Power Supply User Manual

TOSHIBA 4200FA XT UPS
Installation Planning Guide for 15-80kVA UPS
Standard System: 480v Input, 208/120V Output
Rev. 1.02 Page 1 of 2 4200FA-IPG-480v-XT1
General Mechanical Information
Dimensions
(W x D x H)
Approximate Full-Load Heat Loss
UPS kVA/ kW Rating
Inches
Weight
Lbs.
kBTU’s / Hr
15 kVA/12 kW 20 x 36.25 x 59.85 1,260 5.7
25 kVA/ 20 kW 20 x 36.25 x 59.85 1,275 7.6
30 kVA/ 24 kW 20 x 36.25 x 59.85 1,275 9.1
50 kVA/ 40 kW 35.59 x 38.19 x 59.39 2,523 17.7
80 kVA / 64 kW 44 x 31 x 74 2,200 40.0
Primary AC Input (480V 3-Phase / 3-Wire)
Maximum Input Power
Demand
Suggested External
Overcurrent Protection
Suggested Minimum Feeder
Wire Size Per Phase
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA PF Amps Amps AWG or kcmil at 75º C Temp. Rating Feet
15 >0.97 20 25 AT (1) x 10 480
25 >0.97 33.4 40 AT (1) x 8 480
30 >0.97 40 45 AT (1) x 8 480
50 >0.97 66.8 75 AT (1) x 4 480
80 >0.98 105.9 125 AT (1) x 1 480
Optional Alternate AC Input (208/120V 3-Phase / 4-Wire)
Maximum Input Power
Demand
Suggested External
Overcurrent Protection
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA Amps Amps AWG at 75º C Temp. Rating Feet
15 41.6 60 AT (1) x 8 / (1) x 6 480
25 69.4 90 AT (1) x 4 / (1) x 2 480
30 83.3 110 AT (1) x 3 / (1) x 1 480
50 138.8 175 AT (1) x 1/0 / (1) x 4/0 480
80 222.1 300 AT (1) x 4/0 / (1) x 400 480
Battery Input (288VDC Nominal)
Battery Capacity Required
for Full Load Output
Maximum Discharge
at Full Load Output
Suggested External
Overcurrent Protection
Suggested Minimum Feeder
Wire Size Per Phase
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kWB Amps DC Amps AWG or kcmil at 75º C Temp. Rating Feet
15 13.33 61.7 90 AT (1) x 6 70
25 22.22 102.8 125 AT (1) x 2 70
30 26.67 123.0 175 AT (1) x 1 70
50 44.44 205.7 225 AT (1) x 4/0 70
80 71.11 329.2 400 AT (2) x 3/0 70
AC Output (208/120V 3-Phase / 4-Wire)
Rated Output Power
Suggested External
Overcurrent Protection
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA PF Amps Amps AWG or kcmil at 75º C Temp. Rating Feet
15 0.8 41.6 60 AT (1) x 8 / (1) x 6 380
25 0.8 69.4 90 AT (1) x 4 / (1) x 2 380
30 0.8 83.3 110 AT (1) x 3 / (1) x 1 380
50 0.8 138.8 175 AT (1) x 1/0 / (1) x 4/0 380
80 0.8 222.1 300 AT (1) x 4/0 / (1) x 400 380