EcoGuard Installation Guide SS8020 Company Headquarters: Telkonet, Inc. 10200 W. Innovation Dr. Suite 300 Milwaukee, WI 53226 Support Information: Toll Free: +1 (800) 380 9640 Email: support@telkonet.com Sales Information: Toll Free: +1 (888) 703 9398 Email: sales@telkonet.
Table of Contents Table of Contents Table of Contents ....................................................................................................................i Installation Requirements .......................................................................................................... 1 Required Equipment ............................................................................................................. 1 Electrical Requirements .................................................
Installation Requirements Installation Requirements Required Equipment EcoGuard (P/N: SS8020) Flathead screwdriver for mounting and unmounting wall plate. Wire nuts Voltmeter A paperclip for thermostat/occupancy sensor association.
Installation Requirements Regulatory Compliance FCC Notice This equipment has been tested and found to comply with the limits for a class B digital device pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions, may cause harmful interference to radio communications.
Wiring the EcoGuard Wiring the EcoGuard 1. 2. 3. 4. 5. 6. Turn the power off at the circuit breaker. Unmount the existing outlet cover plate. Unmount the existing outlet from the junction box. Use the voltmeter to verify the power is off. Disconnect the existing outlet from its wiring. Use the table below to determine which wires are the 120V LINE, GROUND, and NEUTRAL from the circuit breaker.
Wiring the EcoGuard 12. 13. 14. 15. 16. 17. 18. Turn the power on at the circuit breaker. Verify the LEDs next to both outlets are lit solid green. Turn the power off at the circuit breaker. Mount the EcoGuard into the junction box. Mount the outlet cover plate. Turn the power on at the circuit breaker. Wiring is complete.
Associating the EcoGuard with an EcoInsight Associating the EcoGuard with an EcoInsight 1. Verify both the EcoGuard and the EcoInsight are powered. 2. Press and hold the “Fan” button on the EcoInsight for 10 seconds, then press the “On/Off” button. The Maintenance Menu should appear. 3. Verify the text “Learn” appears in the Maintenance Menu. 4. Press the “On/Off” button to enter the Learn menu.
Associating the EcoGuard with an EcoInsight 5. Assign a unique installer number by pushing the up or down arrows. The number at the bottom of the screen will increase or decrease. 6. Press the “On/Off” button again to activate Learn Mode. The text “On” should appear next to the bottom number. See Figure 4. Figure 4: Maintenance -> Learn Menu with 1 Device Associated, In Learn Mode 7. Using the paperclip, press the pushbutton inside the EcoGuard’s pinhole once. 8.
Associating the EcoGuard with an EcoWave (EcoAir + EcoSource) Associating the EcoGuard with an EcoWave (EcoAir + EcoSource) 1. Verify the EcoGuard, EcoSource, and EcoAir are powered. 2. Press and hold the “Fan” button on the EcoAir for 10 seconds, then press the “On/Off” button. The Maintenance Menu should appear. 3. Verify the text “Learn” appears in the Maintenance Menu. 4. Press the “On/Off” button to enter the Learn menu.
Associating the EcoGuard with an EcoWave (EcoAir + EcoSource) 5. Assign a unique installer number by pushing the up or down arrows. The number at the bottom of the screen will increase or decrease. 6. Press the “On/Off” button again to activate Learn Mode. The text “On” should appear next to the bottom number. See Figure 4. Figure 7: Maintenance -> Learn Menu with 1 Device Associated, In Learn Mode 7. Using the paperclip, press the pushbutton inside the EcoGuard’s pinhole once. 8.
Associating the EcoGuard with an EcoView Occupancy Sensor Associating the EcoGuard with an EcoView Occupancy Sensor 1. 2. 3. 4. 5. Verify the EcoGuard and EcoView are powered. Using the paperclip, press the pushbutton inside the EcoGuard’s pinhole once. Verify the LED on the EcoGuard blinks red. Using the paperclip, press the pushbutton inside the EcoView’s pinhole once. Verify the LED on the EcoGuard returns to solid green.
Troubleshooting Troubleshooting Issues Associating the EcoGuard with an EcoInsight or EcoWave Problem Potential Cause Potential Solution After pressing the EcoGuard’s pushbutton with a paperclip, the EcoGuard LED blinks green. The EcoGuard cannot find an EcoInsight or EcoView in Learn mode on the ZigBee™ network. Reactivate Learn mode on the EcoInsight or EcoWave and try again. After pressing the EcoGuard’s pushbutton with a paperclip, the EcoGuard LED is solid red.