INSTALLATION AND MAINTENANCE GUIDE FOR MARKIII ELECTRIC FIRE PUMP CONTROLLERS MODEL SERIES: FTA740, FTA750, FTA1000, FTA1250, FTA1300, FTA1350, FTA1500, FTA1800, FTA1930 1
FTElectric Manual v2.2.0.0 (CDL) Introduction Electric fire pump controllers are designed to start an electric motor driven fire pump. It can either start the fire pump manually through the local start pushbutton or automatically through the sensing of a pressure drop in the sprinkler system. The fire pump controller is supplied with a pressure transducer. The fire pump can be stopped manually with the local stop pushbutton or automatically after the expiration of a field programmable timer.
TEST START The motor can be started manually by pressing the run test button. METHODS OF STOPPING MANUAL STOP Manual stop is done by pressing the priority STOP push button. Note that pressing the stop push button will prevent the motor from restarting as long as the button is pressed, plus a two second delay. AUTOMATIC STOP Automatic stop is possible only after an automatic start and this function has been activated.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
Electrical Connections A licensed electrician must supervise the electrical connections. The dimension drawings show the area suitable for incoming power and motor connections. No other location shall be used. Only watertight hub fittings shall be used when entering the cabinet to preserve the NEMA rating of the cabinet. The installer is responsible for adequate protection of the fire pump controller components against metallic debris or drilling chips.
Quick Start-Up Guide The rating label is the most important label. It must be read carefully to ensure the compatibility between the controller and the installation. Verify that the controller is installed securely on the wall, or optionally on the mounting stand.
Make sure to drill holes for the motor and power connections and run the cables inside the panel, all in accordance with the specifications in order to minimize interference with other equipment. Verify and/or install the proper water connections for the water input and the drain. They must be securely installed and tightened. Refer to the silkscreen markings on the plastic cover.
Connect the input power and the motor on their respective terminals. Secure with the appropriate torque as indicated on the torque label and verify all connections. Secure the door in closed position then put the circuit breaker disconnecting means in ON position. Verify the readings on the controller main screen. Once the controller has booted up, the “First Start Up” page appears. The controller will automatically detect and display the frequency of the power source.
Verify that the normal voltage shown at L1-L2, L2-L3 and L1-L3 (nominal) is the same as what is written on the fire pump controllers nameplate. The fire pump controller will validate the nominal voltage automatically versus what it has been built for. If all is adequate green check marks will appear.
Press “Motor Rotation” Press the “Start” button to start the electric motor and validate that the electric motor is rotating in the correct direction. If it is not rotating in the correct direction adjust the motor connections as per below. Press the “Stop” button to stop the electric motor. Acknowledge that the motor is tunring in the right direction by checking the Check on Normal Power selector box.
Choose the desired units of measurement for pressure reading and verify that it matches with the calibrated pressure gauge installed on the sensing line. Set the Cut-In value according to your system specifications. Cut-Out value will default to CutIn plus 10 PSI. To manually enter the cut-out, select the check-box besides it and enter the desired value (optional). When finished, press the Service Done button. Any errors will be highlighted in red and, if forced, be logged in the controller’s event logs.
From the “Home” page, verify that the displayed values are correct. The “First Start up” is now completed. The controller is fully installed and configured.
Main Features The Mark III A: Power LED 3 colors: Pulsing green if the Mark III is properly powered. B: Start button: Used to manually start the motor. C: Stop button: Used to stop the motor if all starting conditions are gone. D: Not used. E: Run Test button: Used to start the manual run test. Be aware that water will flow through the drain during the test. F: Touch Screen: 7 inch color touch screen LCD with protective cover. G: Locking mechanism for the protective cover of the screen. Push to open.
Mark III: Manual Rebooting Method If required, here is the procedure to manually reboot the Mark III: 1- Turn OFF all disconnecting means to de-energize the Mark III. The Mark III's screen should turn black. 2- Press the stop button or wait until the Mark III's LED extinguishes. 3- Wait 10 seconds. 4- Turn ON all disconnecting means. Pressure Transducer Test The controller will test the pressure transducer at least once a week if no manual run test or no weekly test has been conducted.
7. Select Controller Language System Status: Display the overwall system status. For more details, refer to the system status page. Motor power voltage. Each box represents an individual phase voltage between the two adjacent lines. Current. Each circle represents an individual line current. Motor contacts. An animation shows the contactor opened or closed depending on the signal sent to the main coil. The pressure gauge: It allows for a precise reading of the actual system pressure.
This page is used to access all data related to events, statistics, pressure history, power logs and the downloading of this information via one of the two USB ports. -Events: This button leads to the “Events” page, which displays the events from the most recent 500 logs. Each event log contains the date and time of occurrence as well as a brief description of the event.
Download Manuals Pressing on the question mark on the Mark III will redirect to the download page. A pdf version of the manual can be downloaded on an USB device. Language The language displayed on the Mark III can be selected on this page.
Firetrol Inc.