E6581341 Expansion IO Card Option 2 ETB004Z Instruction manual NOTICE 1. Make sure that this instruction manual is delivered to the end user of the expansion IO card option. 2. Read this manual before installing or operating the expansion IO card option. Keep it in a safe place for reference. 3. All information contained in this manual are subject to change without notice. Please confirm the latest information on our web site “www.inverter.co.jp”.
E6581341 Safety precautions On the inverter and in its instruction manual, important information is contained for preventing injuries to users and damages to assets and for proper use of the device. Read the instruction manual attached to VF-AS1/PS1 along with this instruction manual for completely understanding the safety precautions and adhere to the contents of these manuals.
E6581341 ■ Limitation of use Safety precaution ▼ Never use this unit with any device other than TOSVERT VF-AS1/PS1 series inverters. Doing so may cause an accident. ■ General Operation Warning ▼ Never disassemble, modify or repair. Doing so could result in electric shock, fire and injury. For repairs, call your sales Disassembly agency. prohibited Prohibited Mandatory ▼ Do not attach this option to any inverter other than the VF-AS1/PS1. Doing so could result in electric shock or fire.
E6581341 ■ Wiring Caution Mandatory ▼ Electrical construction work must be done by a qualified expert. Installation or connection of input power by someone who does not have that expert knowledge may result in fire or electric shock. ▼ Shut off power when installing and wiring this option. Wait at least 15 minutes and check to make sure that the charge lamp (VF-AS1/PS1) is no longer lit. ▼ Tighten the screws on the terminal block to the specified torque (Refer to Section 2.2).
E6581341 Introduction Thank you for purchasing a “Expansion IO card option 2” for industrial inverter TOSVERT VF-AS1/PS1 inverter. By the use of this option, the expansion of input/output terminal is possible. This instruction manual describes connecting method and usage of the “Expansion IO card option”. Read this manual carefully before using the unit. Keep this manual near at hand of the operator who uses the “Expansion IO option” for future reference in the maintenance and inspection.
E6581341 Contents 1. Name and function of each section ............................................................................ 6 1.1. Appearance ......................................................................................................................................6 1.2. Name of each section (terminal) ......................................................................................................6 2. Installing the IO card option in the VF-AS1/PS1.................................
E6581341 1. Name and function of each section Following figure shows appearance and name of each section of the expansion IO card option. 1.1. Appearance Inverter cover hook for the fixation SINK/SOURCE Select SW SOURCE SINK(PLC) TB4 SINK(INT) TB3 TB2 TB1 1.2.
E6581341 2. Installing the IO card option in the VF-AS1/PS1 2.1. Connection to the inverter (1) Turn off input power before installing. Mandatory Turn off the input power of VF-AS1/PS1 and wait for at least 15 minutes and then check that the CHARGE lamp on VF-PS1 is no longer lit.
E6581341 2.2. Wiring When conducting wiring, follow the instructions below. • Use shield wire for control signal line and ground the unit with shield wire (Use twisted pair shield cable for wiring of the analog monitor output.) • Never bind the signal line and main circuit connection wire together. • Fix the communication cables after connected. The wire length of Using screwdriver Tightening peel off the end (The blade tip) torque Terminal Block Applicable wire size TB1 0.2 to 2.
E6581341 Terminal symbol TH2+ TH2- Function Thermal trip input Electrical specification The resistance between TH2+ and TH2Tripping value: about under 50 ohm or over 3k ohm Internal circuit P5 3k TH2+ Voltage detection circuit 10k ohm TH2- Reset value: about 1.8k ohm N10 OUT5 OUT6 NO2 -10V power supply Multifunction programmable open collector output.
E6581341 3. Functional description In this section, functions added by the installation of this expansion IO card option, on top of the standard inverter functions, are described. Note: When power on or reset the inverter, the initialization of the ETB004Z terminal inputs and outputs are delayed about 300ms from the inverter own terminals. 3.1. Multi-function output terminal Two output terminals and one relay output can be added.
E6581341 3.2. Multi-function input terminal Four output terminals can be added. Function is similar to that of the input terminals of the inverter, so refer to the inverter instruction manual.
E6581341 3.4. Multi-function analog output MON1, MON2 terminal output +/-10V, 0 - 10V, 0 - 20mA (4 - 20mA) analog signal. Example : MON1 output (0 - 10V) Example : MON1output (-10V - 10V) Gain adjustment: f673 Gradient characteristics f689 Bias adjustment: f690 -100% 100% 0% Bias adjustment: f690 0V 0% Gain adjustment: f673 10V Gradient characteristics (f689) is invalid when the output setting is -10V - 10V.
E6581341 Parameter Title f222 f223 f224 f225 Function AI1 input point 1 setting AI1 input point 1 frequency AI1 input point 2 setting AI1 input point 2 frequency Adjustment range -100 - 100% 0.0 - fh Hz -100 - 100% 0.0 - fh Hz -250 - 250% (for torque control etc.) -250 - 250% (for torque control etc.) 0 - 255 0 - 255 f226 * AI1 input point 1 rate f227 * AI1 input point 2 rate Optional AI1 input bias Optional AI1 input gain f476 f477 Default setting 0 0.0 100 60.
E6581341 Expansion IO card option P5 3k PTC thermistor TH2+ 10k Voltage detection circuit TH2- 3.8. Pulse train input (RP) The frequency command can be input from the pulse train input.
E6581341 4. External diagram Do not forget to reserve the space for the options at time of installation. External diagram of option (unit: mm) Dimension of optional unit The control panel depth increases about 21.6mm when the option is installed. Secure the front space from the inverter control panel fully. The space which is necessary for the option installation varies in the inverter capacity rate. Please refer to the inverter instruction manual.
E6581341 5. Specification Item Use Environment Ambient Temperature Storage Temperature Relative Humidity Vibration Specification Indoor, less than 3,000 m from the sea level. No direct sunlight, corrosive or explosive gas, steam, cutting dusts or dusts, grinding solution, and grinding oil. -10 to +60℃ -25 to +65℃ 20 to 93 % (No condensation) 5.9m/s² (0.
E6581341 6. Warranty TOSHIBA provides warranty with the product under the following conditions. 1. If and when a trouble occurs on the option unit properly installed and handled within one year of delivery, and if the trouble is clearly attributable to defects inherent in our design and manufacture, the product will be repaired free of charge. 2. The warranty covers only the delivered option unit. 3. Even in the term of the warranty, repair/adjustment service will be charged for the following cases.