testo 557 · Digital manifold Instruction manual
1 Contents Pos : 1 /TD /Übersc hriften/1. Inhalt @ 0\mod_1177587817070_79.doc x @ 1243 @ 1 @ 1 1 Contents 1 Contents .................................................................................. 3 2 Safety and the environment ..................................................... 4 2.1. About this document ............................................................ 4 2.2. Ensure safety ......................................................................... 4 2.3. Protecting the environment ....
2 Safety and the environment Pos : 3 /TD /Übersc hriften/2. Sic herheit und U mwelt @ 0\mod_1173774719351_79.doc x @ 292 @ 1 @ 1 2 Safety and the environment Pos : 4 /TD /Übersc hriften/2.1 Zu di esem Dokument @ 0\mod_1173775252351_79.doc x @ 346 @ 2 @ 1 2.1. About this document Pos : 5 /TD /Sic herheit und U mwelt/Z u di esem Dokument/Ver wendung/Ver wendung (Standar d) @ 0 \mod_1173775068554_79.
3 Product description Pos : 13 /TD/Sic her heit und U mwelt/Sicherheit g ewährleis ten/tes to 550/Mec hanis che Bel astung testo 550 @ 4\mod_1252656121693_79.doc x @ 49837 @ @ 1 > If the manifold falls or another comparable mechanical load occurs, the pipe sections of the refrigerant hoses may break. The valve stem shutoff may also be damaged, whereby further damage to the interior of the manifold may occur that cannot be identified from the outside.
3 Product description Pos : 21 /TD/Ü berschriften/3.2 T ec hnisc he D aten @ 0\mod_1176211088437_79.doc x @ 704 @ 2 @ 1 Pos : 23 /TD/Ü berschriften/4. Produktbeschr eibung @ 0\mod_1173774846679_79.doc x @ 310 @ 1 @ 1 Pos : 24 /TD/Ü berschriften/4.1 Ü bersic ht @ 0\mod_1176379946003_79.doc x @ 733 @ 2 @ 1 3.2. Overview Pos : 25 /TD/Produktbes chr eibung/Ü bersicht/testo 5571 @ 17\mod_1426500685437_79.
3 Product description 4 Display. Instrument status icons: Icon Meaning Battery status Bluetooth® / / Select measuring mode 5 Battery compartment. The rechargeable batteries cannot be charged inside the instrument! 6 Control keys: Key Function [Set] Set units [R, ►, ■] Select refrigerant / Start-Stop leak test [Mode] Switch between measuring modes [Min/Max/Mean] Display min, max, mean values [▲] Up-key: Scroll through menu.
4 First steps : 24 /TD/--- Seitenwec hsel --- @ 0\mod_1173774430601_0.doc @ 281 Pos : 26 /TD/Ü berschriften/5. Erste Sc hritte @ 0\mod_1173774895039_79.doc x @ 319 @ 1 @ 1 4 First steps Pos : 27 /TD/Erste Schritte/testo 5571 @ 17\mod_1426501068054_79.doc x @ 211821 @ 5555 @ 1 Inserting batteries/rechargeable batteries 1. Fold out the hanging hook and open the battery compartment by squeezing the clip lock. 2. Insert batteries (included in delivery) or rechargeable batteries (4x 1.
0 Selectable parameters Description AUTO OFF Activate or deactivate Automatic power-off. Instrument switches off after 30 minutes if no temperature probe is connected and there is no pressure apart from ambient pressure Tfac Activate or deactivate surface temperature compensation factor, icon is shown on the display if the function is deactivated - Settings will be applied following the final selection.
5 Using the manifold 5 Using the manifold Pos : 29 /TD/Produkt ver wenden/testo 557/Ans chli eßen, nullen, ei nstellen @ 7 \mod_1289402475839_79.doc x @ 73068 @ 23553555555 @ 1 5.1. Preparing for measurement 5.1.1. Switching the instrument on > Press [ / ]. Zero the pressure sensors before every measurement. ✓ All connections must be at ambient pressure. > Press [P=0] key for 3 seconds to execute zeroing.
5 Using the manifold Key functions Description [▲] or [▼] Selectng another refrigerant [R, ►, ■] Confirm the selection and exit the refrigerant menu Available refrigerants Representation Description R... Refrigerant number of refrigerant acc. to ISO 817 --- no refrigerant selected. Example: Setting refrigerant R401B 1. Press [R, ►, ■] to activate refrigerant menu. 2. Press [▲] or [▼] several times, until R401B flashes. 3. Press [R, ►, ■] to confirm the setting.
5 Using the manifold Pos : 30 /TD/Produkt ver wenden/testo 557/Vakuumsonde ansc hließ en @ 16\mod_1421057560179_79.doc x @ 206127 @ 3 @ 1 5.1.3. Connecting the vacuum probe > Open the front cover of the connector and connect up the vacuum probe. Pos : 31 /TD/Produkt ver wenden/testo 557/Bluetooth Übersc hrift 557 @ 16 \mod_1421058427681_79.doc x @ 206167 @ 3 @ 1 5.1.4. Switching Bluetooth® on and off Pos : 32 /TD/Produkt ver wenden/testo 557/Bluetooth ei n-aussc halten @ 16\mod_1418732441244_79.
5 Using the manifold Display Mode Function Automatic mode If the automatic mode is activated, the testo 557 digital manifold automatically changes the display of the high and low pressure. This automatic change occurs when the pressure on the low-pressure side is 1 bar (15 psi) higher than the pressure on the high-pressure side. During the change, Load (2 s) is shown in the display. This mode is especially suited to air conditioning systems which cool and heat (heat pumps).
5 Using the manifold condensation temperature Co/tc are displayed after evaporation and condensation are complete. Zeotropes (refrigerants blends mix together) can separate from each other, unlike azeotropes which mix together to become one. Zeoptropes often blend refrigerants with different boiling points (saturation temps), where one will change from liquid to vapor before the other as they go through the evaporator.
5 Using the manifold Changeable - Evaporation Temperature (Ev) - Measured Temperature (T1) - Superheating (SH) Evaporation pressure Changeable - Condensation Temperature (Co) - Measured Temperature (T2) - Subcooling (SC) Condensation pressure With both NTC temperature probes connected, Δt is also shown. > Press [Mean/Min/Max]: to display min. / max. readings and mean values. Leak test / pressure drop test Systems can be tested for tightness with the temperaturecompensated leak test.
5 Using the manifold Duration of test Measured pressure beginning of test Differential pressure start compared to actual Actual measured pressure Vacuum measurement ✓ The vacuum probe is plugged into the front connection of the manifold and connected to the system. 1. Press [Mode] the vacuum mode is displayed. If ambient pressure is applied to the vacuum probe, then oooo is shown on the display. 2. Start the vacuum pump.
6 Technical data 6 Technical data Pos : 22 /TD/Leistungs bes chr eibung/T ec hnische D aten/testo 5571 @ 17\mod_1426500292878_79.doc x @ 211611 @ 33 @ 1 6.1.1. Bluetooth Modul The Bluetooth® option may only be operated in countries in which it is type approved. Feature Values Bluetooth Range >20 m (free field) Bluetooth type LSD Science & Technology Co.
6 Technical data 6.1.2. General technical data Feature Values Parameters Pressure: psi / kPa / MPa / bar Temperature: °F / °C / K Vacuum: micron / inHg / inH2O / hPa / mbar / mTorr /Torr / Pa Sensors 2 Pressure: sensors, 2 Temperature (NTC Thermistors) Measuring cycle 0.5 s Interfaces Pressure connections: 3 x 1/4" SAE, 1x 3/8" SAE NTC measurement External vacuum probe Measuring ranges Pressure measurement range HP/LP: -14.7…870 psi / -100…6000 kPa / -0.
6 Technical data Feature Selectable refrigerants Measurable media Values No refrigerant, R11, R12, R22, R123, R1234ze, R125, R13B1, R134a, R14, R142B, R152a, R161, R23, R227, R290, R32, R401A, R401B, R401C, R402A, R402B, R404A, R406A, R407A, R407B, R407C, R407D, R407F, R408A, R409A, R410A, R411A, R412A, R413A, R414B, R416A, R417A, R420A, R421A, R421B, R422A, R422B, R422C, R422D, R424A, R426A, R427A, R434A, R437A, R438A, R502, R503, R507, R508A, R508B, R600, R600a, R718 (H2O), R744 (CO2) (only in permissi
7 Maintaining the product Feature Values Warranty Duration: 2 years Terms of warranty: see website www.testo.com/warranty Pos : 35 /TD/Ü berschriften/7. Produkt i nstand halten @ 0\mod_1173789831362_79.doc x @ 397 @ 1 @ 1 7 Maintaining the product Pos : 36 /TD/Produkt i nstand halten/Gerät rei nigen 5571 @ 17\mod_1426501226500_79.doc x @ 211891 @ 2 @ 1 Cleaning the instrument Do not use harsh cleaning agents or solvents! Mild soap and water may be used. > Clean instrument using a damp cloth.
7 Maintaining the product 2. Remove discharged batteries/rechargeable batteries and insert new batteries/rechargeable batteries (4x 1.5 V, type AA, Mignon, LR6) in the battery compartment. Observe the polarity! 3. Set on and close cover of the battery compartment (clip must engage). 4. Switch the instrument on. Changing the valve or valve stem shutoff DO NOT ATTEMPT to change the valve stems. Changing the valve stem shutoff or valves themselves will void the warranty.
8 Tips and assistance Pos : 38 /TD/Ü berschriften/8. Tipps und Hilfe @ 0\mod_1173789887985_79.doc x @ 406 @ 1 @ 1 8 Tips and assistance Pos : 39 /TD/Ü berschriften/8.1 Fr agen und Antworten @ 0\mod_1177402017078_79.doc x @ 1093 @ 2 @ 1 8.1. Questions and answers Pos : 40 /TD/Ti pps und Hilfe/Fr agen und Antworten/testo 550/FAQ testo 550 @ 5\mod_1265185945986_79.doc x @ 56964 @ @ 1 Question Possible causes/solution flashes Batteries are almost empty. > Change batteries.
8 Tips and assistance 8.3. Error reports Question Possible causes/solution ---- is lit up instead of measurement parameter display Sensor or cable defective > Please contact your dealer or Testo Customer Service Display EEP FAIL Eeprom defective > Please contact your dealer or Testo Customer Service Display BT ERR No BT module connected or BT module defective.
8 Tips and assistance === Ende der Liste für T extmar ke Inhalt === 24
Testo Inc. 40 White Lake Road Sparta, N. J. 07871 Phone: +1 862 354 5001 Fax: +1 862 354 5020 Email: info@testo.com www.testo.com Headquarter testo AG Testo-Straße 1 79853 Lenzkirch Germany Tel.: +49 7653 681-0 Fax: +49 7653 681-7699 Email: info@testo.de Internet: www.testo.de 0970 5571 en-US 01 V01.
FCC statements: This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. NOTE: The manufacturer is not responsible for any radio or TV interference caused by unauthorized modifications or changes to this equipment.