "Status" screen. • Select 3 (= Relay element) to display the status of the relay elements.
6 F 2 S 0 8 5 7 4.2.4.4 Displaying the Status of the Time Synchronization Source The inner clock of the GRT100 can be synchronized with external clocks such as the IRIG-B time standard signal clock or RSM (relay setting and monitoring system) clock or by an IEC60870-5-103 or SNTP server. To display on the LCD whether these clocks are active or inactive and which clock the relay is synchronized with, do the following: • Select 2 (= Status) on the top "MENU" screen to display the "Status" screen.
6 F 2 S 0 8 5 7 4.2.5 Viewing the Settings The sub-menu "Setting (view)" is used to view the settings made using the sub-menu "Setting (change)" except for the relay version. The following items are displayed: Relay version Description Address in the RSM, IEC60870-5-103 or IEC61850 communication Recording setting Status setting Protection setting Binary input setting Binary output setting LED setting Enter a number on the LCD to display each item as described in the previous sections. 4.2.5.
6 F 2 S 0 8 5 7 Recording Status Protection Binary input Binary output LED All of the above settings except the password can be seen using the "Setting (view)" sub-menu. 4.2.6.1 Setting Method There are three setting methods as follows. - To enter a selective number - To enter numerical values - To enter a text string To enter a selected number If a screen as shown below is displayed, perform setting as follows.
6 F 2 S 0 8 5 7 To correct the entered number, do the following. • If it is before pressing the ENTER key, press the CANCEL key and enter the new number. • If it is after pressing the ENTER key, move the cursor to the correct line by pressing the and keys and enter the new number. Note: If the CANCEL key is pressed after any entry is confirmed by pressing the ENTER key, all the entries performed so far on the screen concerned are canceled and screen returns to the upper one.
6 F 2 S 0 8 5 7 To correct the entered numerical value, do the following. • If it is before pressing the ENTER key, press the CANCEL key and enter the new numerical value. • If it is after pressing the ENTER key, move the cursor to the correct line by pressing the and keys and enter the new numerical value. Note: If the CANCEL key is pressed after any entry is confirmed by pressing the ENTER key, all the entries made so far on the screen concerned are canceled and the screen returns to the upper one.
6 F 2 S 0 8 5 7 and to turn to the "Setting (change)" sub-menu. 4.2.6.2 Password For the sake of security of changing the settings and testing the relay, password protection can be set as follows; • Press 4 (= Setting (change)) on the main "MENU" screen to display the "Setting (change)" screen. /1 Setting(change ) 1=Password 2=Description 3=RSM comm 6=Protection 5=Status 4=Record 9=LED 8=Binary output 7=Binary input • Press 1 (= Password) to display the "Password" screen.
6 F 2 S 0 8 5 7 Canceling or changing the password To cancel the password protection, enter "0000" in the two brackets on the "Password" screen. The "Setting (change)" screen is then displayed without having to enter a password. The password can be changed by entering a new 4-digit number on the "Password" screen in the same way as the first password setting. If you forget the password Press CANCEL and RESET together for one second on the top "MENU" screen.
6 F 2 S 0 8 5 7 • / H I S 3 Address/P DL C ( 1 EC ( 0 YA DJ( -9999 I I I I S S S S G G G G S S S S P1 P1 P1 P1 M1 M1 M1 M1 W1 W1 W1 W1 I1 I1 I1 I1 -1 -2 -3 -4 -1 -2 -3 -4 -1 -2 -3 -4 -1 -2 -3 -4 ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 S S S S S G P P P P I4 I4 I4 I4 MO OI G1 G1 G1 G1 -1( -2( -3( -4( DE( NT( -1( -2( -3( -4( 0 0 0 0 0 1 0 0 0 0 a r a m e te r 32): 2 54 ) : 9999): : - 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 1 2 0 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54 54
6 F 2 S 0 8 5 7 (baud rate) and test mode setting, etc., of the RSM or IEC60870-5-103 or IEC61850. /3 PR 23 IE IE 85 85 TS GS PI Switch TCL1 2C CBR CBLK 0BLK 0AUT TMOD ECHK NGCHK 1/ 1=HD 1=9. 1=9. 1=No 1=No 0=Of 0=Of 0=Of 0=Of LC 2=IEC103 6 2=19.2 3=38.4 6 2=19.2 rmal 2=Blocked rmal 2=Blocked f 1= On f 1= On f 1= On f 1= On 4=57.6 * 2 4 2 1 1 1 0 0 0 • Select the number corresponding to the system and press the ENTER key.
6 F 2 S 0 8 5 7 This function is to check the health of network by regularly sending Ping to IP address which is set on PG∗-∗. Select 1 (=On) to execute Ping response check. 4.2.6.5 Setting the Recording To set the recording function as described in Section 4.2.3, do the following: • Press 4 (= Setting (change)) on the main "MENU" screen to display the "Setting (change)" screen. • Press 4 (= Record) to display the "Record" screen.
6 F 2 S 0 8 5 7 • Enter the number of event to record the status change both to "On" and "Off". If enter 20, both status change is recorded for EV1 to EV20 events and only the status change to "On" is recorded for EV21 to EV128 events. • Enter the signal number to record as the event in Appendix B. It is recommended that this setting can be performed by RSM100 because the signal name cannot be entered by LCD screen. (Refer to Section 3.4.2.
6 F 2 S 0 8 5 7 setting can be performed by RSM100 because the signal name cannot be entered by LCD screen. (Refer to Section 3.4.3.) 4.2.6.6 Status To set the status display described in Section 4.2.4, do the following. Press 5 (= Status) on the "Setting (change)" sub-menu to display the "Status" screen. /2 Status 1=Metering 2=Time synchronization 3=Time zone Setting the metering • Press 1 (= Metering) to display the "Metering" screen.
6 F 2 S 0 8 5 7 4.2.6.7 Protection The GRT100 can have 8 setting groups for protection according to the change of power system operation, one of which is assigned to be active. To set protection, do the following: • Press 6 (= Protection) on the "Setting (change)" screen to display the "Protection" screen. /2 Protec 1=Change 2=Change 3=Copy gr ti ac se ou on tive group tting p Changing the active group • Press 1 (= Change active group) to display the "Change active group" screen.
6 F 2 S 0 8 5 7 /6 VT & CT 1CT ( 2CT ( 3C T ( 1nCT ( 2n CT ( 3n CT ( VT ( r atio 1 - 2 0 00 0 ): 1 - 2 0 00 0 ): 1 - 20 000 ): 1 - 20 000 ): 1 - 20 000 ): 1 - 20 000 ): 1 - 20 000 ): 1 /7 2 000 1 000 400 100 100 100 400 • Enter the VT ratio and press the ENTER key. • Enter the CT ratio and press the ENTER key. CAUTION Do not set the CT primary rated current. Set the CT ratio.
6 F 2 S 0 8 5 7 /6 Scheme DIFTPMD 1REF 2REF 3REF REF_DEF M1OCI M2 OCI M3OCI M1EFI M2EFI M3EFI L/O 2F-LOCK 5F-LOCK DIF1 DIF2 DIF3 : M.T4-1 M.T4-2 M.
6 F 2 S 0 8 5 7 /7 ik p1 p2 DIFT ( ( ( kp kct1 kct2 kct3 yd_p yd _s v e c_ s y d _t v e c_ t k2f k5f kh ( ( ( ( ( ( ( ( ( ( ( ( 0.101010- 1.00): 100): 200): 1. 0. 0. 0. 00- 20 .00): 05- 50 .00): 05- 50 .00): 05- 50 .00): 2): 12): 111): 12): 111): 150 ): 10100 ): 102.00- 20 .00): 0.10 10 100 1. 1. 1. 2. 00 00 50 00 1 1 0 1 0 10 50 2.00 1/15 pu % % pu % % pu [ • Press 2 (= REF) to display the "REF" screen.]
6 F 2 S 0 8 5 7 • Enter the numerical value and press the ENTER key for each element. • After setting all elements, press the END key to return to the "Protection element" menu. 1/24 /7 OC 1OC 2OC 3OC ( ( ( 0.100.100.10- 20.00): 20.00): 20.00): 0.10 0.10 0.10 pu pu pu T T T 1 2 3 T T T 1 2 3 T T T 1 2 3 T T T ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( ( 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 10.0 10.0 10.0 5.0 5.0 5.0 1.0 1.0 1.0 20.0 20.0 20.0 10.0 10.0 10.0 5.0 5.0 5.0 1.0 1.0 1.
6 F 2 S 0 8 5 7 /7 V A L H L H R T T V/F ( ( ( T T T VFH VFA ( ( ( ( ( ( 10 0 . 0 1.031.051.10 1 1 60 1 1 12 0 . 0 ) : 1.30): 1.30): - 1 . 6 6 3 6 6 6 4 0 0 0 0 0 0 0 0 0 0 0 ) ) ) ) ) ) : : : : : : 1/ V pu pu 100.0 1.10 1 .20 9 pu s s s s s 1.30 1 1 60 1 1 • Press 6 (= FRQ) to display the “FRQ” screen. The measuring elements and timers used in the frequency protection are set using this screen. • Enter the numerical value and press the ENTER key for each element.
6 F 2 S 0 8 5 7 /2 Binary BISW 1 BISW 2 BISW 3 input 1=Norm 2=Inv BISW 4 BISW 5 : B I S W 14 B I S W 15 B I S W 16 1 /15 1 1 1 1 1 : 1 1 1 • Enter 1 (= Normal) or 2 (= Inverted) and press the ENTER key for each binary input. 4.2.6.9 Binary Output All the binary outputs of the GRT100 except the tripping command, and the relay failure signal are user-configurable. It is possible to assign one signal or up to six ANDing or ORing signals to one output relay. Available signals are listed in Appendix B.
6 F 2 S 0 8 5 7 Setting the logic gate type and timer • Press 1 to display the "Logic gate type and delay timer" screen. /5 Logic gate Logic 1=OR BOTD 0=Off type & 2=AND 1=On delay timer 1/ 1 1 2 • Enter 1 or 2 to use an OR gate or AND gate and press the ENTER key. • Enter 0 or 1 to add 0.2s drop-off delay time to the output relay or not and press the ENTER key. • Press the END key to return to the "Setting" screen.
6 F 2 S 0 8 5 7 Setting the logic gate type and reset • Press 1 to display the "Logic gate type and reset" screen. /4 Logic gate type & reset Logic 1=OR 2=AND Reset 0=Inst 1=Latch 1/ 1 1 2 • Enter 1 or 2 to use an OR gate or AND gate and press the ENTER key. • Enter 0 or 1 to select “Instantaneous reset” or “Latch reset” and press the ENTER key. • Press the END key to return to the "Setting" screen. Note: To release the latch state, refer to Section 4.2.1.
6 F 2 S 0 8 5 7 alarm purposes. Caution: Be sure to restore these switches after the tests are completed. Disabling automatic monitoring • Press 5 (= Test) on the top "MENU" screen to display the "Test" screen. /1 Test 1=Switch 3=Timer 2=Binary output 4=Logic circuit • Press 1 (= Switch) to display the "Switch" screen. /2 Switch A.M.F. 0=Off Reset 0=Off IECTST 0=Off 1=On 1=On 1=On 1/ 3 1 0 1 • Enter 0 for A.M.F to disable the A.M.F. and press the ENTER key.
6 F 2 S 0 8 5 7 /3 IO# IO# IO# BO 2 2 2 IO# IO# IO# IO# IO# IO# IO# IO# IO# IO# IO# 2 2 2 2 2 2 2 2 2 2 2 (0 =Disable 1=Enable) BO1 BO2 BO3 B B B B B B B B B F O4 O5 O6 O7 O8 O9 O10 O11 O12 AIL 1 /14 1 1 1 0 0 0 0 0 0 0 0 0 0 0 BO13 • Enter 1 and press the ENTER key. • After completing the entries, press the END key. Then the LCD displays the screen shown below. /3 BO Keep pressing Press CANCEL 1 to to operate. cancel. • Keep pressing 1 key to operate the output relays forcibly.
6 F 2 S 0 8 5 7 initiated and the following display appears. The input and output signals of the timer can be observed at monitoring jacks A and B respectively. The LEDs above monitoring jacks A or B are also lit if the input or output signal exists. /2 Tim Operat Press Press e i E C r ng... ND to ANCEL reset. to cancel. • Press the END key to reset the input signal to the timer. The "TESTING" LED turns off. • Press the CANCEL key to test other timers. Repeat the above testing. 4.2.7.
6 F 2 S 0 8 5 7 4.3 Personal Computer Interface The relay can be operated from a personal computer using an RS-232C port on the front panel. On the personal computer, the following analysis and display of the fault voltage and current are available in addition to the items available on the LCD screen.
6 F 2 S 0 8 5 7 Twisted paired cable G1PR2 Figure 4.4.1.1 Relay Setting and Monitoring System (1) UTP cable (10Base-T or 100Base TX) 214B-13- 10 100/1 10/1 15/1 20V HUB. PC Other relays Relay Figure 4.4.1.2 Relay Setting and Monitoring System (2) 4.4.2 IEC 60870-5-103 Interface The relay can support the IEC60870-5-103 communication protocol.
6 F 2 S 0 8 5 7 4.4.3 IEC 61850 interface The relay can also communicate with substation automation system via Ethernet communication networks using IEC 61850 protocols. Figure 4.4.3.1 Substation Automation System using Ethernet-based IEC 61850 protocol 4.
6 F 2 S 0 8 5 7 5. Installation 5.1 Receipt of Relays When relays are received, carry out the acceptance inspection immediately. In particular, check for damage during transportation, and if any is found, contact the vendor. Check that the following accessories are attached. • 3 pins for the monitoring jack, packed in a plastic bag. • An optional attachment kit required in rack-mounting. (See Appendix F.
6 F 2 S 0 8 5 7 CAUTION • Before removing a module, ensure that you are at the same electrostatic potential as the equipment by touching the case. • Handle the module by its front plate, frame or edges of the printed circuit board. Avoid touching the electronic components, printed circuit board or connectors. • Do not pass the module to another person without first ensuring you are both at the same electrostatic potential. Shaking hands achieves equipotential.
6 F 2 S 0 8 5 7 6. Commissioning and Maintenance 6.1 Outline of Commissioning Tests The GRT100 is fully numerical and the hardware is continuously monitored. Commissioning tests can be kept to a minimum and need only include hardware tests and conjunctive tests. The function tests are at the user’s discretion. In these tests, user interfaces on the front panel of the relay or local PC can be fully applied.
6 F 2 S 0 8 5 7 6.2 Cautions 6.2.1 Safety Precautions CAUTION • The relay rack is provided with a grounding terminal. Before starting the work, always make sure the relay rack is grounded. • When connecting the cable to the back of the relay, firmly fix it to the terminal block and attach the cover provided on top of it. • Before checking the interior of the relay, be sure to turn off the power. Failure to observe any of the precautions above may cause electric shock or malfunction. 6.2.
6 F 2 S 0 8 5 7 6.3 Preparations Test equipment The following test equipment is required for the commissioning tests.
6 F 2 S 0 8 5 7 6.4 Hardware Tests The tests can be performed without external wiring, but DC power supply and AC voltage and current source are required. 6.4.1 User Interfaces This test ensures that the LCD, LEDs and keys function correctly. LCD display • Apply the rated DC voltage and check that the LCD is off. Note: If there is a failure, the LCD displays the "Auto-supervision" screen when the DC voltage is applied.
6 F 2 S 0 8 5 7 6.4.2 Binary Input Circuit The testing circuit is shown in Figure 6.4.1. GRT100 TB4 GRT100 TB4 -A4 BI1 -B4 BI2 : : -A10 : : -B4 -A4 -B5 -A5 BI1 BI2 : : : : -B10 -A10 BI13 BI12 -B11 TB3 -A14 TB3 -A14 BI14 -B14 BI15 -A15 -B15 -B14 BI14 BI15 -A15 BI16 BI16 -B15 + DC power supply − + DC power supply − TB4 -A16 -A17 TB4 -A16 -A17 E E (a) For Model 203, 204 (a) For Model 101,102, 201, 202 Figure 6.4.
6 F 2 S 0 8 5 7 6.4.3 Binary Output Circuit This test can be performed by using the "Test" sub-menu and forcibly operating the relay drivers and output relays. Operation of the output contacts is monitored at the output terminal. The output contact and corresponding terminal number are shown in Appendix G. • Press 2 (= Binary output) on the "Test" screen to display the "Binary output" screen. The LCD displays the output modules mounted, depending on the model.
6 F 2 S 0 8 5 7 6.4.4 AC Input Circuits This test can be performed by applying the checking voltages and currents to the AC input circuits and verifying that the values applied coincide with the values displayed on the LCD screen. The testing circuit for Model 100 series is shown in Figure 6.4.2. A single-phase voltage source and two single-phase current sources are required. (Test Model 200 series by same testing method of Model 100 series.
6 F 2 S 0 8 5 7 6.5 Function Test 6.5.1 Measuring Element Measuring element characteristics are realized by the software, so it is possible to verify the overall characteristics by checking representative points. Operation of the element under test is observed by the binary output signal at monitoring jacks A or B or by the LED indications above the jacks. In any case, the signal number corresponding to each element output must be set on the "Logic circuit" screen of the "Test" sub-menu.
6 F 2 S 0 8 5 7 GRT100 + Single-phase current source − A TB1 -1 Ia -2 Monitoring jack DC power supply + TB4 -A16 − -A17 A 0V E DC voltmeter + − Figure 6.5.1 Operating Current Value Test Circuit (Model 100s, 200s) The output signal numbers of the DIF elements are as follows: Element Signal number DIF-A 44 DIF-B 45 DIF-C 46 • Press 4 (= Logic circuit) on the "Test" sub-menu screen to display the "Logic circuit" screen.
6 F 2 S 0 8 5 7 Iout DF2 DF1 0 ik Iin 2+p1 2−p1 2 kp + 4 ik Figure 6.5.2 Current Differential Element (Iout - Iin Plane) Figure 6.5.3 shows a testing circuit simulating an infeed from a primary winding and outflow from a secondary winding. GRT100 Infeed current (Iin) + Single-phase current source − Iin -2 Outflow current (Iout) + Single-phase current source − DC power supply TB1 -1 A φ Monitoring jack -9 A Iout A 0V -10 + TB4 -A16 − -A17 E DC voltmeter + − Figure 6.5.
6 F 2 S 0 8 5 7 • Press 4 (= Logic circuit) on the "Test" sub-menu screen to display the "Logic circuit" screen. • Enter a signal number 44 to observe the DIF-A output at monitoring jack A and press the ENTER key. • Apply an infeed current to terminal TB1-1 and -2. When the infeed current applied is larger than the setting of ik (pu) and smaller than kp(2+p1)/2 + ik(2-p1)/4 (pu), characteristic DF1 is checked.
6 F 2 S 0 8 5 7 GRT100 A Single-phase current source TB1 -1 Ia -2 Monitoring jack DC power supply + TB4 -A16 − -A17 A 0V E Start Time counter Stop OV Figure 6.5.4 Operating Time Test (Model 100s, 200s) • Set a test current to 3 times of DIF operating current (= CT secondary rated current × ik setting). • Apply the test current and measure the operating time. • Check that the operating time is 40 ms or less.
6 F 2 S 0 8 5 7 6.5.1.2 2F element The testing circuit is shown in Figure 6.5.5. Current source 50 or 60Hz Current source GRT100 + TB1 I1 -1 Ia − -2 + I2 − 100 or 120Hz Monitoring jack A 0V DC power supply DC voltmeter + TB4 -A16 − -A17 + − Figure 6.5.5 Testing 2F Element (Model 100s, 200s) The output signal number of the 2F element is as follows: Element 2F Signal number 122 • Set the second harmonic restraint setting k2f to 15%(= default setting).
6 F 2 S 0 8 5 7 6.5.1.3 5F element The testing circuit is shown in Figure 6.5.6. Current source GRT100 + TB1 I1 -2 50 or 60Hz Current source -1 Ia − + I2 − 250 or 300Hz Monitoring jack A 0V DC power supply DC voltmeter + TB4 -A16 − -A17 + − Figure 6.5.6 Testing 5F Element (Model 100s, 200s) The output signal number of the 5F element is as follows: Element 5F Signal number 123 • Set the fifth harmonic restraint setting k5f to 30%.
6 F 2 S 0 8 5 7 6.5.1.4 High-set overcurrent element HOC Operating current value The testing circuit is shown in Figure 6.5.1. The output signal numbers of the HOC elements are as follows: Element Signal number HOC-A 41 HOC-B 42 HOC-C 43 • Press 4 (= Logic circuit) on the "Test" sub-menu screen to display the "Logic circuit" screen. • Enter a signal number 41 to observe the HOC-A output at monitoring jack A and press the ENTER key.
6 F 2 S 0 8 5 7 6.5.1.5 Restricted earth fault element REF The restricted earth fault element is checked on the following items. • Operating current value • Percentage restraining characteristic Note: Set all the CT ratio matching settings (1kct1 - 1kct3 to 3kct1 - 3kct3) to "1", because the operating value depends on the settings. Operation current value The testing circuit is shown in Figure 6.5.7.
6 F 2 S 0 8 5 7 Percentage restraining characteristics The percentage restraining characteristic is tested on the outflow current (lout) and infeed current (lin) plane as shown in Figure 6.5.8. The characteristic shown in Figure 6.5.8 is equivalent to the one on the differential current (ld) and restraining current (lr) plane shown in Figure 2.11.2. Iout DF2 DF1 Operating zone ik 0 [kp・p2 + (1- p1)ik]/(p2 – p1) Iin Figure 6.5.8 REF_DIF Element (Iout - Iin Plane) Figure 6.5.
6 F 2 S 0 8 5 7 • Apply an infeed current to terminal TB1-1 and -2. When the infeed current applied is larger than the setting of ik (pu) and smaller than [kp⋅p2 + (1−p1)ik]/(p2 − p1) (pu), characteristic DF1 is checked. When the infeed current applied is larger than [kp⋅p2 + (1−p1)ik]/(p2 − p1) (pu), characteristic DF2 is checked. Note: When the default settings are applied, the critical infeed current which determines DF1 checking or DF2 checking is 1.6×(CT secondary rated current).
6 F 2 S 0 8 5 7 6.5.1.6 Definite time overcurrent elements OC, EF The testing circuit is shown in Figure 6.5.10. GRT100 A Single-phase current source TB1 -1 -2 -7 -8 Ia IN Monitoring jack DC power supply + TB4 -A16 − -A17 A 0V E Figure 6.5.10 Testing OC and EF (Model 100s, 200s) Element Signal number 1OC, 2OC, 3OC 47, 53, 59 1EF, 2EF, 3EF 72, 75, 78 The testing procedure is as follows: • Press 4 (= Logic circuit) on the "Test" sub-menu screen to display the "Logic circuit" screen.
6 F 2 S 0 8 5 7 6.5.1.7 Inverse time overcurrent elements OCI, EFI The testing circuit is shown in Figure 6.5.11. GRT100 A Single-phase current source TB1 -1 -2 -7 -8 Ia IN Monitoring jack DC power supply + TB4 -A16 − -A17 A 0V E Start Time counter Stop OV Figure 6.5.
6 F 2 S 0 8 5 7 6.5.1.8 Thermal overload element THR The testing circuit is shown in Figure 6.5.12. GRT100 + Single-phase current − source A TB1 -1 Ia -2 Monitoring jack DC power supply + TB4 -A16 − -A17 A 0V E Start Time counter Stop OV Figure 6.5.12 Testing THR (Model 100s, 200s) The output signal of testing element is assigned to the monitoring jack A. The output signal numbers of the elements are as follows: Element Signal No.
6 F 2 S 0 8 5 7 6.5.1.9 Frequency element FRQ The frequency element is checked on the following items • Operating frequency • Undervoltage block Operating frequency test The testing circuit is shown in Figure 6.5.13. GRT100 V Variable frequency source DC power supply f + TB1 -27 V − -28 + TB4 -A16 − -A17 Monitoring jack A 0V E DC voltmeter + − Figure 6.5.
6 F 2 S 0 8 5 7 6.5.1.
6 F 2 S 0 8 5 7 Operating time characteristic test The testing circuit is shown in Figure 6.5.15. GRT100 V TB1 -27 Single-phase voltage source V -28 DC power supply + TB4 -A16 − -A17 Monitoring jack A 0V E Start Time counter Stop OV Figure 6.5.15 Operating Time Characteristic Test of V/F (Model 100s, 200s) The testing procedure is as follows: • Press 4 (= Logic circuit) on the "Test" sub-menu screen to display the "Logic circuit" screen.
6 F 2 S 0 8 5 7 • Press 3 (= Timer) on the "Test" sub-menu screen to display the "Timer" screen. • Enter the number corresponding to the timer to be observed. The timers and assigned numbers are listed in Appendix C. • Press the END key to display the following screen. /2 Timer Press ENTER Press CANCEL to to operate. cancel. • Press the ENTER key to start measuring the time. The "TESTING" LED turns on, and timer is initiated and the following display appears.
6 F 2 S 0 8 5 7 6.5.3 Protection Scheme In the protection scheme tests, a dynamic test set is required to simulate power system pre-fault, fault and post-fault conditions. Tripping is observed with the tripping command output relays TRIP-1 to -5. Check that the indications and recordings are correct. 6.5.4 Metering and Recording The metering function can be checked while testing the AC input circuit. See Section 6.4.4. Fault recording can be checked while testing the protection schemes.
6 F 2 S 0 8 5 7 6.6 Conjunctive Tests 6.6.1 On Load Test With the relay connected to the line which is carrying a load current, it is possible to check the polarity of the voltage transformer and current transformer and the phase rotation with the metering displays on the LCD screen. • Open the following "Metering" screen from the "Status" sub-menu. /2 Metering Ia1 ∗∗.∗∗kA 16/Oct/1997 18:13 3/20 ∗∗∗.∗° Ia2 ∗∗.∗∗kA ∗∗∗.∗° Ib1 ∗∗.∗∗kA ∗∗∗.∗° Ib2 ∗∗.∗∗kA ∗∗∗.∗° Ic1 ∗∗.∗∗kA ∗∗∗.∗° Ic2 ∗∗.
6 F 2 S 0 8 5 7 /3 IO# IO# IO# BO 1 (0 =Disable 1=Enable) 1 1 TP-1 TP-2 TP-3 1/ 1 1 1 IO# 1 IO# 1 TP-4 TP-5 0 0 5 TP-1 to 5 are output relays with one normally open contact. Models 203 and 204 are not provided with TP-4 and TP-5. • Enter 1 for TP-1 and press the ENTER key. • Press the END key. Then the LCD displays the screen shown below. /3 BO Keep pressing Press CANCEL 1 to to operate. cancel. • Keep pressing the 1 key to operate the output relay TP-1 and check that the No.
6 F 2 S 0 8 5 7 6.7 Maintenance 6.7.1 Regular Testing The relay is almost completely self-supervised. The circuits which cannot be supervised are binary input and output circuits and human interfaces. Therefore regular testing can be minimized to checking the unsupervised circuits. The test procedures are the same as described in Sections 6.4.1, 6.4.2 and 6.4.3. 6.7.2 Failure Tracing and Repair Failures will be detected by automatic supervision or regular testing.
6 F 2 S 0 8 5 7 Table 6.7.
6 F 2 S 0 8 5 7 If no message is shown on the LCD, this means that the failure location is either in the DC power supply circuit or in the microprocessors mounted on the SPM module. Then check the "ALARM" LED. If it is off, the failure is in the DC power supply circuit. If it is lit, open the relay front panel and check the LEDs mounted on the SPM module. If the LED is off, the failure is in the DC power supply circuit. If the LED is lit, the failure is in the microprocessors.
6 F 2 S 0 8 5 7 The software name is indicated on the memory device on the module with letters such as GSPTM1-∗∗∗, etc. CAUTION CAUTION When handling a module, take anti-static measures such as wearing an earthed wrist band and placing modules on an earthed conductive mat. Otherwise, many of the electronic components could suffer damage. After replacing the SPM module, check all of the settings including the data related to the PLC, IEC103 and IEC61850, etc. are restored the original settings.
6 F 2 S 0 8 5 7 • Open the left-side front panel by unscrewing the two binding screws located on the right side of the panel. • Detach the module holding bar by unscrewing the binding screw located on the left side of the bar. • Unplug the ribbon cable running among the modules by nipping the catch (in case of black connector) and by pushing the catch outside (in case of gray connector) on the connector. • Pull out the module by pulling up or down the top and bottom levers.
6 F 2 S 0 8 5 7 7. Putting Relay into Service The following procedure must be adhered to when putting the relay into service after finishing commissioning or maintenance tests. • Check that all external connections are correct. • Check the setting of all measuring elements, timers, scheme switches, recordings and clock are correct. In particular, when settings are changed temporarily for testing, be sure to restore them.
6 F 2 S 0 8 5 7 Appendix A Block Diagram ⎯ 157 ⎯
6 F 2 S 0 8 5 7 Scheme Logic No.1 DIFT DIFT (#87) HOC 2f lock 1 5f lock 1 & Selection ≥1 DIF Q S F/F switches for R ≥1 each element & + (ON) & 1 − (OFF) & RESET TRIP-1 1OC (#150) t + (ON) 1OC 0 TP1 L/O TRIP OUTPUT CONTACT No.1 - (OFF) 0.00-10.00s 1OCI 1OCI(#151) TP2 2OC 2OC (#250) t 0 TP3 0.00-10.00s 2OCI 2OCI(#251) 3OC 3OC (#350) t TP5 3OCI 3OCI(#351) t 0 0.00-10.00s 1EFI t 0 2EFI 2EFI(#251N) 3REF 2EF 3REF 3EF 3EF t 0 3EFI V/F 0.00-10.
6 F 2 S 0 8 5 7 Appendix B Signal List ⎯ 159 ⎯
6 F 2 S 0 8 5 7 Signal list No.
6 F 2 S 0 8 5 7 Signal list No.
6 F 2 S 0 8 5 7 Signal list No.
6 F 2 S 0 8 5 7 Signal list No.
6 F 2 S 0 8 5 7 Signal list No. 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 Signal Name Contents WIND.4_TP-1 MEC.TRIP-1 ELEMENT_OR-1 TRIP-1 WIND.1_TP-2 WIND.2_TP-2 WIND.3_TP-2 WIND.4_TP-2 MEC.TRIP-2 ELEMENT_OR-2 TRIP-2 WIND.1_TP-3 WIND.2_TP-3 WIND.3_TP-3 WIND.4_TP-3 MEC.
6 F 2 S 0 8 5 7 Signal list No. 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 : : : 508 509 510 Signal Name Contents THR_TRIP DIFT_TRIP FRQ-UF_TRIP FRQ-OF_TRIP FRQ-UF_ALARM FRQ-OF_ALARM MEC.TRIP1 MEC.TRIP2 MEC.TRIP3 MEC.TRIP4 MEC.
6 F 2 S 0 8 5 7 Signal list No.
6 F 2 S 0 8 5 7 Signal list No.
6 F 2 S 0 8 5 7 Signal list No.
6 F 2 S 0 8 5 7 Signal list No.
6 F 2 S 0 8 5 7 Signal list No.
6 F 2 S 0 8 5 7 Signal list No. 1536 1537 1538 1539 1540 1541 1542 1543 1544 1545 1546 1547 1548 1549 1550 1551 1552 1553 1554 1555 1556 1557 1558 1559 1560 1561 1562 1563 1564 1565 1566 1567 1568 1569 1570 1571 1572 1573 1574 1575 1576 1577 1578 1579 1580 1581 1582 1583 1584 1585 1586 1587 1588 1589 1590 1591 1592 1593 1594 1595 1596 1597 1598 1599 1600 1601 1602 1603 1604 1605 Signal Name Contents EXT_MEC.TP1 EXT_MEC.TP2 EXT_MEC.TP3 EXT_MEC.TP4 IND.
6 F 2 S 0 8 5 7 Signal list No.
6 F 2 S 0 8 5 7 Signal list No.
6 F 2 S 0 8 5 7 Signal list No. 2621 2622 2623 2624 2625 2626 2627 2628 2629 2630 2631 2632 2633 2634 2635 2636 2637 2638 2639 2640 2641 2642 2643 2644 2645 2646 2647 2648 2649 2650 2651 2652 2653 2654 2655 2656 2657 2658 2659 2660 2661 2662 2663 2664 2665 2666 2667 2668 2669 2670 2671 2672 2673 2674 2675 2676 2677 2678 2679 2680 2681 2682 2683 2684 2685 2686 2687 2688 : 2810 Signal Name Contents F.RECORD1 F.RECORD2 F.RECORD3 F.
6 F 2 S 0 8 5 7 Signal list No.
6 F 2 S 0 8 5 7 Signal list No.
6 F 2 S 0 8 5 7 Signal list No.
6 F 2 S 0 8 5 7 Signal list No.
6 F 2 S 0 8 5 7 Appendix C Variable Timer List ⎯ 179 ⎯
6 F 2 S 0 8 5 7 Variable Timer List Timer Timer No.
6 F 2 S 0 8 5 7 Appendix D Binary Output Default Setting List ⎯ 181 ⎯
6 F 2 S 0 8 5 7 Binary Output Default Setting List Relay Module Model Name BO No. Signal Name Contents Setting Signal No.
6 F 2 S 0 8 5 7 Relay Module Model Name BO No. Signal Name Contents Setting Signal No.
6 F 2 S 0 8 5 7 Relay Module Model Name BO No. Signal Name Contents Setting Signal No.
6 F 2 S 0 8 5 7 Appendix E Details of Relay Menu and LCD & Button Operation ⎯ 185 ⎯
6 F 2 S 0 8 5 7 MENU 1=Record 3=Setting(view) 5=Test 2=Status 4=Setting(change) /1 Record 1=Fault record 2=Event record 3=Disturbance record /2 Fault record 1=Display 2=Clear /3 #1 #2 #3 Fault record 16/Oct/1998 23:18:03.913 12/Feb/1998 03:51:37.622 30/Jan/1997 15:06:11.835 2/8 /2 Fault record Clear all fault records? ENTER=Yes CANCEL=No /2 Event record 1=Display 2=Clear /3 Event record 2/48 16/Oct/1998 23:18:04.294 Trip Off 16/Oct/1998 23:18:03.913 Trip On 12/Feb/1998 03:51:37.622 Rly.
6 F 2 S 0 8 5 7 a-1 /1 Setting(view) 1=Version 2=Description 3=Comm. 4=Record 5=Status 6=Protection 7=Binary input 8=Binary output 9=LED /2 Relay version 3/ 8 Relay type: ******************** Serial No.
6 F 2 S 0 8 5 7 a-1 b-1 /2 Protection (Active group= *) 1=Group1 2=Group2 3=Group3 4=Group4 5=Group5 6=Group6 7=Group7 8=Group8 /3 Protection 1=Transformer parameter 2=Trip (Group 1) /4 Transformer parameter 1= VT & CT ratio (Group 1) /4 Trip 1=Phase matching 2=Scheme switch 3=Protection element (Group 1) /5 VT & CT ratio 1CT ( 2000 ) 3CT ( 1500 ) 2nCT ( 500 ) 2CT ( 1500 1nCT ( 1000 3nCT ( 2000 3/ 4 ) ) ) /5 Phase matching 1=Alpha 2=Beta Current No.
6 F 2 S 0 8 5 7 a-1 : Password trap Password Input password [_ ] /1 Setting(change) 1=Password 2=Description 3=Comm. 4=Record 5=Status 6=Protection 7=Binary input 8=Binary output 9=LED : Confirmation trap /2 Password Input new password Retype new password /2 ************* Change settings? ENTER=Yes CANCEL=No [ _ ] [ ] /2 Description 1=Plant name 2=Description /3 Plant name [ _ ] ABCDEFGHIJKLMNOPQRSTUVWXYZ()[]@_← → abcdefghijklmnopqrstuvwxyz{}*/+-<=>← → 0123456789!”#$%&’:;,.
6 F 2 S 0 8 5 7 a-1 b-2 /2 Protection 1=Change active group 2=Change setting 3=Copy group /3Change active group(Active group= *) 1=Group1 2=Group2 3=Group3 4=Group4 5=Group5 6=Group6 7=Group7 8=Group8 Current No.= * Select No.
6 F 2 S 0 8 5 7 a-1 b-2 /2 Binary input BISW 1 1=Norm 2=Inv BISW 2 1=Norm 2=Inv BISW 3 1=Norm 2=Inv 1/16 1 _ 1 1 /2 Binary output 1=IO#2 2=IO#3 /3 Binary output Select BO ( 1- 13) (IO#2) Select No.
6 F 2 S 0 8 5 7 LCD AND BUTTON OPERATION INSTRUCTION MANUAL MODE 1. PRESS ARROW KEY TO MOVE TO EACH DISPLAYED ITEMS NORMAL (DISPLAY OFF) VIEW PRESS ANY BUTTON EXCEPT FOR "VIEW" AND "RESET" 2.
6 F 2 S 0 8 5 7 Appendix F Case Outline • Flush Mount Type • Rack Mount Type ⎯ 193 ⎯
6 F 2 S 0 8 5 7 266 254 2 28 Front View 276.2 65 Side view 4-φ5.5 190.5 223 6.2 235.4 Rear view Panel cut-out TB3/TB4 TB2 A1 B1 A1 B1 TB2-TB4: M3.5 Ring terminal TB1 A10 B10 A18 B18 TB1: M3.5 Ring terminal 1 3 5 7 9 11 13 15 17 2 4 6 8 10 12 14 16 18 19 21 23 25 27 29 20 22 24 26 28 30 Terminal block Case Outline : Flush Mount Type ⎯ 194 ⎯ 34.
312 6 F 2 S 0 8 5 7 Attachment kit (top bar) Attachment kit (large bracket) Attachment kit (small bracket) Top View 4 HOLES - 6.8x10.3 2 6 5. 9 TRANSFORMER PROTECTION GRT100 3 7. 7 201B-11-10 1A 100/110/115/120V 465.1 483.
265.9 265.9 132 6 F 2 S 0 8 5 7 247.8 19.4 (b) Small Bracket 18 (a) Large Bracket 216 (c) Bar for Top and Bottom of Relay Parts (a) 1 Large bracket, 5 Round head screws with spring washers and washers (M4x10) (b) 1 Small bracket, 3 Countersunk head screws (M4x6) (c) 2 Bars, 4 Countersunk head screws (M3x8) Dimensions of Attachment Kit EP-101 ⎯ 196 ⎯ 18.
6 F 2 S 0 8 5 7 How to Mount Attachment Kit for Rack-Mounting Caution: Be careful that the relay modules or terminal blocks, etc., are not damage while mounting. Tighten screws to the specified torque according to the size of screw. Step 1. Remove case cover. GPS ALARM SYNC. ALARM MODE 2A CF Right bracket Left bracket Seal Step 2. Screw Remove the left and right brackets by unscrewing the three screws respectively, then remove two screws on left side of the relay.
6 F 2 S 0 8 5 7 ⎯ 198 ⎯
6 F 2 S 0 8 5 7 Appendix G External Connections ⎯ 199 ⎯
6 F 2 S 0 8 5 7 TB3-A2 BO1 TB1 -1 2 43 CT A1 BO2 B1 BO3 B2 5 6 A3 B3 BO4 CB VT A4 IO#2 CT B4 BO5 A5 7 B5 BO6 A6 8 CT B6 BO7 CB A7 CT 9 B7 BO9 B8 A8 10 11 12 13 14 15 16 A9 BO10 B9 A10 27 28 30 (∗1) BO8 (CASE EARTH) BO11 B10 A11 BO12 B11 (HIGH SPEED RELAY) A13 B13 (HIGH SPEED RELAY) (+) BO13 TB4 -A4 B4 MECHANICAL TRIP A5 B5 A6 INDICATION RESET B6 A7 B7 A8 B8 A9 B9 A10 BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 (-) B11 TB3-A14 BI14 B14 EVENT A15 (
6 F 2 S 0 8 5 7 TB2-A1 TB3-A2 BO1 CT A1 BO2 TB1 -1 2 43 BO1 B1 A2 B1 BO2 BO3 B2 B2 5 6 A3 A3 CB BO4 VT BO3 B3 B3 A4 CT IO#2 A4 BO4 B4 BO5 B4 A5 7 A5 B5 BO6 8 BO5 A6 B6 BO7 CB BO6 A7 CT BO10 BO11 BO13 BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 A6 B5 B6 A7 B7 A8 B8 A9 B9 A10 (-) B11 TB3-A14 B14 EVENT A15 (-) B15 BI14 BI15 BI16 FAIL BO10 B10 IO#3 A12 B12 COM-A B9 A10 B11 (HIGH SPEED RELAY) A13 B13 (HIGH SPEED RELAY) BO12 INDICATION RESET A9
6 F 2 S 0 8 5 7 TB1 -1 2 3 4 5 6 CT CB B2 A3 BO4 BO5 CT B4 A5 15 16 17 18 19 20 21 22 23 24 CB B3 A4 IO#2 CT CT B1 BO3 910 1112 13 14 CB A1 BO2 7 8 VT CT TB3-A2 BO1 BO6 B5 BO7 B6 A6 A7 BO8 B7 A8 BO9 B8 A9 CT BO10 27 (∗1) 28 30 B9 A10 BO11 B10 (CASE EARTH) A11 B11 (HIGH SPEED RELAY) A13 B13 (HIGH SPEED RELAY) BO12 (+) [Default Setting] BO13 TB4 -A4 BI1 BI2 B4 EXT.
6 F 2 S 0 8 5 7 CT CB BO1 A2 BO2 B2 B2 A3 A3 910 1112 BO4 BO3 A4 A4 IO#2 B3 B3 BO5 BO4 B4 B4 CT A5 CB CT B1 B1 BO3 13 14 CT BO1 A1 BO2 7 8 VT TB2-A1 TB3-A2 TB1 -1 2 3 4 5 6 15 16 17 18 1920 CB CT BO6 A5 BO5 B5 BO7 21 22 23 24 A6 B6 BO6 A7 B7 BO7 A8 BO10 27 A8 BO8 BO11 (+) [Default Setting] BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 A5 B5 A6 B6 A7 B7 A8 B8 A9 B9 A10 (-) B11 TB3-A14 B14 EVENT A15 (-) B15 FAIL COM-A B10 IO#3 A12 B12 RELAY FAILURE TB3-A18
6 F 2 S 0 8 5 7 TB1 -1 2 3 4 5 6 CT CB TB3-A2 BO1 7 8 VT A1 BO2 B1 BO3 B2 910 1112 A3 13 14 BO4 B3 BO5 B4 A4 CT CT CB CT 15 16 17 18 1920 CB CT A5 BO6 B5 BO7 B6 A6 21 22 23 24 IO#2 A7 BO8 B7 A8 BO9 B8 CT A9 27 BO10 (∗1) B9 28 30 A10 BO11 (CASE EARTH) B10 A11 (+) TB4 -B4 [Default Setting] A4 B5 A5 B6 A6 B7 A7 B8 A8 B9 A9 B10 A10 B11 A11 B12 A12 B13 A13 B14 A14 B15 A15 EXT.
6 F 2 S 0 8 5 7 TB1 -1 2 3 4 5 6 CT CB CT CT BO4 B3 BO5 B4 BO3 B3 A4 A4 BO4 B4 A5 BO6 A5 BO5 B5 B5 A6 21 22 23 24 BO7 IO#2 A6 B6 BO6 B6 A7 BO8 A7 B7 BO7 A8 BO9 A8 BO8 A9 27 BO10 B8 B9 28 30 A9 A10 BO11 (CASE EARTH) B7 B8 CT (∗1) B2 B2 A3 15 16 17 18 1920 CB A2 BO2 A3 910 1112 13 14 CB B1 B1 BO3 CT CT BO1 A1 BO2 7 8 VT TB2-A1 TB3-A2 BO1 BO9 B9 B10 A10 A11 B11 (HIGH SPEED BO12 (+) A4 B5 A5 B6 A6 B7 A7 B8 A8 B9 A9 B10 A10 B11 A11 B12
6 F 2 S 0 8 5 7 ⎯ 206 ⎯
6 F 2 S 0 8 5 7 Appendix H Relay Setting Sheet 1. Relay Identification 2. Contacts Setting 3.
6 F 2 S 0 8 5 7 Relay Setting Sheets 1. Relay Identification Date: Relay type Serial Number Frequency CT rating VT rating dc supply voltage Password Active setting group 2.
6 F 2 S 0 8 5 7 3.
6 F 2 S 0 8 5 7 Def ault Setting of Relay Series(5A rating / 1A rating) № Name 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 2EFI1 2EFI2 2EFI3 2EFI4 2EFI5 3REF1 3REF2 3REF3 3REF4 3REF5 3OC1 3OC2 3OC3 3OC4 3OC5 3OCI1 3OCI2 3OCI3 3OCI4 3OCI5 3EF1 3EF2 3EF3 3EF4 3EF5 3EFI1 3EFI2 3EFI3 3EFI4 3EFI5 FR
6 F 2 S 0 8 5 7 № Range Name 5A rating Units Contents 1A rating Default Setting of Relay Series(5A rating / 1A rating) World wide ENA 2-Winding 3-Winding 3-Winding 101D 102D 201D 202D 203D 204D 176 3ik 0.05 - 0.50 pu 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 3kct1 3kct2 3kct3 3p2 3kp T1REF T2REF T3REF 1OC 2OC 3OC T1OC T2OC T3OC 1OCI 2OCI 3OCI 1.00 - 50.00 1.00 - 50.00 1.00 - 50.00 50 - 100 0.50 - 2.00 0.00 - 10.00 0.00 - 10.00 0.00 - 10.00 0.10 - 20.00 0.10 - 20.00 0.
6 F 2 S 0 8 5 7 Def ault Setting of Relay Series(5A rating / 1A rating) № Range Name 5A rating 214 215 216 217 V/F V A L H 218 LT Units Contents V - Voltage Alarm lev el Low lev el High lev el Inv erce time delay f or high lev el Inv erce time delay f ir low lev el Radiant heat time Delay time f or high lev el Delay time f or alarm lev el Frequency -1 in 50Hz rating Frequency -1 in 60Hz rating Frequency -2 in 50Hz rating Frequency -2 in 60Hz rating Voltage TRIP delay timer f or low lev el TRIP d
6 F 2 S 0 8 5 7 Range № Name 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 IP2-1 IP2-2 IP2-3 IP2-4 SM2-1 SM2-2 SM2-3 SM2-4 GW2-1 GW2-2 GW2-3 GW2-4 SI1-1 SI1-2 SI1-3 SI1-4 SI2-1 SI2-2 SI2-3 SI2-4 SI3-1 SI3-2 SI3-3 SI3-4 SI4-1 SI4-2 SI4-3 SI4-4 SMODE GOINT PG1-1 PG1-2 PG1-3 PG1-4 PG2-1 PG2-2 PG2-3 PG2-4 0 - 254 0 - 254 0 - 254 0 - 254 0 - 255 0 - 255 0 - 255 0 - 255 0 - 254 0 - 254 0 - 254 0 - 254 0
6 F 2 S 0 8 5 7 Event record default setting No. Name Range Unit 1 EV1 0 - 3071 - 2 EV2 0 - 3071 3 EV3 0 - 3071 4 EV4 5 Contents Default setting Model Sig. NO. Signal name type Event record signal 1536 Mec.Trip1 On/Off - ditto 1537 Mec.Trip2 On/Off - ditto 1538 Mec.Trip3 On/Off 0 - 3071 - ditto 1539 Mec.Trip4 On/Off EV5 0 - 3071 - ditto 314 Trip On/Off 6 EV6 0 - 3071 - ditto 1540 Ind.
6 F 2 S 0 8 5 7 Event record default setting No. Name Range Unit 65 EV65 0 - 3071 - Contents Default setting Sig. NO.
6 F 2 S 0 8 5 7 Disturbance record default setting Default setting Unit Contents Model No.
6 F 2 S 0 8 5 7 PLC default setting Output № 1536 1537 1538 1539 1540 1541 1542 1543 1544 1545 1546 1547 1548 1549 1550 1551 1552 1553 1554 1555 1556 1557 1558 1559 1560 1561 1562 1563 1564 1565 1566 1567 1568 1569 1570 1571 1572 1573 1574 1575 1576 1577 1578 1579 1580 1581 1582 1583 1584 1585 1586 1587 1588 1589 1590 1591 1592 1593 1594 1595 1596 1597 1598 1599 Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 Flip Flop Back Release Norm Up Signal Del
6 F 2 S 0 8 5 7 Output № 1600 1601 1602 1603 1604 1605 1606 1607 1608 1609 1610 1611 1612 1613 1614 1615 1616 1617 1618 1619 1620 1621 1622 1623 1624 1625 1626 1627 1628 1629 1630 1631 1632 1633 1634 1635 1636 1637 1638 1639 1640 1641 1642 1643 1644 1645 1646 1647 1648 1649 1650 1651 1652 1653 1654 1655 1656 1657 1658 1659 1660 1661 1662 1663 Signal TP1_DELAY TP2_DELAY TP3_DELAY TP4_DELAY TP5_DELAY Timing Cycle 30 X X X X X 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 [3
6 F 2 S 0 8 5 7 Output № 1664 1665 1666 1667 1668 1669 1670 1671 1672 1673 1674 1675 1676 1677 1678 1679 1680 1681 1682 1683 1684 1685 1686 1687 1688 1689 1690 1691 1692 1693 1694 1695 1696 1697 1698 1699 1700 1701 1702 1703 1704 1705 1706 1707 1708 1709 1710 1711 1712 1713 1714 1715 1716 1717 1718 1719 1720 1721 1722 1723 1724 1725 1726 1727 Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 Flip Flop Back Release Norm Up Signal ⎯ 219 ⎯ Delay Time /
6 F 2 S 0 8 5 7 Output № Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 1728 1729 1730 1731 1732 1733 1734 1735 1736 1737 1738 1739 1740 1741 1742 1743 1744 1745 1746 1747 1748 1749 1750 1751 1752 1753 1754 1755 1756 1757 1758 1759 1760 1761 1762 1763 1764 1765 1766 1767 1768 1769 1770 1771 1772 1773 1774 1775 1776 1777 1778 1779 1780 1781 1782 1783 1784 1785 1786 1787 1788 1789 1790 1791 ⎯ 220 ⎯ Flip Flop Back Release Norm Up Signal Delay Time /
6 F 2 S 0 8 5 7 Output № 1792 1793 1794 1795 1796 1797 1798 1799 1800 1801 1802 1803 1804 1805 1806 1807 1808 1809 1810 1811 1812 1813 1814 1815 1816 1817 1818 1819 1820 1821 1822 1823 1824 1825 1826 1827 1828 1829 1830 1831 1832 1833 1834 1835 1836 1837 1838 1839 1840 1841 1842 1843 1844 1845 1846 1847 1848 1849 1850 1851 1852 1853 1854 1855 Signal IO#1-TP1 IO#1-TP2 IO#1-TP3 IO#1-TP4 IO#1-TP5 Timing Cycle 30 X X X X X 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 [284]TR
6 F 2 S 0 8 5 7 Output № Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 1856 1857 1858 1859 1860 1861 1862 1863 1864 1865 1866 1867 1868 1869 1870 1871 1872 1873 1874 1875 1876 1877 1878 1879 1880 1881 1882 1883 1884 1885 1886 1887 1888 1889 1890 1891 1892 1893 1894 1895 1896 1897 1898 1899 1900 1901 1902 1903 1904 1905 1906 1907 1908 1909 1910 1911 1912 1913 1914 1915 1916 1917 1918 1919 ⎯ 222 ⎯ Flip Flop Back Release Norm Up Signal Delay Time /
6 F 2 S 0 8 5 7 Output № Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 ⎯ 223 ⎯ Flip Flop Back Release Norm Up Signal Delay Time /
6 F 2 S 0 8 5 7 Output № Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 2026 2027 2028 2029 2030 2031 2032 2033 2034 2035 2036 2037 2038 2039 2040 2041 2042 2043 2044 2045 2046 2047 ⎯ 224 ⎯ Flip Flop Back Release Norm Up Signal Delay Time /
6 F 2 S 0 8 5 7 Output № Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 2048 2049 2050 2051 2052 2053 2054 2055 2056 2057 2058 2059 2060 2061 2062 2063 2064 2065 2066 2067 2068 2069 2070 2071 2072 2073 2074 2075 2076 2077 2078 2079 2080 2081 2082 2083 2084 2085 2086 2087 2088 2089 2090 2091 2092 2093 2094 2095 2096 2097 2098 2099 2100 2101 2102 2103 2104 2105 2106 2107 2108 2109 2110 2111 ⎯ 225 ⎯ Flip Flop Release Back Norm Signal Up Delay Time /
6 F 2 S 0 8 5 7 Output № Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 2112 2113 2114 2115 2116 2117 2118 2119 2120 2121 2122 2123 2124 2125 2126 2127 2128 2129 2130 2131 2132 2133 2134 2135 2136 2137 2138 2139 2140 2141 2142 2143 2144 2145 2146 2147 2148 2149 2150 2151 2152 2153 2154 2155 2156 2157 2158 2159 2160 2161 2162 2163 2164 2165 2166 2167 2168 2169 2170 2171 2172 2173 2174 2175 ⎯ 226 ⎯ Flip Flop Back Release Norm Up Signal Delay Time /
6 F 2 S 0 8 5 7 Output № Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 2176 2177 2178 2179 2180 2181 2182 2183 2184 2185 2186 2187 2188 2189 2190 2191 2192 2193 2194 2195 2196 2197 2198 2199 2200 2201 2202 2203 2204 2205 2206 2207 2208 2209 2210 2211 2212 2213 2214 2215 2216 2217 2218 2219 2220 2221 2222 2223 2224 2225 2226 2227 2228 2229 2230 2231 2232 2233 2234 2235 2236 2237 2238 2239 ⎯ 227 ⎯ Flip Flop Back Release Norm Up Signal Delay Time /
6 F 2 S 0 8 5 7 Output № Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 2240 2241 2242 2243 2244 2245 2246 2247 2248 2249 2250 2251 2252 2253 2254 2255 2256 2257 2258 2259 2260 2261 2262 2263 2264 2265 2266 2267 2268 2269 2270 2271 2272 2273 2274 2275 2276 2277 2278 2279 2280 2281 2282 2283 2284 2285 2286 2287 2288 2289 2290 2291 2292 2293 2294 2295 2296 2297 2298 2299 2300 2301 2302 2303 ⎯ 228 ⎯ Flip Flop Back Release Norm Up Signal Delay Time /
6 F 2 S 0 8 5 7 Output № Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 2304 2305 2306 2307 2308 2309 2310 2311 2312 2313 2314 2315 2316 2317 2318 2319 2320 2321 2322 2323 2324 2325 2326 2327 2328 2329 2330 2331 2332 2333 2334 2335 2336 2337 2338 2339 2340 2341 2342 2343 2344 2345 2346 2347 2348 2349 2350 2351 2352 2353 2354 2355 2356 2357 2358 2359 2360 2361 2362 2363 2364 2365 2366 2367 ⎯ 229 ⎯ Flip Flop Back Release Norm Up Signal Delay Time /
6 F 2 S 0 8 5 7 Output № Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 2368 2369 2370 2371 2372 2373 2374 2375 2376 2377 2378 2379 2380 2381 2382 2383 2384 2385 2386 2387 2388 2389 2390 2391 2392 2393 2394 2395 2396 2397 2398 2399 2400 2401 2402 2403 2404 2405 2406 2407 2408 2409 2410 2411 2412 2413 2414 2415 2416 2417 2418 2419 2420 2421 2422 2423 2424 2425 2426 2427 2428 2429 2430 2431 ⎯ 230 ⎯ Flip Flop Release Back Norm Signal Up Delay Time /
6 F 2 S 0 8 5 7 Output № Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 2432 2433 2434 2435 2436 2437 2438 2439 2440 2441 2442 2443 2444 2445 2446 2447 2448 2449 2450 2451 2452 2453 2454 2455 2456 2457 2458 2459 2460 2461 2462 2463 2464 2465 2466 2467 2468 2469 2470 2471 2472 2473 2474 2475 2476 2477 2478 2479 2480 2481 2482 2483 2484 2485 2486 2487 2488 2489 2490 2491 2492 2493 2494 2495 ⎯ 231 ⎯ Flip Flop Release Back Norm Signal Up Delay Time /
6 F 2 S 0 8 5 7 Output № Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 2486 2487 2488 2489 2490 2491 2492 2493 2494 2495 2496 2497 2498 2499 2500 2501 2502 2503 2504 2505 2506 2507 2508 2509 2510 2511 2512 2513 2514 2515 2516 2517 2518 2519 2520 2521 2522 2523 2524 2525 2526 2527 2528 2529 2530 2531 2532 2533 2534 2535 2536 2537 2538 2539 2540 2541 2542 2543 2544 2545 2546 2547 2548 2549 ⎯ 232 ⎯ Flip Flop Release Back Norm Signal Up Delay Time /
6 F 2 S 0 8 5 7 Output № Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 2550 2551 2552 2553 2554 2555 2556 2557 2558 2559 2560 2561 2562 2563 2564 2565 2566 2567 2568 2569 2570 2571 2572 2573 2574 2575 2576 2577 2578 2579 2580 2581 2582 2583 2584 2585 2586 2587 2588 2589 2590 2591 2592 2593 2594 2595 2596 2597 2598 2599 2600 2601 2602 2603 2604 2605 2606 2607 2608 2609 2610 2611 2612 2613 ⎯ 233 ⎯ Flip Flop Release Back Norm Signal Up Delay Time /
6 F 2 S 0 8 5 7 Output № 2614 2615 2616 2617 2618 2619 2620 2621 2622 2623 2624 2625 2626 2627 2628 2629 2630 2631 2632 2633 2634 2635 2636 2637 2638 2639 2640 2641 2642 2643 2644 2645 2646 2647 2648 2649 2650 2651 2652 2653 2654 2655 2656 2657 2658 2659 2660 2661 2662 2663 2664 2665 2666 2667 2668 2669 2670 2671 2672 2673 2674 2675 2676 2677 Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 F.RECORD1 F.RECORD2 F.RECORD3 F.RECORD4 D.RECORD1 D.
6 F 2 S 0 8 5 7 Output № Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 2678 2679 2680 2681 2682 2683 2684 2685 2686 PROT_COM_RECV 2687 2688 TPLED_RST_RCV 2689 2690 2691 2692 2693 2694 2695 2696 2697 2698 2699 2700 2701 2702 2703 2704 2705 2706 2707 2708 2709 2710 2711 2712 2713 2714 2715 2716 2717 2718 2719 2720 2721 2722 2723 2724 2725 2726 2727 2728 2729 2730 2731 2732 2733 2734 2735 2736 2737 2738 2739 2740 2741 ⎯ 235 ⎯ Flip Flop Release Back
6 F 2 S 0 8 5 7 Output № Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 2742 2743 2744 2745 2746 2747 2748 2749 2750 2751 2752 2753 2754 2755 2756 2757 2758 2759 2760 2761 2762 2763 2764 2765 2766 2767 2768 2769 2770 2771 2772 2773 2774 2775 2776 2777 2778 2779 2780 2781 2782 2783 2784 2785 2786 2787 2788 2789 2790 2791 2792 2793 2794 2795 2796 2797 2798 2799 2800 2801 2802 2803 2804 2805 2806 2807 2808 2809 2810 2811 2812 2813 2814 2815 ⎯ 236 ⎯ F
6 F 2 S 0 8 5 7 Output № 2816 2817 2818 2819 2820 2821 2822 2823 2824 2825 2826 2827 2828 2829 2830 2831 2832 2833 2834 2835 2836 2837 2838 2839 2840 2841 2842 2843 2844 2845 2846 2847 2848 2849 2850 2851 2852 2853 2854 2855 2856 2857 2858 2859 2860 2861 2862 2863 2864 2865 2866 2867 2868 2869 2870 2871 2872 2873 2874 2875 2876 2877 2878 2879 2880 Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 TEMP001 TEMP002 TEMP003 TEMP004 TEMP005 TEMP006 TEMP007
6 F 2 S 0 8 5 7 Output № 2881 2882 2883 2884 2885 2886 2887 2888 2889 2890 2891 2892 2893 2894 2895 2896 2897 2898 2899 2900 2901 2902 2903 2904 2905 2906 2907 2908 2909 2910 2911 2912 2913 2914 2915 2916 2917 2918 2919 2920 2921 2922 2923 2924 2925 2926 2927 2928 2929 2930 2931 2932 2933 2934 2935 2936 2937 2938 2939 2940 2941 2942 2943 2944 Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 TEMP066 TEMP067 TEMP068 TEMP069 TEMP070 TEMP071 TEMP072 TEMP0
6 F 2 S 0 8 5 7 Output № 2945 2946 2947 2948 2949 2950 2951 2952 2953 2954 2955 2956 2957 2958 2959 2960 2961 2962 2963 2964 2965 2966 2967 2968 2969 2970 2971 2972 2973 2974 2975 2976 2977 2978 2979 2980 2981 2982 2983 2984 2985 2986 2987 2988 2989 2990 2991 2992 2993 2994 2995 2996 2997 2998 2999 3000 3001 3002 3003 3004 3005 3006 3007 3008 Signal Timing Cycle 30 90 User Logic expression Model 100s Model 200s Turn Filename: PGRT100DA000 TEMP130 TEMP131 TEMP132 TEMP133 TEMP134 TEMP135 TEMP136 TEMP1
6 F 2 S 0 8 5 7 Output № 3009 3010 3011 3012 3013 3014 3015 3016 3017 3018 3019 3020 3021 3022 3023 3024 3025 3026 3027 3028 3029 3030 3031 3032 3033 3034 3035 3036 3037 3038 3039 3040 3041 3042 3043 3044 3045 3046 3047 3048 3049 3050 3051 3052 3053 3054 3055 3056 3057 3058 3059 3060 3061 3062 3063 3064 3065 3066 3067 3068 3069 3070 3071 Signal Timing Cycle 30 90 User Turn Logic expression Model 100s Model 200s Filename: PGRT100DA000 TEMP194 TEMP195 TEMP196 TEMP197 TEMP198 TEMP199 TEMP200 TEMP201 TE
6 F 2 S 0 8 5 7 Appendix I Commissioning Test Sheet (sample) 1. Relay identification 2. Preliminary check 3. Hardware test 3.1 User interface check 3.2 Binary input/Binary output circuit check 3.3 AC input circuit check 4. Function test 4.1 Percentage current differential element DIF test 4.2 2F-lock element check 4.3 5F-lock element check 4.4 High-set overcurrent element HOC test 4.5 Restricted earth fault element REF test 4.6 Overcurrent element test 4.7 Thermal overload element THR test 4.
6 F 2 S 0 8 5 7 1. Relay identification Type Serial number Model System frequency Station Date Circuit Engineer Protection scheme Witness Active settings group number 2. Preliminary check Ratings CT shorting contacts DC power supply Power up Wiring Relay inoperative alarm contact Calendar and clock 3. Hardware check 3.1 User interface check 3.2 Binary input/Binary output circuit check Binary input circuit Binary output circuit 3.
6 F 2 S 0 8 5 7 4. Function test 4.1 Percentage current differential element DIF test (1) Minimum operating value test Tap setting Measured current (2) Percentage restraining characteristic test I1 Tap setting Measured current (I2) × Ik × Ik (3) Operating time test Tap setting Test current Measured time 4.2 2F-lock element check 4.3 5F-lock element check 4.
6 F 2 S 0 8 5 7 4.6 Overcurrent element test (1) OC element Element Tap setting Measured current Tap setting Measured current Element Test current Measured operating time OCI 2 × Is OC (2) EF element Element EF (3) OCI element 20 × Is Is: Setting value (4) EFI element Element Test current EFI 2 × Is Measured operating time 20 × Is 4.7 Thermal overload element THR test Element Test current Measured operating time THR 4.
6 F 2 S 0 8 5 7 (2) Undervoltage block Setting Measured voltage 4.9 Overexcitation element V/F test (1) Operating value test Element Setting Measured voltage V/F (2) Operating time test Test voltage 5. Measured operating time Protection scheme test Scheme 6. Metering and recording check 7.
6 F 2 S 0 8 5 7 ⎯ 246 ⎯
6 F 2 S 0 8 5 7 Appendix J Return Repair Form ⎯ 247 ⎯
6 F 2 S 0 8 5 7 RETURN / REPAIR FORM Please fill in this form and return it to Toshiba Corporation with the GRT100 to be repaired. TOSHIBA CORPORATION Fuchu Complex 1, Toshiba-cho, Fuchu-shi, Tokyo, Japan For: Power Systems Protection & Control Department Quality Assurance Section Type: GRT100 (Example: Type: Model: GRT100 Model: 101D- 10-A0 ) Product No.: Serial No. : Date: 1. Why the relay is being returned ? mal-operation does not operate increased error investigation others 2.
6 F 2 S 0 8 5 7 Fault Record Date/Month/Year Time / / (Example: 04/ Nov./ 1997 / : : . 15:09:58.
6 F 2 S 0 8 5 7 3. What was the message on the LCD display at the time of the incident. 4. Please write the detail of the incident. 5. Date of the incident occurred. Day/ Month/ Year: / / / (Example: 10/ July/ 1998) 6. Please write any comments on the GRT100, including the document.
6 F 2 S 0 8 5 7 Customer Name: Company Name: Address: Telephone No.: Facsimile No.
6 F 2 S 0 8 5 7 ⎯ 252 ⎯
6 F 2 S 0 8 5 7 Appendix K Technical Data ⎯ 253 ⎯
6 F 2 S 0 8 5 7 TECHNICAL DATA Ratings AC current 1A or 5A AC voltage 100V, 110V, 115V, 120V Frequency 50Hz or 60Hz DC power supply 110Vdc/125Vdc (Operative range: 88 to 150Vdc) 220Vdc/250Vdc (Operative range: 176 to 300Vdc) 48Vdc/54Vdc/60Vdc (Operative range: 38.4 to 72Vdc) 24Vdc/30Vdc (Operative range: 19.
6 F 2 S 0 8 5 7 Restricted earth fault element Minimum operating current 0.05 to 0.50pu in 0.01pu steps Slope 1 (p1) 10 % Slope 2 (p2) 50 to 100% in 1% steps kp 0.50 to 2.00pu in 0.01pu steps CT ratio correction (kct) 1.00 to 50.00 in 0.01 steps Operating time typical 35ms Time-overcurrent protection High-set overcurrent element Pick up level (OC, EF) 0.10 to 20.00pu in 0.10pu steps Delay time (TOC, TEF) 0.00 to 10.00s in 0.
6 F 2 S 0 8 5 7 Accuracy Current differential element: pick-up reset Time-overcurrent protection: pick-up ±5% ±5% ±5% Inverse time overcurrent characteristics: Standard inverse, Very and long-time inverse IEC60255-3 class 5 Extremely inverse IEC60255-3 class 7.5 Thermal overload protection: pick-up ±10% Frequency protection: pick-up ±0.03Hz Overexitation protection ±2% of pick-up voltage (frequency range ±2%) Disturbance record initiation Overcurrent element 0.10 to 20.00pu in 0.
6 F 2 S 0 8 5 7 Contact ratings Trip contacts Make and carry 5A continuously, 30A, 290Vdc for 0.5s (L/R=10ms) Break 0.15A, 290Vdc (L/R=40ms) Auxiliary contacts Make and carry 4A continuously, 10A, 220Vdc for 0.5s (L/R≧5ms) Break 0.1A, 220Vdc (L/R=40ms) Durability Make and carry 10,000 operations minimum Break 100,000 operations minimum Mechanical design Weight 12kg Case color 2.5Y7.
6 F 2 S 0 8 5 7 CT requirement The GRT100 does not require the use of dedicated CTs nor the use of CTs with an identical ratio. The GRT100 can share the CTs with other protections and the different ratios are adjusted by setting. The general CT requirements are set for the through-fault stability which comes up when any CTs saturate under very large through-fault currents.
6 F 2 S 0 8 5 7 ENVIRONMENTAL PERFORMANCE CLAIMS Test Standards Details Atmospheric Environment Temperature IEC60068-2-1/2 Operating range: -10°C to +55°C. Storage / Transit: -25°C to +70°C. Humidity IEC60068-2-78 56 days at 40°C and 93% relative humidity.
6 F 2 S 0 8 5 7 Test Standards Details European Commission Directives 89/336/EEC Compliance with the European Commission Electromagnetic Compatibility Directive is demonstrated according to EN 61000-6-2 and EN 61000-6-4. 73/23/EEC Compliance with the European Commission Low Voltage Directive is demonstrated according to EN 50178 and EN 60255-5.
6 F 2 S 0 8 5 7 Appendix L Setting of REF Element ⎯ 261 ⎯
6 F 2 S 0 8 5 7 Type of transformer 1ct-1 1REF Scheme switch setting HV 1nCT [1REF] = 1I0 [2REF] = 1I0 2ct-1 LV 2nCT In2 In1 2REF [1REF] = 2I0 1ct-1 2REF1 = OFF 2REF2 = OFF 2REF3 = OFF 2REF4 = OFF 2REF5 = OFF HV 1REF 1nCT LV In1 3REF1 = OFF 3REF2 = OFF 3REF3 = OFF 3REF4 = OFF 3REF5 = OFF 1ct-2 HV 1ct-1 1REF In1 1nCT ⎯ 262 ⎯ LV 1REF = 1I0
6 F 2 S 0 8 5 7 Type of transformer Scheme switch setting HV LV 2REF = 1I0 I02 2ct-1 2nCT I1a I1b I1c 1REF I2N HV 1ct-1 1nCT 3REF1 to 5 = OFF 2REF I2a I2b I2c 2nCT LV I3a, I3b, I3c 3nCT I3N HV 3REF MV 1REF = 1I0 2REF = 1I0 2ct-1 I2a I2b I2c I1a I1b I1c 1REF 2REF I2N 3ct-1 1REF = 1I0 2REF = 1I0 3REF = 1I0 2ct-1 MV I1N 1ct-1 1REF1 to 5 = OFF I2a I2b I2c 1nCT LV I1N ⎯ 263 ⎯ 2nCT I2N 2REF 3REF1 to 5 = OFF
6 F 2 S 0 8 5 7 Type of transformer Scheme switch setting 1ct-1 HV I1a I1b I1c 1REF MV 1REF = 1I0 3REF = 1I0 1nCT 2REF1 to 5 = OFF LV I1N 3nCT I3N 3REF 3ct-1 I3a, I3b, I3c HV MV 2nCT LV 2REF = 1I0 3REF = 1I0 2ct-1 I2a I2b I2c I2N 1REF1 to 5 = OFF 2REF 3nCT I3N 3REF 3ct-1 I3a, I3b, I3c 1ct-1 HV HV 3REF1 to 5 = OFF 1nCT LV I1N 2REF = 1I0 2ct-1 MV LV 1REF = 1I0 2REF1 to 5 = OFF I1a I1b I1c 1REF MV I2a I2b I2c 2nCT I2N ⎯ 264 ⎯ 2REF 1REF1 to 5 = OFF 3REF1 to 5 = OFF
6 F 2 S 0 8 5 7 Type of transformer Scheme switch setting HV MV 3REF = 1I0 1REF1 to 5 = OFF 3REF1 to 5 = OFF LV 3nCT I3N 3REF 3ct-1 I3a, I3b, I3c HV LV I3a, I3b, I3c I3N LV 1REF = 2I0 3REF = 1I0 I1a I1b I1c 3REF I1N 2REF1 to 5 = OFF 1REF I2a, I2b, I2c 1REF = 2I0 1ct-1 LV HV 2REF1 to 5 = OFF MV I1a I1b I1c 1nCT I1N 3REF1 to 5 = OFF 1REF 1ct-2 I2a, I2b, I2c 1REF = 1I0 2REF = 2I0 2ct-1 MV HV I1a, I1b, I1c 1ct-1 1nCT I1N LV 2nCT 1REF I2N 3REF1 to 5 = OFF I2a I2b I2c 2REF 2c
6 F 2 S 0 8 5 7 Type of transformer Scheme switch setting 2REF = 2I0 2ct-1 MV HV 1REF1 to 5 = OFF I2a I2b I2c LV 2nCT I2N 3REF1 to 5 = OFF 2REF 2ct-2 I3a, I3b, I3c I1a, I1b, I1c I2a, I2b, I2c 1REF = 3I0 1ct-2 1ct-1 HV 2REF1 to 5 = OFF 3REF1 to 5 = OFF MV 1nCT I1N 1REF 1ct-3 I3a, I3b, I3c 1REF = 3I0 1ct-1 HV 2REF1 to 5 = OFF 3REF1 to 5 = OFF I1a I1b I1c MV 1nCT 1ct-2 I1N 1ct-3 ⎯ 266 ⎯ 1REF I3a I3b I3c I2a I2b I2c
6 F 2 S 0 8 5 7 Appendix M Symbols Used in Scheme Logic ⎯ 267 ⎯
6 F 2 S 0 8 5 7 Symbols used in the scheme logic and their meanings are as follows: Signal names Marked with : Measuring element output signal Marked with : Binary signal input from or output to the external equipment Marked with [ ] : Scheme switch Marked with " " : Scheme switch position Unmarked : Internal scheme logic signal AND gates A B & Output A 1 & Output A 1 B C 1 0 Other cases Output 1 0 & Output A 1 B C 0 0 Other cases Output 1 0 ≥1 Output A 0 B C 0 0 Other cases Outp
6 F 2 S 0 8 5 7 Signal inversion A 1 A 0 1 Output Output 1 0 Timer t Delaye pick-up timer with fixed setting 0 XXX: Set time XXX 0 Delayed drop-off timer with fixed setting t XXX: Set time XXX t Delaye pick-up timer with variable setting 0 XXX - YYY: Setting range XXX - YYY 0 Delayed drop-off timer with variable setting t XXX - YYY: Setting range XXX - YYY One-shot timer A A Output Output XXX - YYY XXX - YYY: Setting range Flip-flop S 0 1 0 1 S F/F Output R R 0 0 1 1 Output
6 F 2 S 0 8 5 7 ⎯ 270 ⎯
6 F 2 S 0 8 5 7 Appendix N Implementation of Thermal Model to IEC60255-8 ⎯ 271 ⎯
6 F 2 S 0 8 5 7 Implementation of Thermal Model to IEC60255-8 Heating by overload current and cooling by dissipation of an electrical system follow exponential time constants. The thermal characteristics of the electrical system can be shown by equation (1).
6 F 2 S 0 8 5 7 where: IP = prior load current. In fact, the cold curve is simply a special case of the hot curve where prior load current IP = 0, catering for the situation where a cold system is switched on to an immediate overload. Figure N-2 shows a typical thermal profile for a system which initially carries normal load current, and is then subjected to an overload condition until a trip results, before finally cooling to ambient temperature.
6 F 2 S 0 8 5 7 ⎯ 274 ⎯
6 F 2 S 0 8 5 7 Appendix O IEC60870-5-103: Interoperability and Troubleshooting ⎯ 275 ⎯
6 F 2 S 0 8 5 7 IEC60870-5-103 Configurator IEC103 configurator software is included in a same CD as RSM100, and can be installed easily as follows: Installation of IEC103 Configurator Insert the CD-ROM (RSM100) into a CDROM drive to install this software on a PC. Double click the “Setup.exe” of the folder “\IEC103Conf” under the root directory, and operate it according to the message. When installation has been completed, the IEC103 Configurator will be registered in the start menu.
6 F 2 S 0 8 5 7 • FUN of System function • Test mode, etc. CAUTION: To be effective the setting data written via the RS232C, turn off the DC supply of the relay and turn on again. 3. 1 IEC60870-5-103 Interface 3.1.1 Spontaneous events The events created by the relay will be sent using Function type (FUN) / Information numbers (INF) to the IEC60870-5-103 master station. 3.1.
6 F 2 S 0 8 5 7 List of Information IEC103 Configurator Default setting INF Description Contents GI Type ID COT FUN DPI Signal No. OFF ON Standard Information numbers in monitor direction System Function 0 End of General Interrogation Transmission completion of GI items. -- 8 10 255 -- -- -- 0 Time Synchronization Time Synchronization ACK.
6 F 2 S 0 8 5 7 IEC103 Configurator Default setting INF Description Contents GI Type ID COT FUN DPI Signal NO.
6 F 2 S 0 8 5 7 IEC103 configurator Default setting INF Description Contents GI Type COT ID FUN Max. No. Measurands 144 Measurand I No 145 Measurand I,V Ib1, Vab measurand 146 Measurand I,V,P,Q No 0 147 Measurand IN,VEN No 0 148 Measurand IL1,2,3, VL1,2,3, P,Q,f -- Ia1, Ib1, Ic1, f measurand -- 3.
6 F 2 S 0 8 5 7 IEC103 Configurator Default setting INF Description Contents COM Type ID COT FUN Selection of standard information numbers in control direction System functions 0 Initiation of general interrogation -- 7 9 255 0 Time synchronization -- 6 8 255 General commands 16 Auto-recloser on/off Not supported 17 Teleprotection on/off Not supported 18 Protection on/off (*1) 19 LED reset 23 ON/OFF 20 20 176 Reset indication of latched LEDs.
6 F 2 S 0 8 5 7 Description Contents GRT100 supported Basic application functions Test mode Yes Blocking of monitor direction Yes Disturbance data No Generic services No Private data Yes Miscellaneous Max.
6 F 2 S 0 8 5 7 [Legend] GI: General Interrogation (refer to IEC60870-5-103 section 7.4.3) Type ID: Type Identification (refer to IEC60870-5-103 section 7.2.
6 F 2 S 0 8 5 7 IEC103 setting data is recommended to be saved as follows: (1) Naming for IEC103setting data The file extension of IEC103 setting data is “.csv”. The version name is recommended to be provided with a revision number in order to be changed in future as follows: First draft: ∗∗∗∗∗∗_01.csv Second draft: ∗∗∗∗∗∗_02.csv Third draft: ∗∗∗∗∗∗_03.csv Revision number The name “∗∗∗∗∗∗” is recommended to be able to discriminate the relay type such as GRZ100 or GRL100, etc.
6 F 2 S 0 8 5 7 Troubleshooting No. Phenomena Supposed causes Check / Confirmation Object 1 Communication trouble (IEC103 communication is not available.) Address setting is incorrect. Procedure BCU Match address setting between BCU and relay. RY Avoid duplication of address with other relay. Transmission baud rate setting is incorrect. BCU Match transmission baud rate setting between BCU and relay. Start bit, stop bit and parity settings of data that BCU transmits to relay is incorrect.
6 F 2 S 0 8 5 7 2 3 HMI does not display IEC103 event on the SAS side. Time can be synchronised with IEC103 communication. The relevant event sending condition is not valid. RY Change the event sending condition (signal number) of IEC103 configurator if there is a setting error. When the setting is correct, check the signal condition by programmable LED, etc. The relevant event Information Number (INF) and/or Function Type (FUN) may be different between the relay and SAS.
6 F 2 S 0 8 5 7 Appendix P IEC61850: MICS & PICS ⎯ 287 ⎯
6 F 2 S 0 8 5 7 MICS: IEC61850 Model Implementation Conformance Statement The GRT100 relay supports IEC 61850 logical nodes and common data classes as indicated in the following tables.
6 F 2 S 0 8 5 7 Common data classes in IEC61850-7-3 Common data classes Status information SPS DPS INS ACT ACD SEC BCR Measured information MV CMV SAV WYE DEL SEQ HMV HWYE HDEL Controllable status information SPC DPC INC BSC ISC Controllable analogue information APC Status settings SPG ING Analogue settings ASG CURVE Description information DPL LPL CSD GRT100 Yes --Yes Yes Yes ----Yes Yes --Yes --Yes ------Yes --Yes --------Yes Yes --Yes Yes --- ⎯ 289 ⎯
6 F 2 S 0 8 5 7 LPHD class Attribute Name Attr.
6 F 2 S 0 8 5 7 LLNO class Attribute Name Attr.
6 F 2 S 0 8 5 7 PHAR class Attribute Name Attr.
6 F 2 S 0 8 5 7 PTOF class Attribute Name Attr.
6 F 2 S 0 8 5 7 PTTR class Attribute Name Attr. Type Explanation LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2) Data Common Logical Node Information T M/O GRT100 Resetable operation counter M O N Current for thermal load model Temperature for thermal load Relation between temperature and max.
6 F 2 S 0 8 5 7 PVPH class Attribute Name Attr.
6 F 2 S 0 8 5 7 GGIO class Attribute Name Attr.
6 F 2 S 0 8 5 7 MMXN class Attribute Name Attr.
6 F 2 S 0 8 5 7 MSQI class Attribute Name Attr.
6 F 2 S 0 8 5 7 SPS class Attribute Name DataName DataAttribute stVal q t subEna subVal subQ subID Attribute Type FC TrgOp Value/Value Range M/O/C GRT100 M M M Y Y Y PICS_SUBST PICS_SUBST PICS_SUBST PICS_SUBST N N N N O O AC_DLNDA_M AC_DLNDA_M AC_DLN_M N N N N N Inherited from Data Class (see IEC 61850-7-2) BOOLEAN Quality TimeStamp ST ST ST dchg qchg status TRUE | FALSE substitution SV SV TRUE | FALSE SV SV configuration, description and extension VISIBLE STRING255 DC Text UNICODE STRING
6 F 2 S 0 8 5 7 ACT class Attribute Attribute Type FC TrgOp Value/Value Range Name DataName Inherited from Data Class (see IEC 61850-7-2) DataAttribute status general BOOLEAN ST dchg phsA BOOLEAN ST dchg phsB BOOLEAN ST dchg phsC BOOLEAN ST dchg neut BOOLEAN ST dchg q Quality ST qchg t TimeStamp ST configuration, description and extension operTm TimeStamp CF d VISIBLE STRING255 DC Text dU UNICODE STRING255 DC cdcNs VISIBLE STRING255 EX cdcName VISIBLE STRING255 EX dataNs VISIBLE STRING255 EX Services As de
6 F 2 S 0 8 5 7 MV class Attribute Attribute Type FC TrgOp Value/Value Range M/O/C Name DataName Inherited from Data Class (see IEC 61850-7-2) DataAttribute measured values instMag AnalogueValue MX O mag AnalogueValue MX dchg M range ENUMERATED MX dchg normal | high | low | high-high | O low-low |… q Quality MX qchg M t TimeStamp MX M substitution subEna BOOLEAN SV PICS_SUBST subVal AnalogueValue SV PICS_SUBST subQ Quality SV PICS_SUBST subID VISIBLE STRING64 SV PICS_SUBST configuration, description and ex
6 F 2 S 0 8 5 7 CMV class Attribute Attribute Type FC TrgOp Value/Value Range M/O/C Name DataName Inherited from Data Class (see IEC 61850-7-2) DataAttribute measured values instCVal Vector MX O cVal Vector MX dchg M range ENUMERATED MX dchg normal | high | low | high-high | O low-low |… q Quality MX qchg M t TimeStamp MX M substitution subEna BOOLEAN SV PICS_SUBST subVal Vector SV PICS_SUBST subQ Quality SV PICS_SUBST subID VISIBLE STRING64 SV PICS_SUBST configuration, description and extension units Unit
6 F 2 S 0 8 5 7 WYE class Attribute Name DataName Data phsA phsB phsC neut net res DataAttribute angRef Attribute Type seqT TrgOp Value/Value Range M/O/C GRT100 GC_1 GC_1 GC_1 GC_1 GC_1 GC_1 Y Y Y Y N N Inherited from Data Class (see IEC 61850-7-2) CMV CMV CMV CMV CMV CMV ENUMERATED d VISIBLE STRING255 dU UNICODE STRING255 cdcNs VISIBLE STRING255 cdcName VISIBLE STRING255 dataNs VISIBLE STRING255 Services As defined in Table 21 SEQ class Attribute Name DataName Data c1 c2 c3 DataAttribute FC
6 F 2 S 0 8 5 7 SPC class Attribute Attribute Type FC TrgOp Value/Value Range Name DataName Inherited from Data Class (see IEC 61850-7-2) DataAttribute control and status ctlVal BOOLEAN CO off (FALSE) | on (TRUE) operTm TimeStamp CO origin Originator CO, ST ctlNum INT8U_RO CO, ST 0..
6 F 2 S 0 8 5 7 INC class Attribute Attribute Type FC TrgOp Value/Value Range Name DataName Inherited from Data Class (see IEC 61850-7-2) DataAttribute control and status ctlVal INT32 CO operTm TimeStamp CO origin Originator CO, ST ctlNum INT8U CO, ST 0..
6 F 2 S 0 8 5 7 ING class Attribute Attribute Type FC TrgOp Value/Value Range Name DataName Inherited from Data Class (see IEC 61850-7-2) DataAttribute setting setVal INT32 SP setVal INT32 SG, SE configuration, description and extension minVal INT32 CF maxVal INT32 CF stepSize INT32U CF 1 … (maxVal – minVal) d VISIBLE STRING255 DC Text dU UNICODE STRING255 DC cdcNs VISIBLE STRING255 EX cdcName VISIBLE STRING255 EX dataNs VISIBLE STRING255 EX Services As defined in Table 39 M/O/C GRT100 AC_NSG_M AC_SG_M
6 F 2 S 0 8 5 7 DPL class Attribute Attribute Type FC TrgOp Value/Value Range Name DataName Inherited from Data Class (see IEC 61850-7-2) DataAttribute configuration, description and extension vendor VISIBLE STRING255 DC hwRev VISIBLE STRING255 DC swRev VISIBLE STRING255 DC serNum VISIBLE STRING255 DC model VISIBLE STRING255 DC location VISIBLE STRING255 DC cdcNs VISIBLE STRING255 EX cdcName VISIBLE STRING255 EX dataNs VISIBLE STRING255 EX Services As defined in Table 45 M/O/C GRT100 M O O O O O AC_DLND
6 F 2 S 0 8 5 7 PICS: IEC61850 ASCI Conformance Statement Client/ subscriber Server/ publisher GRT10 0 - c1 Y c1 - - Client-server roles B11 Server side (of TWO-PARTYAPPLICATION-ASSOCIATION) B12 Client side of (TWO-PARTYAPPLICATION-ASSOCIATION) SCSMs supported B21 SCSM: IEC61850-8-1 used B22 SCSM: IEC61850-9-1 used B23 SCSM: IEC61850-9-2 used B24 SCSM: other Generic substation event model (GSE) B31 Publisher side B32 Subscriber side Transmission of sampled value model (SVC) B41 Publisher side B42
6 F 2 S 0 8 5 7 M12-2 DataRefInc M13 GSSE If SVC (B41/B42) is supported M14 Multicast SVC M15 Unicast SVC M16 Time M17 File Transfer Server S1 ServerDirectory Application association S2 Associate S3 Abort S4 Release Logical device S5 LogicalDeviceDirectory Logical node S6 LogicalNodeDirectory S7 GetAllDataValues Data S8 GetDataValues S9 SetDataValues S10 GetDataDirectory S11 GetDataDefinition Data set S12 GetDataSetValues S13 SetDataSetValues S14 CreateDataSet S15 DeleteDataSet S16 GetDataSetDirectory Subs
6 F 2 S 0 8 5 7 S31 SetLCBValues Log S32 QueryLogByTime S33 QueryLogAfter S34 GetLogStatusValues Generic substation event model (GSE) GOOSE-CONTROL-BLOCK S35 SendGOOSEMessage S36 GetGoReference S37 GetGOOSEElementNumber S38 GetGoCBValues S39 SetGoCBValues GSSE-CONTROL-BLOCK S40 SendGSSEMessage S41 GetGsReference S42 GetGSSEElementNumber S43 GetGsCBValues S44 SetGsCBValues Transmission of sampled value model (SVC) Multicast SVC S45 SendMSVMessage S46 GetMSVCBValues S47 SetMSVCBValues Unicast SVC S48 SendUSV
6 F 2 S 0 8 5 7 c10 – shall declare support for at least one (SendMSVMessage or SendUSVMessage).
6 F 2 S 0 8 5 7 A-Profile shortcut Profile Description PICS for A-Profile support Client Server F/S F/S GRT100 Remarks A1 A2 Client/server A-Profile c1 c1 Y GOOSE/GSE c2 c2 Y management A-Profile A3 GSSE A-Profile c3 c3 N A4 TimeSync A-Profile c4 c4 Y c1 Shall be ‘m’ if support for any service specified in Table 2 are declared within the ACSI basic conformance statement. c2 Shall be ‘m’ if support for any service specified in Table 6 are declared within the ACSI basic conformance statement.
6 F 2 S 0 8 5 7 InitiateRequest MMS InitiateRequest general parameters Client-CR Server-CR Base F/S Value/range Base F/S Value/range InitiateRequest localDetailCalling proposedMaxServOutstandingCalling proposedMaxServOustandingCalled initRequestDetail InitiateRequestDetail proposedVersionNumber proposedParameterCBB servicesSupportedCalling additionalSupportedCalling additionalCbbSupportedCalling privilegeClassIdentityCalling c1 Conditional upon Parameter CBB CSPI InitiateRequest m m m m m m m m m m m
6 F 2 S 0 8 5 7 MMS service supported conformance table Client-CR Server-CR MMS service supported CBB Base F/S Value/range Base F/S Value/range status getNameList identify rename read write getVariableAccessAttributes defineNamedVariable defineScatteredAccess getScatteredAccessAttributes deleteVariableAccess defineNamedVariableList getNamedVariableListAttributes deleteNamedVariableList defineNamedType getNamedTypeAttributes deleteNamedType input output takeControl relinquishControl defineSemaphore deleteSe
6 F 2 S 0 8 5 7 MMS service supported CBB deleteProgramInvocation start stop resume reset kill getProgramInvocationAttributes obtainFile defineEventCondition deleteEventCondition getEventConditionAttributes reportEventConditionStatus alterEventConditionMonitoring triggerEvent defineEventAction deleteEventAction alterEventEnrollment reportEventEnrollmentStatus getEventEnrollmentAttributes acknowledgeEventNotification getAlarmSummary getAlarmEnrollmentSummary readJournal writeJournal initializeJournal report
6 F 2 S 0 8 5 7 MMS service supported CBB Base Client-CR F/S Value/range Base Server-CR F/S Value/range GRT100 defineAccessControlList o c10 o c10 N getAccessControlListAttributes o c10 o c10 N reportAccessControlledObjects o c10 o c10 N deleteAccessControlList o c10 o c10 N alterAccessControl o c10 o c10 N reconfigureProgramInvocation o c10 o c10 N c1 Shall be ‘m’ if logical device or logical node model support is declared in ACSI basic conformance statement.
6 F 2 S 0 8 5 7 GetNameList GetNameList conformance statement Client-CR Server-CR Base F/S Value/range Base F/S Value/range GRT100 Request ObjectClass m m m m Y ObjectScope m m m m Y DomainName o o m m Y ContinueAfter o m m m Y Response+ List Of Identifier m m m m Y MoreFollows m m m m Y ResponseError Type m m m m Y NOTE Object class ‘vmd' (formerly VMDSpecific in MMS V1.0) shall not appear. If a request contains this ObjectClass, an MMS Reject shall be issued.
6 F 2 S 0 8 5 7 Read conformance statement Client-CR Base F/S Value/range Base Read Request specificationWithResult variableAccessSpecification Response variableAccessSpecification listOfAccessResult Request variableAccessSpecification listOfData Response failure success o m o m m m Y Y o m o m o m m m Y Y Server-CR F/S Value/range Request variableAccessSpecification listOfAccessResult m m m m m m Y Y m m m m m m m m Y Y Base F/S m m m m Value/range Base F/S m m m m Value/ra
6 F 2 S 0 8 5 7 GetNamedVariableListAttributes conformance statement Client-CR Server-CR GetNamedVariableListAttributes Base F/S Value/range Base F/S Value/range Request ObjectName Response mmsDeletable listOfVariable variableSpecification alternateAccess GRT100 m m m m Y m m m o m m m m m m m o m m m i Y Y Y N DeleteNamedVariableList conformance statement Not applicable. ReadJournal conformance statement Not applicable. JournalEntry conformance statement Not applicable.
6 F 2 S 0 8 5 7 FileRead Request frsmID Response+ fileData MoreFollows FileClose Request frsmID Response+ FileRead conformance statement Client-CR Server-CR Base F/S Value/range Base F/S Value/range GRT100 m m m m Y m m m m m m m m Y Y FileClose conformance statement Client-CR Server-CR Base F/S Value/range Base F/S Value/range m m m m m m m m GOOSE conformance statement Subscriber Publisher Value/comment GRT100 Y Y GRT100 GOOSE Services c1 c1 Y SendGOOSEMessage m m Y GetGoReference o
6 F 2 S 0 8 5 7 ⎯ 321 ⎯
6 F 2 S 0 8 5 7 Appendix Q Inverse Time Characteristics ⎯ 322 ⎯
6 F 2 S 0 8 5 7 IEC/UK Inverse Curves (NI) (Time Multiplier TMS = 0.1 - 1.5) 100 IEC/UK Inverse Curves (VI) (Time Multiplier TMS = 0.1 - 1.5) 100 10 Operating Time (s) Operating Time (s) 10 TMS 1.5 1. TMS 1.5 1 1.0 0.5 0.5 1 0.2 0.1 0.2 0.1 0.1 0.01 0.
6 F 2 S 0 8 5 7 IEC/UK Inverse Curves (EI) (Time Multiplier TMS = 0.1 - 1.5) 1000 100 UK Inverse Curves (LTI) (Time Multiplier TMS = 0.1 - 1.5) 10 100 Operating Time (s) Operating Time (s) 1000 1 TMS 1.5 1.0 0.1 TMS 1.5 10 1.0 0.5 0.5 0.2 1 0.1 0.2 0.1 0.1 0.
6 F 2 S 0 8 5 7 ⎯ 325 ⎯
6 F 2 S 0 8 5 7 Appendix R Failed Module Tracing and Replacement ⎯ 326 ⎯
6 F 2 S 0 8 5 7 1. Failed module tracing and its replacement If the “ALARM” LED is ON, the following procedure is recommended. If not repaired, contact the vendor. Procedure “ALARM” LED ON? Any LCD messages? Countermeasure No No No failure Not displayed Press [VIEW] key Yes Press [VIEW] key Contact the vendor. Yes Not displayed Contact the vendor. Locate the failed module referring to Table R-1. Caution: Check that the replacement module has an identical module name (VCT, SPM, IO1, IO2, etc.
6 F 2 S 0 8 5 7 Table R-1 LCD Message and Failure Location Message Failure location VCT SPM Checksum err × ROM data err × ROM-RAM err × SRAM err × CPU err × Invalid err × NMI err × BU-RAM err × EEPROM err × A/D err × Sampling err × IO1 or IO8 IO2 IO3 HMI AC cable CT1 err × (2) × (2) × (1) CT2 err × (2) × (2) × (1) CT3 err × (2) × (2) × (1) DIO err × (2) × (1) RSM err × (1) × (2) × (1) PLC, LAN cable/ IEC61850 data network × (1) × LCD err × DC supply off
6 F 2 S 0 8 5 7 2. Methods of Replacing the Modules CAUTION When handling a module, take anti-static measures such as wearing an earthed wrist band and placing modules on an earthed conductive mat. Otherwise, many of the electronic components could suffer damage. CAUTION After replacing the SPM module, check all of the settings including the data related the PLC, IEC103 and IEC61850, etc. are restored the original settings. The initial replacement procedure is as follows: 1).
6 F 2 S 0 8 5 7 5). Unplug the cables. Unplug the ribbon cable running among the modules by nipping the catch (in case of black connector) and by pushing the catch outside (in case of gray connector) on the connector. Gray connector Black connector 6). Pull out the module. Pull out the failure module by pulling up or down the top and bottom levers (white). SPM module 7). Insert the replacement module. Insert the replacement module into the same slots where marked up. . 8). Do the No.5 to No.
6 F 2 S 0 8 5 7 9). Lamp Test • • RESET key is pushed 1 second or more by LCD display off. It checks that all LCDs and LEDs light on. 10). Check the automatic supervision functions. • LCD not display “Auto-supervision” screens in turn, and Event Records • Checking the “IN SERVICE” LED light on and “ALARM LED” light off.
6 F 2 S 0 8 5 7 Appendix S Ordering ⎯ 332 ⎯
6 F 2 S 0 8 5 7 Ordering GRT100 D Model 100 series Type: Transformer protection Relay Model: -Model 100 series: 2 three-phase current inputs for 2-winding transformer - 16 BIs, 13 BOs, 5 trip BOs - 16 BIs, 23 BOs, 5 trip BOs CT Rating: 1A, 50Hz, 110V/125Vdc 1A, 60Hz, 110V/125Vdc 5A, 50Hz, 110V/125Vdc 5A, 60Hz, 110V/125Vdc 1A, 50Hz, 220V/250Vdc 1A, 60Hz, 220V/250Vdc 5A, 50Hz, 220V/250Vdc 5A, 60Hz, 220V/250Vdc 1A, 50Hz, 48V/54V/60Vdc 1A, 60Hz, 48V/54V/60Vdc 5A, 50Hz, 48V/54V/60Vdc 5A, 60Hz, 48V/54V/60Vdc 1
6 F 2 S 0 8 5 7 GRT100 D Model 200 series Type: Transformer protection Relay Model: -Model 200 series: 3 three-phase current inputs for 3-winding transformer - 16 BIs, 13 BOs, 5 trip BOs - 16 BIs, 23 BOs, 5 trip BOs - 15 BIs (12-independent), 13 BOs, 3 trip BOs - 15 BIs (12-independent), 23 BOs, 3 trip BOs CT Rating: 1A, 50Hz, 110V/125Vdc 1A, 60Hz, 110V/125Vdc 5A, 50Hz, 110V/125Vdc 5A, 60Hz, 110V/125Vdc 1A, 50Hz, 220V/250Vdc 1A, 60Hz, 220V/250Vdc 5A, 50Hz, 220V/250Vdc 5A, 60Hz, 220V/250Vdc 1A, 50Hz, 48V/
6 F 2 S 0 8 5 7 Version-up Records Version No. Date 0.0 1.0 Sep. 12, 2007 Apr. 14, 2008 2.0 Jul. 31, 2009 3.0 Oct. 16, 2009 4.0 Dec. 11, 2009 Revised Section -2.2.2 3.1.3 4.2.6.4, 4.2.6.6 4.4.2 Precaution 4.2.2,4.2.6.2,4.2.7 Appendixes 2.2.5 2.3 2.5 2.9 2.10.6 3.1.3 Appendix 2.2.1 Contents First issue Modified the description and Figure 2.2.2.1. Modified the description. Modified the description. Modified the description. Modified the description of ‘Disposal’. Modified the description.