User manual for DV with control system Air handling unit Manual version 1.01.
Detailed table of contents on the following pages General description a. Manufacturer b. Name of machines c. Declaration of conformity ‐ example d. General descriptions, dangers and warnings e. Drawings, diagrams, guides and instructions for use, maintenance, repairs f. Employees in charge of operation/control/maintenance g. Intended use and applications h. Unintended use and misuse – inappropriate applications for the machine Installation i.
Contents A. MANUFACTURER ................................................................................................................................. 11 B. NAME OF MACHINES........................................................................................................................... 11 C. DECLARATION OF CONFORMITY ‐ EXAMPLE ............................................................................. 12 D. GENERAL DESCRIPTIONS, DANGERS AND WARNINGS ..........................................
i.1.2 Unloading by crane ............................................................................................................... 24 i.1.3 Transport of unit without base frame on the site ................................................................... 24 i.1.4 Lifting a unit with straps ........................................................................................................ 24 i.1.5 Lifting a unit with preinstalled brackets on the base frame for lifting. ..........................
i.4.4.3.4 Valve motor and valve for cooling .................................................................................... 38 i.4.5 Draining condensate water .................................................................................................... 38 i.4.6 Draining condensate water from plate heat exchanger ........................................................... 38 i.4.7 Draining condensate water from cooling battery ....................................................................
k.6.11.2 Cabinet placed on the DV unit with control system ........................................................... 44 k.6.12 Temperature sensors .......................................................................................................... 45 k.6.13 Damper motors .................................................................................................................. 45 k.6.14 Filter guards .............................................................................................
N. THE ESSENTIAL CHARACTERISTICS OF TOOLS WHICH MAY BE FITTED TO THE MACHINERY ............................................................................................................................................... 50 O. THE CONDITIONS OF STABILITY DURING USE, TRANSPORTATION, ASSEMBLY, DISMANTLING WHEN OUT OF SERVICE............................................................................................ 50 o.1 Installed reliable to avoid units to be tilted or moved by the any storm. ............
r.5.7.1 Motor ................................................................................................................................ 62 r.5.8 Silencer DVD ......................................................................................................................... 63 r.5.9 Outdoor air section DVY ........................................................................................................ 63 r.5.10 Heat pump unit – DVU‐HP .....................................................
ANNEX 8 INSTALLATION OF STEEL ROOF IN THE SIZES 10‐150 ............................................. 68 ANNEX 9 ROTARY EXCHANGER – SPEED CONTROL AND ASSEMBLY OF DIVIDED ROTOR ........................................................................................................................................................................ 68 ANNEX 10 HEAT PUMP UNIT – DVU‐HP............................................................................................
Annex 8. Installation of steel roof in the sizes 10‐150 .................................... 8—1 8.1 Overview ................................................................................................................................. 8—1 8.1.1 Mount rails. Units of size 10, 15, 20, and 25 ....................................................................... 8—1 8.1.2 Mount rails. Units of size 30 and units larger than size 30. .................................................. 8—2 8.1.
12.5.1 Connection .................................................................................................................... 12—8 Residual‐current‐operated protective devices .......................................................................... 12—9 12.5.2 Diagnostic/faults ........................................................................................................... 12—9 Annex 13. Commissioning report ................................................................
a. Manufacturer This User Manual covers all air handling units with control system delivered by Systemair A/S. Manufacturer and supplier data: Systemair A/S Ved Milepælen 7 DK‐8361 Hasselager Responsible for documentation: Ulf Bang b.
c. Declaration of Conformity ‐ example The manufacturer: Systemair A/S Ved Milepælen 7 DK - 8361 Hasselager Hereby declares that, air handling units of the flowing types: DANVENT DV10, DANVENT DV15, DANVENT DV20, DANVENT DV25, DANVENT DV30, DANVENT DV40, DANVENT DV50, DANVENT DV60, DANVENT DV80, DANVENT DV100, DANVENT DV120, DANVENT DV150, DANVENT DV190 and DANVENT DV240.
d. General descriptions, dangers and warnings TIME and DV air handling units are order specific machines available in thousands of different configurations. Only a few examples of machine configurations are described below. The air handling units are intended for the transport and treatment of air between ‐40 °C and + 40 °C The units are exclusively for comfort ventilation. Maintenance of the units must be carried out by skilled technicians.
d.1.1 Where are pictograms placed on the units Example (Symbols and descriptions of functions for fast identification) Position Description 1 The CE label and the unique production number of this machine 2 Machine card 3 Damper ‐ supply air 4 Filter ‐ supply air 5 Fan‐ supply air 6 Heating battery ‐ supply air 7 Fan ‐ extract air 8 Rotary heat exchanger 9 Filter – extract air 10 Damper – extract air 11A 3 labels.
d.1.2 CE label – example for DV unit This is the mandatory informations for the CE marking with; Product name (in this example Danvent DV 20, where 20 informs about the size of the unit), Production number for the complete unit (in this example YYMM‐xxxxx‐x, where YYMM informs about year and month for the manufacture), xxxxx‐x is the unique production number. d.1.
d.1.
DVE Plug fan DVD Silencer DVX Humidifier d.1.
d.2 Data about the unit according to cards and labels in and on the unit d.2.1 Machine card with unique data on every unit An example of a machine card is shown below.
d.2.2 Label with data about the cabinet Systemair A/S An example of the label that is always placed on or with the cabinet Systemair declares hereby that the cabinet is in conformity with: SBB Low voltage N60439‐1 panels: Electrical material on EN60204‐1 machines: EMC‐directive 89/336/EOF environment: Diagram version DV ver. 2.
d.2.4 Symbols in the flowchart and explanation about the symbols.
d.2.5 Example of label placed on or with the cabinet – Terminal plan for external components d.3 Hand terminal The hand terminal is delivered in a cardboard box containing the other external components. This cardboard box is usually, but not always, placed in the section with the supply air fan. The Operator’s Guide for the hand terminal is the annex 17 attached to this – User Manual. 1. ALARM: Press for alarm list 2. Alarm LED – red light for alarm 3. LED indicating change of parameters 4. OK/ENTER 5.
d.5 Ordinary automatically operation – only manual operation by new parameters. The unit is operating fully automatically and manual operation includes only selection of new parameters via the buttons on the hand terminal. The hand terminal is connected by a cable to the controller in the cabinet. 10 meters of cable is delivered with the unit and the customer has the possibility to replace this cable with an identical type of cable that is up to 100 meters long.
Instructions for use of the machine – section k in this manual Instructions about adjustment and maintenance – section r in this manual Safety during adjustment and maintenance – section s f. Employees in charge of operation/control/maintenance The units are constructed and built with a fully integrated control system. After start‐up and hand‐over from installer to operators, the unit operates fully automatically.
i. Instructions for unloading on the site as well as installation and connection i.1. Unloading on the site The air handling unit – AHU ‐ is delivered as one section or in several sections, which are to be assembled on site. The AHU is delivered on transport pallets, legs or on a base frame. Loading and unloading as well as transport on the site is possible by fork‐lift truck or by crane using suitable lifting straps. i.1.
i.1.5 Lifting a unit with preinstalled brackets on the base frame for lifting. Lifting beam and straps are not included in the delivery. i.1.6 Roof unit with bitumen roof Avoid damaging the drip nose profiles along the bitumen roof. Keep the protection profiles of Styrofoam on the unit until the installation has been completed. If the unit is lifted by straps, the straps must be kept away from the drip nose profiles by bars to avoid damage to roofing profiles.
i.1.7 Roof unit with steel roof For units with steel plate roof, the steel plates are delivered uninstalled on a separate pallet. Do not step or walk on the plates. . i.1.8 Pre‐assembly storage The AHU must be protected from the weather and accidental impact. Plastic packaging must be removed and the unit covered with tarpaulin or similar materials. In order to minimize condensation, sufficient air circulation must be ensured between the covering and the unit. i.1.
i.2.4 Base frame assembly Base frame is delivered unassembled for the indoor units that are delivered in sections on pallets. Assembly of the base frame is illustrated on 4 pages in a manual in a plastic bag which is attached to one of the large base frame parts. The 4 pages with the illustration regarding the assembly of the base frame are also available in this user manual in annex 4, 5, 6 or 7. There are two types of base frames: 1. 150 mm high base frames 2.
i.2.6 Installation on the site of unit sections at the base frame when sections are delivered on pallets Lift up the section by hand manual forklifts to the level where the underside of the section is even with the overside of the base frame. 1. Pull the section to the correct position on the base frame by lifting straps – it is maybe necessary to support the section by heavy duty furniture trolleys (see the photos below) Example of heavy duty furniture trolley turned with the wheels upwards.
2. Pull sections together with lifting straps. We recommend the below shown type of brackets because this type is not damaging the frame profiles of the units. An example of lifting straps is shown below. 3. Sections are mounted to base frames with long self‐drilling screws. The frame profile under the inspection doors is placed over the horizontal profile of the base frame. See the example on the photo below.
i.2.7 Joining the AHU sections The sections must be placed on the base frame and if the unit is delivered with 100 mm legs, the sections must be positioned directly opposite each other. 1. Ensure that the internal factory‐fitted rubber sealing is undamaged 2. The sections are then to be positioned directly opposite each other. If the sections are built with legs, the adjustable feet can be used to get the sections parallel and at the same height. 3.
i.2.10 Remove transport brackets – when spring mounts are installed i.2.10.1 Impeller diameters 220 – 560 mm If the fans are installed on spring mounts the transport brackets must be removed after the installation of the air handling unit. Two transport brackets are fitted to the coil springs during transport and installation. Both transport brackets must all be removed to give the full anti‐vibration function to the coil springs. The transport brackets are made more visible with yellow labels.
i.2.10.2 Impeller diameters 630 – 1.000 mm If the fans are installed on spring mounts the transport brackets must be removed after the installation of the air handling unit. Four transport brackets are fitted to the coil springs during transport and installation. The four transport brackets must all be removed to give the full anti‐vibration function to the coil springs. The transport brackets are made more visible with yellow labels, as shown in the picture below.
i.2.11 Refitting of guards The guard is a safety guard installed inside the door. Tools are necessary for the removal of the guard. If the guard has been demounted during the installation on the site, the guard must be refitted before startup of the unit. Insert the edges of the guard in the frame profile in the groove that is in the frame profile, and connect both parts of the guard at the middle with 2 screws. Replace the vibration damping foam rubber list if it is damaged. i.3.
i.3.2.1 DV units – labels on or with the cabinet Label with data about the cabinet – including data about fuses – see section d.2.2 Flowchart – see section d.2.3 – unique for the order specific unit – printed with the unique production number of the unit Label with terminal plan for external components – see section d.2.5 – standard, and not unique for the order specific unit i.3.3 Installation of mains power supply An AC/DC residual current device must be installed in the power supply.
Position Description 1 Alarm button: Press for alarm list. 2 Alarm indicator: Flashing for unacknowledged alarm. 3 Write enable LED: Slow flashing indicates parameters can be changed. 4 OK button: Press to activate a selected menu/setting, if possible. 5 Button for clear: Abort a parameter setting or – if possible ‐ restore the original value. 6 Right/left – and up/down buttons: Used for navigation up and down and to the right and left in the menu tree.
i.4.2 Pipe connections Connection pipes on heating‐ and cooling coils are provided with external thread. Drainage outlets on drip trays are provided with external thread. i.4.3 Possibility of extracting components from the unit Pipes and cables must not obstruct the inspection doors and components which can be extracted from the unit. Potential components for extraction are filters, fans and rotary heat exchanger. i.4.4 Pipe connections to batteries i.4.4.
To protect against frost a temperature sensor for the transmission of an analog signal to the controller is placed in a pipe on the collection pipe for return water. The sensor must be fitted water tight with a cap in the pipe before water under pressure is in the battery. The pipe for the sensor is soldered on the collection pipe and it is important to hold contra on the pipe, when the cap is tightened. Battery seen from above.
i.4.4.3.3 Valve motor and valve for heating The valve and valve motor are not installed. 2‐way or 3‐way valve is available. i.4.4.3.4 Valve motor and valve for cooling TThe valve and valve motor are not installed. 2‐way or 3‐way valve is available. i.4.5 Draining condensate water Drip trays for collection of condensate water are installed under plate heat exchanger and cooling coil. Each drip tray is provided with a drainage outlet. A water trap is always necessary.
i.4.7 Draining condensate water from cooling battery If the cooling battery and the drip tray are placed in the unit where negative pressure (underpressure) occurs, the closing level of the water trap must be estimated correctly. See the above‐mentioned information in section i.4.6 – Draining condensate water from the plate heat exchanger.
j. Installation and assembly instructions for reduction of noise and vibration emissions Due to the design and construction of the units the (A) weighed sound pressure level from fans and other components do not exceed 70 dB (A) outside the units. Data about sound in annex 2. Installation of the units on springs will reduce the transmission of noise and vibrations to the building. Systemair does not deliver springs for this purpose.
CO2 sensor Control panel Humidifier E‐Tool software for fast communication with the Corrigo controller Other k.3 Documentation is available for download from https://techdoc.systemair.dk Your local Systemair company is able to provide the data. k.4 Start‐up by installer All protection and safety measures must be met before start‐up of the unit. The mains supply voltage must also be checked too. The mains supply voltage must be measured at the supply terminals in the cabinet. k.4.
K.6 Description of functions K.6.1 Remote control k.6.1.1 Communication to BMS systems with MODBUS The controller has been prepared for communication via RS485 communication port to a MODBUS based BMS system (Building Management System). The controller can work as a stand‐alone system without any support from other controllers. k.6.1.2 Communication to BMS systems with LON The controller has been prepared for communication via LON communication port to BMS systems (Building Management Systems).
k.6.7 Fire alarm function k.6.7.1 External fire signal that indicate block or run The unit is available without components for this function. The controller is as standard configured for ordinary running when the contact is closed (NC). By open contacts the fans stop and the dampers close. If disconnected, fire is indicated and the unit will stop until the signal is re‐connected. On the site qualified technicians are able to change the configuration. k.6.7.
k.6.9.2 Control of heating capacity connected to unit without Systemair control system Electrical heater installed with separate controller beside the heater. The separate controller is designed for capacity conversion of the 0‐10 V control signal from the main control system. The heating capacity is adapted in steps. The electric heater is not supplied from the air handling unit cabinet as the cabinet is not designed to supply the heater with power.
k.6.12 Temperature sensors Four sensors are always delivered with each unit. See below where the sensors are placed; 1 sensor in the extract air, installed inside the unit 1 sensor in the outdoor air, installed inside the unit before the supply air filter on the cold side of the heat exchanger 1 sensor in the supply air to be placed in the supply air duct by the installer 1 sensor in the exhaust, installed inside the unit k.6.
k.6.19 Free cooling A temperature sensor has been installed inside the unit in the outdoor air entrance. If the outdoor temperature after midnight is below the room temperature set point and the actual average room temperature is above the set point temperature, the fans start during the summer to cool down the building during night hours. k.6.20 Alarm signal By alarm there are 24 V DC on terminals in the cabinet. Lamps and cables are not available from Systemair. k.6.
l.2.1 Risk caused by surfaces, edges and corners Hazards/dangerous area: Sharp edges on plates might occur inside the machines as well as sharp edges on frames of dampers. No sharp edges on the outside of the units. Dangerous incident: Cut fingers/hands. Claim for reduction of danger: Risk only exists during maintenance and cleaning. This takes place at least once every year. Use of gloves and helmet is described in this manual.
l.6 Filters type DVG – DVF l.6.1 Risk caused by missing change of filters Hazards/dangerous area: Missing change of filters and missing maintenance decrease the capacity and final consequence will be breakdown. Dangerous incident: By extensive lack of of filter change and maintenance the machine can break down. Claim for reduction of danger: In the manual is the method and schedule for change of filters and maintenance specified. l.6.
l.7.3 Risk of rotating impeller caused by stack effect (chimney effect). Hazards/dangerous area: On special occasions stack effect – also called chimney effect – in the ducts create airflows that drives the impellers by turned off motors. Dangerous incident: Injury of fingers, hands and arms. Claim for reduction of danger: Eliminate this airflow for supply air and exhaust air by dampers with spring return motors for automatic closing of the dampers by turned off fan motors and by power failure. l.
Installer and user must be aware of the fact that lightning makes a risk that requires installation of overvoltage protection devices to lead the lightning overvoltage to an earth lead on a safe way. The need for overvoltage protection devices depend on where the unit is placed in and on the building. Installer and user must take care of this according to local statutory requirements. Overvoltage protection devices are also described in section i.3.3.2 of this manual m.
o.2 Transport of section with heat pump unit During transportation, the unit section – DVU ‐ must always be in the upright position or tilted less than 30˚. If it is necessary to tilt the unit more than 30˚, the suction pipe of the compressor must point upwards to prevent the escape of oil from the compressor sump. o.
Check that the automatic circuit breaker marked F5 is still switched on because the lamps inside the unit, and only those lamps, are connected to this switch. Switch on the lamps for light during the maintenance activities. Use the start‐up procedure described in section k, when the maintenance activities are completed.
r.2 Recommended maintenance intervals. Function Maintenance Unit casing Cleaning of the unit casing. Control of rubber seals on doors and between sections. Control of filters. Change the filters when maximum pressure is exceeded. To maintain the calculated SFPv values, filters with similar performance must replace the factory‐mounted filters. Start pressures of factory‐mounted filters appear from.
Function Maintenance Dampers Test the operation. Visual inspection of seals and tightness when closed. Check the dirt accumulation and clean, if needed. Coils may only be cleaned by gentle vacuum cleaning or by gentle blowing of compressed air. Coils may only be cleaned by high‐pressure water if it is one of the very few special batteries that are ordered and built for this. Bleeding, if needed. Test of frost protection sequence Test of cirkulation pump Check dirt accumulation and clean, if needed.
r.3. Filters – always replace filters with new filters with the same characteristics to maintain SFP value Filters in supply air and in extract air always have the same sizes of frames and the number of filters for supply air and extract air are always the same. REMEMBER to order filters for supply air as well as for extract air.
r.3.1 Bag filters – the number of filters and the sizes of the frames Size of air handling unit Numbers of filters and sizes of frames (Width x Height) in mm.
r.3.
r.3.3 Bag filters Release the bag filter cells by activating the handles and pull out the filter cells of the unit casing. The frame profiles are to be cleaned and all seals checked for damage. The handles and locking guide rails are also to be checked to ensure that they can operate unobstructed. The new filter bags must be pushed carefully into the unit in order to ensure that they are sealed properly.
r.5 Other functions to maintain r.5.1 The unit The unit should be cleaned once a year when operating with normal air quality for comfort ventilation with no special hygiene requirements. To clean the unit, dry it off with a dry cloth, or use water mixed with a non‐corrosive cleaning medium. Any corrosion i.e. at the filters should be cleaned off immediately, and the surface treated.
r.5.3 Rotary heat exchanger DVC r.5.3.1 Rotor The rotor is to be checked at least once a year to ensure that it can turn freely and easily. This can be done by removing the belt drive at the motor and then turning the rotor manually with a hand on the peripheral rotor casing. At the same time the brush seals are to be checked for damage. The bearings are factory lubricated and do not require any service lubrication. During operation the rotor can become dirty.
If there is dust on the edges of the plates, remove it with a soft brush. If grease or other such substances are present, then the edges must be washed using grease dissolving detergents. r.5.4.1 By‐pass damper The damper blades are fitted with synthetic bearings requiring no lubrication. Each damper blade is connected by a pivoting system. The steel rods and brass bushes do not require lubrication.
r.5.6 Heating coil DVH, cooling coil DVK and change over coil DVHK After an extended running period (normally a few years) dust particles can accumulate on the surface of the coil. This can reduce the efficiency of the coil. Cleaning must be carried out with the utmost care to ensure that the coil fins are not damaged. The piping system must be vented once a year as air in the system can significantly reduce the capacity of the coil. r.5.6.
r.5.8 Silencer DVD During operation dust particles can accumulate on the surface of the baffles. Silencers that are designed for dry and wet cleaning are fitted with baffles that can be extracted from the unit casing. Large inspection doors give access to easily extraction of the baffles. Baffles designed for dry cleaning can be cleaned using a soft brush or they can be vacuum cleaned. Baffles designed for wet cleaning can be washed down using a soft brush and soapy water.
r.5.10 Heat pump unit – DVU‐HP Mandatory annual control must be done by certified technicians from a certified company. See further description in annex 10 and 11.
s. Instructions designed to enable adjustment and maintenance to be carried out safely, including the protective measures that should be taken during these operations s.1. Protective measures and additional protective measures Adjustment and maintenance must be done by skilled technicians – usually based on service contracts for some years or long‐term ESCO contracts. The units are provided with guards to avoid unintended hazards and injury because of rotating parts in the unit.
s.1.3 Personal protective equipment for maintenance staff – health and safety Use the below‐mentioned personal protective equipment for maintenance: Cut‐resistant gloves for protection against injury from sharp metal plate edges. Use CE‐marked gloves for this purpose. Helmet Particulate respirator – maintenance free including foam face‐seal and adjustable pre‐threaded headbands – for replacing filters. Padlock for locking the above mentioned automatic circuit breakers. Permanent magnet motor.
Annex for the User Manual Air Handling Units Danvent DV With control system Version 1.01.
Overview of annexes Annexes 1, 2, 3, 13, 14, 16 and 17 are enclosed in a separate cover. Annex 1 Declaration of conformity with unique production number Printed on separate page and delivered with every unit. Enclosed in separate cover. Annex 2 Technical data – unique data for every unit Printed on separate pages and delivered with every unit. Enclosed in separate cover. Annex 3 spare part lists Printed on separate pages but not delivered with every unit. Available on demand.
Annex 11 Menu for internal controller in the heat pump unit Annex 12 Connection of fan motor and set‐up manual for Danfoss VLT FC101 frequency converter Annex 13 Commissioning protocol – proposal (receipt for hand‐over) Printed on separate pages and delivered with every unit. Enclosed in separate cover Annex 14 Report with data from the final functional test on the Systemair factory Printed on separate pages and delivered with every unit. Enclosed in separate cover.
Annex 4.
4.
4.
4.
Annex 5.
5.
5.
5.
Annex 6.
6.
6.
6.
Annex 7.
7.
7.
7.
Annex 8. Installation of steel roof in the sizes 10‐150 8.1 Overview Mount rails A1, B2, C3, D4, E5 on the unit for support of trapezoidal roof plates (mount also rails Y and Z on units of the size 30 and on units that are larger than size 30 longitudinally at the centre‐ line of the units). Place foam bands – P – on the horizontal rails A1, B2, C3 and D4 for support of roof plates.
sealant to achieve the tightest connection between rails and unit to prevent rainwater from passing under the rails and into the unit. Mount the rails A1 and B2 on the front side (the side with the inspection doors) – use the simple self‐drilling screws without the sealing washer – see the illustration of the screw below. Note: Rail B2 fits into the rail A1, and this offers the advantage that the rail B2 can be slid inside the rail A1 to adjust the length of rail B2 accurately to the length of the unit.
Note: Rail B2 fits into the rail A1, and this offers the advantage that the rail B2 can be slid inside the rail A1 to adjust the length of rail B2 accurately to the length of the unit. In this way it is not necessary to spend time and effort cutting the rail B2. Mount the lower rails C3 and D4 on the back side of the unit. Note: Rail D4 fits into the rail C3, and this offers the advantage that the rail D4 can be slid inside the rail C3 to adjust the length of rail D4 accurately to the length of the unit.
The unit is delivered with 2 similar overhang profiles ‐ G1 and G5 ‐ one for each end of the roof. Mount one of the 2 roof overhang profiles – G on a trapezoidal roof plate. Use the self drilling, painted screws with sealing washers ‐ W ‐ see the illustration. Note: Foam bands ‐ P – are necessary between the overhang profile G1 and the roof plate F1. See the illustration. Self‐drilling, painted screws supplied with sealing washer for the mounting of the trapezoidal plate to the roof overhang profile.
AHU length AL Roof length RL AHU length AL Roof length RL AHU length AL Roof length RL 1670 – 1870 2100 4568 – 4768 4970 7466 – 7666 7840 1877 – 2077 2305 4775 – 4975 5175 7673 – 7873 8045 2084 – 2284 2510 4982 – 5182 5380 7880 – 8080 8250 2291 – 2491 2715 5189 – 5389 5585 8087 – 8287 8455 2498 – 2698 2920 5396 – 5596 5790 8294 – 8494 8660 2705 – 2905 3125 5603 – 5803 5995 8501 – 8701 8865 2912 – 3112 3330 5810 – 6010 6200 8708 – 8908 9070 3119 – 3319 3535 6
8.1.5 Foam bands between rails and roof plates – mount roof plates. Place foam bands P between profiles A1, B2, C3, D4 and roof plates. The trapezoidal roof plates are mounted with the self‐drilling, painted screws supplied with sealing washer. 8.1.6 Foam bands between roof plates Mount the self‐adhesive foam band – O ‐ on the underlapping rib for water resistant and effective sealing due to the small slope of the roof. 8.1.
8.1.9 Mount side profiles and corners along the edges of the roof to protect persons Profiles N and O with the rectangular holes are for the long and lower side of the roof because rain can escape through the holes. Mount the profiles type N first and the profile O last because the profile O goes over the profile N. Mounted in this order, the profile O can match the end of the roof and the surplus length of the profile O will just cover part of the previous profile N.
8—8
Annex 9. Speed control for rotor and assembly of divided rotor 9.1 Speed control The cabinet with the speed control system for the rotor is installed behind the inspection door in the rotor section. The cabinet contains the speed controller with all components, terminal blocks, LED displaying the operation mode, the dual position DIP switch with 8 sliding levers for programming the rotor motor signal and a button for the activation of the test mode.
The factory sets the positions of the 8 DIP switch levers for the maximum of 20 revolutions per minute for sorption exchangers. The position of each DIP switch lever is shown below.
Restart of rotor: ‐ Switch off power and switch on power again or ‐ Press the test button inside the cabinet Test of motor by checking the resistance in all 3 windings Motor sizes 90TYD‐S214‐M 120TYD‐S214‐M 120TYD‐S214‐L Ohm 40Ω 18Ω 10Ω Setting of constant speed: ‐ Set DIP switch 4 in position – ON, and the revolutions are controlled by the adjustable potentiometer on the board.
9.1.
Connection of cables to the terminals on the board Terminal Connection 1 Earth ‐ supply 2 Earth ‐ supply 3 Fase – supply 4 Neutral – supply 5 7 Rotor turns upwards seen from inspection side. Terminal 5 = wire 1 Terminal 6 = wire 2 Terminal 7 = wire 3 8 Earth for rotor motor Test Set DIP switch 4 in position – ON – and press the button for test. The signal is controlled by the potentiometer at constant speed and not by any signal from the control system.
9.
9—7
A1 Size DV 60 DV 80 DV 100 DV 120 DV 150 A1 Quantity 4 4 4 4 4 Length (mm) 1014 1164 1314 1464 1614 9—8
B1 B5 B4 B2 B3 Size DV 150 Size DV 60 DV 80 DV 100 DV 120 DV 150 B1 Quantity 1 1 1 1 1 # 10122310 10122610 10122710 10122810 10122910 B2 Quantity ‐ 4 4 4 4 Size DV 60 DV 80 DV 100 DV 120 DV 150 # ‐ 11200400 11200410 12100410 11200420 A 2170 2320 2520 2890 3040 B3 Quantity ‐ 4 4 4 4 C 520 588 588 558 558 # ‐ 21000200 21000210 21000230 21000220 B5 Number # 2 12100510 B4 Quantity 1 1 1 1 1 # 10722310 10722610 10722710 10722810 10722910 D 2240 2540 2840 3140 3440 9—9
9.3 Assemble divided rotor from Hoval Enventus for DV 60, DV 80 and DV 100 9.3.
9.3.2 Lifting instruction WARNING! RISK OF CRUSHING! To ensure that the lifting of the heat exchanger takes place in a safe manner, and to avoid personal injury and damage to the heat exchanger, we refer to the following instructions. The Hoval Enventus product warranty applies only if the following instructions are followed.
9.3.3 Installation During installation, make sure that the exchanger stands flat so that the rotor is not “at an angle” in the casing. CSD 290 mm 290 mm 9.3.4 Installation of radial walls Uncontrolled movement of radial walls may cause serious injury. Secure the radial walls carefully while working. Boards can be used to secure them.
9.3.5 Measurement. The hub with radial walls must be aligned both vertically and horizontally with the casing. If measurement indicates that there are discrepancies, the radial walls, and possibly also the hub, will need to be adjusted. Start measuring at the upper radial wall. Measure the distances A and B between the radial walls and the casing at points 1, 2, 3 and 4. Measure similar points on the next radial wall.
9.3.6 Installation of rotor segment and periphery plates. . Uncontrolled movement of radial walls and segments may cause serious injury. Secure the radial walls and segments carefully while working. Use a rope or strap with a pulley for controlled rotation.
Make sure that the upper and lower edges of the segment are located within the bent edges of the radial walls. Tap gently with a rubber mallet to ensure that the segment is in the right position. 9.3.7 Installation, first periphery plate Position the first periphery plate. The side with a hole must face up. See figure A. Insert a bolt in the hole at the top edge of the periphery plate. See figure A. Do not tighten. Insert a bolt in the groove at the lower edge of the periphery plate.
9.3.8 Installation of next segment Rotate the hub, radial walls and segment in order to facilitate the positioning of the next segment. Use a pulley with a rope or strap for controlled rotation.
9.3.9 Installation, next periphery plate. Position the second periphery plate. The side with a hole must face up. See figure A. Insert a bolt in the hole at the top edge of the periphery plate. See figure A. Do not tighten. The lower edge of the second periphery plate must overlap the first periphery plate and be secured using the bolt installed previously. See figure B. Tighten the bolt at the overlap. See figure B. A B Fasten the periphery plates together with a clamp bolt. Do not tighten.
9.3.10 Preparation of segments and periphery plates The periphery plates must be mounted together for preparation of segments and periphery plates. If a standard bolt is insufficient for bringing together the first and last periphery plates, a threaded rod can be used as described below. Position the threaded rod and nut. Tighten until an overlap is achieved. Tighten the bolt in the overlap. Replace the threaded rod with clamp bolts.
9—19
9.4 Installation of motor that turns rotor and sensor for rotation Installation of rotor motor and sensor for control of rotation in DVC module after assembly of divided rotor Fig.
Fig.2 Fig. 1, 2 and 6 By delivery of a DVC module with divided rotor, the motor is installed before delivery to the customer. Fig. 2 Fig.3 Fig.4 Fig.5 The drive belt must be placed around the rotor and the ideal distance is 9 cm from the 2 sides of the rotor. The rotors are always 20 cm thick. The distance to the drive belt from a side of the rotor must be between 9–11 cm. from the 2 sides of the rotor. Fig.6 Fig.
Fig.7 Fig. 7 and 8 Sensor for control of rotation must be installed by the installer. Distance must be 1‐4 mm between sensor and rotor. Check that the brackets which are used for the assembly of the rotor segments do not hit the sensor. Fig.8 1 ‐ 4mm Fig.9 Fig. 9 Pay attention to the heights of the brackets which are used for the assembly of the rotor segments. Please turn the rotor by hand in order to verify that the sensor will not be hit by the brackets.
Annex 10. Reversible heat pump for cooling and heating 10.1 DVU‐HP section (reversible heat pump unit) The air handling unit section – DVU‐HP – is a separate section in the air handling unit, containing a complete stand‐alone reversible heat pump system (heating and cooling). If the air handling unit was delivered with this section, a separate manual about the heat pump was enclosed in the separate cover.
Annex 11. Menu for internal controller in the DVU‐HP If the air handling unit was delivered with this section, a separate manual about the heat pump was enclosed in the separate cover.
Annex 12. Connection of fan motor and set‐up for frekv. conv. 12.1 Connection of fan motor Delta connection is shown to the left, and star connection is shown to the right.
12.2 Set‐up for Danfoss FC101 for DV‐units with AC motors SETUP IS DONE IN FACTORY BEFORE DELIVERY To reload Systemair factory settings from the control panel: 0‐50: LCP Copy: [2] Systemair factory set‐up is based on Danfoss initialization. 14‐22: Operation mode: [2] Initialisation (Danfoss Initialisation) Turn power off and on. Systemair factory set‐up: 0‐01: Language selection: 1‐03: Torque characteristic: Single fan: [3] Auto‐Energy optim.
12—3
12.3 AC‐fan operation without thermistor for Danfoss FC101 Systemair factory set‐up is based on Danfoss initialization. 14‐22: Operation mode: [2] Initialisation (Danfoss Initialisation) Turn power off and on. Systemair factory set‐up: 0‐01: Language selection: 1‐03: Torque characteristic: 1‐20: Motor power: 1‐24: Motor Current: 1‐25: Motor Nominal Speed: 1‐29: Automatic motor adption (AMA): 1‐42: Motor Cable Length: 1‐50: Motor Magnetisation at zero speed.: 1‐52: Min.
12.4 Set‐up Danfoss FC101 for DV‐units with PM motors SETUP IS DONE IN FACTORY BEFORE DELIVERY To reload Systemair factory settings from the control panel: 0‐50: LCP Copy: [2] Systemair factory set‐up is based on Danfoss initialization. 14‐22: Operation mode: [2] Initialisation (Danfoss Initialisation) Turn power off and on.
Schedule for PM motor parameters Menu: 3‐41 3‐42 1‐24 1‐25 1‐26 1‐30 1‐37 1‐39 1‐40 Motor type Ramp up Ramp down Poles 20 Nm Name plate 2,0 mH (Lf‐0) 30 Motor RPM rated 3800 Ohm (Rf‐0) HPS 71 3800 18 Amp name plate 1,9 3,900 11,75 6 Bemf @ 1000 67 HPS 71 3700 28 30 20 3,0 3700 3,6 2,100 8,25 6 HPS 71 3300 18 30 20 1,9 3300 2,6 6,250 19,25 HPS 71 3200 30 30 20 3,2 3200 4,2 2,000 HPS 71 2900 21 30 20 2,4 2900 3,3 HPS 71 2800 40 30 20 4,1 2800 HPS 71
Frequency converter is always necessary for the control of each PM motor 12—7
12.5 Installation ECblue 12.5.1 Connection 4 Input 0...10 V 5 PWM input, f = 1...10 kHz For ECblue 3 ~ types and when connecting 1 ~ types between two outer conductors, only all-current sensitive fault current circuit breakers (type B) are allowed ( EN 50 178, Art. 5.2).
Residual‐current‐operated protective devices Terminal Function / connection L1, N, PE Mains connection for 1 ~ types (observe the line voltage indicated rating plate). L1, L2, L3, PE Mains connection for 3 ~ types (observe the line voltage indicated rating plate). 11, 14 Relay output “K1” for fault indication.* • For operation the relay is energized, and “14” are bridged. For fault the relay Diagnostics / faults).
LED Code Relays K1* Cause OFF de-energized, 11 - 14 interrupted No line voltage ON energized, 11 - 14 bridged Normal operation without fault 1x energized, 11 - 14 bridged No enable = OFF 2x energized, 11 - 14 bridged Temperature management active 3x de-energized, 11 - 14 interrupted HALL-IC error 4x de-energized, 11 - 14 interrupted Line failure (only for 3 ~ types) 5x de-energized, 11 - 14 interrupted Motor blocked 6x de-energized, 11 - 14 interrupted IGBT Fault 7x de-energized, 11 -
Annex 13.
Annex 14.
Annex 15. Short description of main components in control system 15.1 DV units delivered in several sections This model of the DV unit has an integrated control system and depending on the size of the unit, the cabinet is installed on the unit or on the front of the unit. The 2 controllers ‐ Systemair E28–2 port controller and a Systemair E28 expansion ‐ both controllers are mounted in the cabinet, and all electrical connections between cabinet and components in the unit are installed.
15—2
Annex 16.
Systemair A/S Ved Milepælen 7 DK-8361 Hasselager Tel. +45 87 38 75 00 mail@systemair.dk www.systemair.dk Systemair A/S • November 2017 Part number of this manual 90925372 - Version 1.01.