Jet fan - IV Smart EC, IV Smart EC Modbus Installation and Operating Instructions EN
© Copyright Systemair All rights reserved Systemair reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.
Contents 1 2 3 4 5 6 7 8 General information.................................................................... 4 1.1 Notice symbols............................................................... 4 1.1.1 Instruction symbols........................................................ 4 Safety notes................................................................................. 4 2.1 Personnel......................................................................... 5 2.2 Personal protective equipment.....
| IV Smart EC / Modbus 1 General information 1.1 Notice Symbols Danger Direct hazard Failure to comply with this warning will lead directly to death or serious injury. Warning Potential hazard Failure to comply with this warning may lead to death or serious injury. Caution Hazard with a low risk Failure to comply with this warning may lead to moderate injuries. Important Hazard with risk of damage to objects Failure to comply with this warning will lead to damage to objects.
IV Smart EC / Modbus i | 5 Note: The operator is responsible for ensuring that personnel are instructed and have understood the contents of the operating instructions. If something is unclear, please contact Systemair or its representative. 2.1 Personnel The fan may only be used by qualified, instructed and trained personnel. The persons must know the relevant safety directives in order to recognize and to avoid risks.
| IV Smart EC / Modbus Warning Suspended loads. ◊ Wear protective equipment during all work in the vicinity of the fan, details see 2.2 Personal protective equipment, page 5. ◊ Do not walk under suspended loads. ◊ Make sure that there is nobody under a suspended load. 4.2 Delivery Each fan leaves Systemair in proper mechanical and electrical condition. The fan should remain in the original packaging until the final delivery to the installation site. 4.2.
IV Smart EC / Modbus | 7 ◊ Do not stack the fans on top of one another after uncrating. ◊ Use hoisting and/or lifting equipment that is suitable for the weight to be vertically moved. Preconditions: ◊ Store the devices in a clean, dry and vibration-free environment. ◊ Storage temperature should be between –20°C and 60°C. 5 Description 5.
| IV Smart EC / Modbus 5.4 Dimensions 6-13/16 8 9-7/8 3-7/8 6-5/8 5-1/2 5/16 29-15/16 19-7/8 2-7/8 2-9/16 5-7/8 5-5/8 31-1/2 27-13/16 6 22-3/8 Nameplate The following nameplate is shown as an example of formatting. The shown image is for the IV Smart EC model specifically. i 6.1 Note: Variation in the current draw of an Electronically Commutated Motor can be expected, which is dependent on the line impedance.
IV Smart EC / Modbus | 7 Installation 7.1 Safety information Warning Danger from falling fan or fan parts. Check the surface before installation for load bearing capacity. ◊ Installation may only be carried out by adequately qualified persons, see Table 1: Qualifications ◊ Wear protective equipment during all work in the vicinity of the fan, see 2.2 Personal protective equipment. ◊ Abide by the system-related conditions and requirements of the system manufacturer or plant constructor.
| IV Smart EC / Modbus Mounting to concrete: ◊ If using Post-Installed Mechanical Anchors (expansion or undercut), anchors must be tested and evaluated to ACI 355.2 requirements. ◊ If using Post-Installed Mechanical Anchors (Adhesive), anchors must be tested and evaluated to ACI 355.4 requirements.
IV Smart EC / Modbus 8 Electrical connection 8.1 Safety information Warning Danger from electrical voltage. ◊ Observe the 5 rules of electrical safety, see 2.3 Five rules of electrical safety. ◊ Prevent the ingress of water into the connection box. ◊ The electrical connection must be carried out by qualified persons, see Table 1: Qualifications. ◊ Wear protective equipment during all work in the vicinity of the fan, see 2.2 Personal protective equipment.
| IV Smart EC / Modbus 8.4 Motor Controls ◊ Each fan contains two EC motors that have their own wire leads landed in the electrical box of the fan. ◊ Each fan type is speed controlled differently. ◊ The IV Smart EC fan is controlled via an analog PWM or 0-10V signal. ◊ The IV Smart EC Modbus is controlled by digital Modbus communications. Each motor must be individually addressed on the job site.
Control Options IV Smart EC 8.5.
| IV Smart EC / Modbus 8.5.3 IV Smart EC Modbus Connection Diagram ◊ All connections shall be made using the supplied quick connect lever-action or push-to-connect terminals. The left side of the below image is the field wiring side. Line voltage (L1, L2, Ground): • Field power connections are to be made in the electrical box • The grounding terminal is electrically connected to the unit through the DIN rail.
IV Smart EC / Modbus 8.6 | 15 Residual current circuit breaker ◊ All-current-sensitive residual current circuit breakers are required for use in alternating-current systems with 50/60 Hz, in combination with electronic devices such as EC motors, frequency converters or uninterruptible power supplies (UPS). 9 Commissioning 9.1 Safety information ◊ Commissioning may only be carried out by adequately qualified persons, see Table 1: Qualifications.
| IV Smart EC / Modbus ◊ Operation may only be carried out by adequately qualified persons, see Table 1: Qualifications. ◊ The device may only be operated by people who understand the function and risks and can act accordingly. ◊ Abide by the system-related conditions and requirements of the system manufacturer or plant constructor. 10.2 Preconditions ◊ Ensure access only to persons who can safely handle the device.
IV Smart EC / Modbus | 17 11.3 Maintenance As set forth in the Limited Warranty, warranty claims can only be made if maintenance work is carried out correctly and written evidence thereof is provided. We recommend regular maintenance intervals to ensure continuous fan operation. These maintenance intervals are specified in the “Activities” table below. In addition, the operator must carry out follow-up activities such as cleaning, replacing defective components or other corrective measures.
| IV Smart EC / Modbus 11.4 Variable speed fans Important Varying speeds may lead to increased vibrations dependent on the support structure. ◊ Pay particular attention to damage from vibrations. ◊ After commissioning, start with shorter maintenance intervals. ◊ If no damage occurs, adjust the maintenance intervals up to those stated in the operating instructions. ◊ Responsibility for gradual adaptation is with the system operator/installer. 11.
IV Smart EC / Modbus 15 | 19 Commissioning Report Please keep the completed commissioning report in a safe place. As set forth in the Limited Warranty, in the case of a warranty claim, this report can be requested by Systemair. Fan Description: Article no.: Manufacturing order no.: Installer Company: Contact person: Company address: Tel. no.: Email: Operator (Place of installation) Company: Contact person: Company address: Tel. no.
| IV Smart EC / Modbus Frequency [Hz]: Power [kW]: Fan impeller speed [rpm]: Measured data at commissioning Voltage [V]: Temp. of transported air [C]: Current l1 [A]: Impeller speed [rpm]: Current L2 [A] Air volume [CFM]: Current L3 [A]: Differential pressure [in.wg.
IV Smart EC / Modbus 498198 | 21
| IV Smart EC / Modbus 498198
IV Smart EC / Modbus 498198 | 23
Systemair reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications. Systemair Inc. • April, 2022 • Art.