E6581541② TOSVERT VF-PS1 series APOGEE® FLN option unit Instruction Manual APG001Z NOTICE 1. Make sure that this instruction manual is delivered to the end user of APOGEE® FLN option unit. 2. Read this manual before installing or operating the APOGEE® FLN option unit. Keep it in a safe place for reference. 3. All information contained in this manual are subject to change without notice. Please confirm the latest information on our web site “www.inverter.co.jp”.
E6581541② Safety precautions On the inverter and in its instruction manual, important information is contained for preventing injuries to users, damages to assets, and for proper use of the device. Read the instruction manual attached to the inverter along with this instruction manual to completely understand the safety precautions, the symbols and indications shown below. Please adhere to the contents of these manuals at all times.
E6581541② Limitation of use Safety precaution Never use this unit with any device other than TOSVERT VF-PS1 series inverters. Doing so may cause an accident. Handling in general Warning Never Disassemble Prohibited Mandatory Never disassemble, modify or repair the product. Disassembling the product may cause electric shocks, fire or injuries. For repairs, call your sales/repair agency. Do not open the front cover on the inverter while the inverter power is on. It may lead to electric shocks.
E6581541② Wiring Caution Mandatory Electrical construction work must be done by a qualified expert. Connection of input power by someone who does not have expert knowledge may result in electric shocks or fire. Turn off input power before wiring. Wait at least 15 minutes and make sure that the charge lamp (on the inverter unit) is no longer lit. Otherwise, it may lead to electric shocks. Tighten the screws on the terminal blocks to the specified torque when connecting cables to terminal blocks.
E6581541② Preface Thank you for purchasing the “APOGEE® FLN option (APG001Z)” for TOSVERT VF-PS1 inverter. By Installing this board into the VF-PS1, data communication can be made with a host computer or other device via APOGEE® FLN network. Before using this unit, carefully read this instruction manual in order to completely and correctly utilize excellent performance of this unit.
E6581541② Table of Contents 1. Overview ···································································································································6 2. Names and functions·················································································································6 2.1. Outline·······························································································································6 2.2.
E6581541② 1. Overview The APOGEE® FLN interface (APG001Z) allows the VF-PS1 inverter to be connected into a APOGEE® FLN network. APG001Z is applicable for VF-PS1 software version V620 or later. 2. Names and functions The drawing below shows names and functions of main parts. 2.1. Outline Connector to the inverter Don’t use this connecter Don’t use this switch Panel mounting tabs APOGEE LED indicator (See 2.3) Don’t use these switches Termination resistor SW(SW102) Earth Plate APOGEE Connector(See 2.
E6581541② 2.3. LED indicator The LED shows the present status of the network and error. ■Layout of LED COM 2.1 ERR 2.2 2.3 2.4 2.5 The option has two LEDs. Those function are below table. COM (Green) OFF OFF ON ERR (Red) OFF OFF 1s A State A 2s 1s B C LEDs COM LED: OFF ERR LED: Flashing 5 times in 1 second COM LED: OFF ERR LED: 3 times in 2 seconds, OFF for 1 second C COM LED: ON ERR LED: OFF 0.5s, ON 0.
E6581541② 3. Installing the APG001Z Install the APOGEE® FLN option to VF-PS1 as follows. Mandatory Turn off the input power of VF-PS1 and wait for at least 15 minutes and then check that the CHARGE lamp on VF-PS1 is no longer lit. (1) Turn off input power of VF-PS1 and wait for at least 15 minutes and then check that the CHARGE lamp on VF-PS1 is no longer lit.
E6581541② 3.1. Case of installing two options Please install this option (APG001Z) on the top of options when you install two options. Do not install under the another option. 3.2. Network cable connection Connect the APOGEE® FLN network cable to communication option as follows.
E6581541② 3.3. Network configuration Make up the network as follows. - Transmission/reception signals (A, B) Make up the communication path by connecting all transmission/reception data cables. - Signal common (GND) GND is the signal common. - Grounding the shield of cable (SCR) Connect the all shield lines of network cable. The shield shall be grounded at one end only prevent currents from being created.
E6581541② 4. Parameters 4.1. Communication parameters Set up the inverter parameters as follows. To update, reset of inverter. If these parameters are not set to correct value, this unit can not work normally. Title Commu nication No.
E6581541② 5. Command & Setpoint selection (Local/Remote) Indication to display Local/Remote mode is on the inverter unit (Refer to the inverter instruction manual for details). APOGEE® FLN option command and setpoint are activated on Remote mode. Inverters have some switches to select the command and setpoint location. Following figure shows the diagram. Refer to the inverter instruction manual for the parameter in detail.
E6581541② The example below shows how to configure the VF-PS1 for local/remote operation. F terminal..................... Operating command R terminal .................... The APOGEE® FLN local/remote (Terminal in this example) switching RR/S4 terminal..........
E6581541② 6.