EcoSmart VRF Controller Firmware Version 2.x Installation, Operation & Maintenance Guide Use this guide along with the EcoAir or EcoTouch+ IOM as applicable.
EcoSmart VRF Controller: Part of the EcoWave Remote Thermostat/Controller Package ............................ 5 EcoSmart VRF Controller Required Equipment ............................................................................... 9 EcoSmart VRF Controller Installation .......................................................................................... 9 ZigBee Wireless...................................................................................................................
The EcoSmart Energy Management System any interference received, including interference that may cause undesired operation. The EcoSmart Energy Management System reduces HVAC energy consumption without interfering with occupant comfort. EcoSmart thermostats such as the EcoAir/EcoTouch automatically learn and adapt to the heating and cooling patterns of each room.
EcoAir/EcoTouch thermostats in different areas of a building give each individual area the ability to make setpoint changes to control a single EcoSource+. Together, the EcoWave package forms a wireless programmable controllable thermostat with over 125 configurable settings used to control the efficiency of HVAC systems. It can be easily installed on packaged terminal air conditioners, fan coils, heat pumps, split systems, and more.
EcoSmart VRF Controller: Part of the EcoWave Remote Thermostat/Controller Package EcoSmart VRF Controller: Part of the EcoWave Remote Thermostat/Controller Package The EcoWave package is comprised of two hardware components as shown below. Together they form a wireless programmable controllable thermostat. With software-based relay control and fan speed configuration, programming setup is simple and fast.
EcoSmart VRF Controller: Part of the EcoWave Remote Thermostat/Controller Package Multiple EcoTouch+ (or EcoAirs) can control one HVAC system, equipped with one EcoSource VRF. The wiring interface conforms to industry standards. Telkonet can develop specific wiring diagrams, if a complete specification is provided for the HVAC unit(s) in use at the site. EcoSmart VRF Controller I, O & M Guide For Use with Firmware Version 2.
EcoSmart VRF Controller: Part of the EcoWave Remote Thermostat/Controller Package Figure 1- EcoAir/Controller/HVAC Wiring Diagram EcoSmart VRF Controller I, O & M Guide For Use with Firmware Version 2.x EcoSmart VRF Controller: Part of the EcoWave Remote Thermostat/Controller Package Revision 2.3 Page 7 Telkonet, Inc. 20800 Swenson Drive, Suite 175 Waukesha, WI 53186 (800) 380-9640 www.telkonet.
EcoSmart VRF Controller: Part of the EcoWave Remote Thermostat/Controller Package Figure 2- EcoTouch+/Controller/HVAC Wiring Diagram EcoSmart VRF Controller I, O & M Guide For Use with Firmware Version 2.x EcoSmart VRF Controller: Part of the EcoWave Remote Thermostat/Controller Package Revision 2.3 Page 8 Telkonet, Inc. 20800 Swenson Drive, Suite 175 Waukesha, WI 53186 (800) 380-9640 www.telkonet.
EcoSmart VRF Controller Required Equipment Caution Power to the indoor unit should be removed before connecting the EcoSmart VRF Controller. Communication The EcoAir and EcoTouch+ communicate with the EcoSmart VRF Controller via a 2.4GHz wireless interface. Join & Pair Set up the EcoAir & EcoSmart VRF Controller to talk to each other by “pairing” them. If EcoSmart products will be networked, they must first “join” the network (see steps below).
EcoSmart VRF Controller Installation 1. Mount EcoSmart VRF Controller next to indoor unit so harness connects directly to indoor unit terminals (see Figure 7 & Figure 8). Figure 3 Figure 4 2. Turn off power at EcoSmart VRF Controller mounting location using a disconnect switch or breaker lockout/tag out on appropriate breaker panel. 3. Test that power is off by using a voltmeter. 4. Using the end tabs, screw the EcoSmart VRF Controller to the wall or HVAC. 5.
EcoSmart VRF Controller Installation Figure 5-J4 Molex Properly Seated Figure 6 EcoSmart VRF Controller I, O & M Guide For Use with Firmware Version 2.x EcoSmart VRF Controller Installation Revision 2.3 Page 11 Telkonet, Inc. 20800 Swenson Drive, Suite 175 Waukesha, WI 53186 (800) 380-9640 www.telkonet.
EcoSmart VRF Controller Installation Figure 7 Figure 8 6. Install EcoAir/EcoTouch+ per EcoAir or EcoTouch+ IOM. 7. Associate devices as outlined in the Device Association Guide. 8. Test as outlined in EcoAir/EcoTouch+ IOM. For variable output connections, see Appendix B. EcoSmart VRF Controller I, O & M Guide For Use with Firmware Version 2.x EcoSmart VRF Controller Installation Revision 2.3 Page 12 Telkonet, Inc. 20800 Swenson Drive, Suite 175 Waukesha, WI 53186 (800) 380-9640 www.telkonet.
ZigBee Wireless Table 1-Wiring J4 Connector PIN # Wire 22AWG stranded SIGNAL COLOR 1 F3 12VDC PLC (Power 3 communication on the same wires) BLUE *1 *2 2 F4 12VDC PLC WHITE *1 *2 3 RS485_N2 ORANGE Friedrich VRP RS485_P2 YELLOW Friedrich VRP 5 GND GREEN *2 6 NC BLUE 7 RS485_N1 PURPLE 8 RS485_P1 GREY 9 GND (EcoAir) BLACK (Move J5 to inside pins) 10 3.
ZigBee Wireless ZigBee Wireless Telkonet’s suite of products—including the EcoSmart VRF Controller —rely on the ZigBee wireless communications protocol. Field Modifications-Functional Caveats Telkonet ships equipment to customers pre-programmed based on a pre-deployment analysis and discussion with Property Management. Generally, command-level programming at the field level will not be needed. When a command change is needed, Telkonet will provide a detailed synopsis of the proposed changes.
Regular Maintenance In most cases, entering the room will have initiated an HVAC drive cycle after the Sensor detected occupancy. Possible exceptions: -If the temperature in the room is within hysteresis of the HVAC setpoint, a drive cycle may not commence; -A delay may have been programmed into the EcoSmart VRF Controller thermostat, instructing the unit to wait for a particular duration before triggering a drive. (Although uncommon, this feature is sometimes requested by a property.
Troubleshooting Troubleshooting If the EcoSmart VRF Controller loses association to any one of its sensors, either the on-board PIR sensor or the external EcoSense or EcoContact, the thermostat will immediately revert to Occupied mode. This is done to ensure that sensor association loss does not affect the comfort of the room occupant. Any setpoint limits (e.g. max/min allowed temperatures) that have been assigned to the thermostat remain in force.
Troubleshooting Window or outside door is open. 7 EcoSmart VRF Controller I, O & M Guide For Use with Firmware Version 2.x Troubleshooting Revision 2.3 Page 17 Ensure that no monitored windows or patio doors are open. Telkonet, Inc. 20800 Swenson Drive, Suite 175 Waukesha, WI 53186 (800) 380-9640 www.telkonet.
Appendix A-Anatomy of EcoSource VRF Conroller Appendix A-Anatomy of EcoSource VRF Conroller J1 Used for power options J6 EcoSmart data jack-RS232 J2 Used for power options J7 VO output #3 J3 IR LED driver J8 JTag J4 Wiring Molex harness for HVAC connection J9 VO output #2 J5 Used for power options J10 VO output #1 1 1 *J3: The IR LED driver is used to transmit IR signals to IR receivers (such as IR remote controlled HVAC like most mini-splits) 7 EcoSmart VRF Controller I, O & M Guide For
Appendix B-Additional Installation Options Appendix B-Additional Installation Options NTC Probe Temp probes can be used for multiple purposes: 1) 2) 3) 4) HVAC Discharge Air temp HVAC Return Air temp Supply Water Temp AquaStat Mode (switches thermostat’s Heat/Cool) If not using Telkonet provided external temperature probe, use a probe with a Beta R0 must match. Alternatively, a probe can be provided to Telkonet for lab calibration.
Appendix B-Additional Installation Options If no jumpers installed, then there is no output. Cooling Valve, Heating Valve, Motor Each of the 3 outputs can be configured for any of these modes (cooling valve, heating valve, motor). Currently, firmware is built specifically for each application. 7 EcoSmart VRF Controller I, O & M Guide For Use with Firmware Version 2.x Appendix B-Additional Installation Options Revision 2.3 Page 20 Telkonet, Inc.