Genius Modbus Cross Reference List Of Modbus Slave

1(3)
CrossReferenceListofModbusSlave
ToolModbusslave
ControllerGenius,trunk
Saved2017-04-2715:11
Printed2017-04-2715:19
ModbusDeviceAddress:1
TCP/IPEnabled:Yes
Coils
AddrEXOLVariableDescription
0HW_FastHeatActivatefasthotwaterheating(0=No,1=Yes)
1RegioShutDown(1)Room1:Mode(0=Active,1=Off)
2RegioShutDown(2)Room2:Mode(0=Active,1=Off)
3RegioShutDown(3)Room3:Mode(0=Active,1=Off)
4RegioShutDown(4)Room4:Mode(0=Active,1=Off)
5RegioShutDown(5)Room5:Mode(0=Active,1=Off)
6RegioShutDown(6)Room6:Mode(0=Active,1=Off)
7RegioShutDown(7)Room7:Mode(0=Active,1=Off)
8RegioShutDown(8)Room8:Mode(0=Active,1=Off)
9RegioShutDown(9)Room9:Mode(0=Active,1=Off)
10RegioShutDown(10)Room10:Mode(0=Active,1=Off)
11forcedCoolingManualcooling(0=No,1=Yes)
12HW_LegionellaActivatelegionellatreatment(0=No,1=Yes)
13HW_EmergencyModeHotwateremergencyOperation(0=No,1=Yes)
14PTC_functionPTC-funcion(0=Off,1=Yes)
15PTC_EmergencyModePTCemergencyOperation(0=No,1=Yes)
DiscreteInputs
AddrEXOLVariableDescription
1RegioUo1(1)Room1:PTC(0=Blocked,1=Normal)
2RegioUo1(2)Room2:PTC(0=Blocked,1=Normal)
3RegioUo1(3)Room3:PTC(0=Blocked,1=Normal)
4RegioUo1(4)Room4:PTC(0=Blocked,1=Normal)
5RegioUo1(5)Room5:PTC(0=Blocked,1=Normal)
6RegioUo1(6)Room6:PTC(0=Blocked,1=Normal)
7RegioUo1(7)Room7:PTC(0=Blocked,1=Normal)
8RegioUo1(8)Room8:PTC(0=Blocked,1=Normal)
9RegioUo1(9)Room9:PTC(0=Blocked,1=Normal)
10RegioUo1(10)Room10:PTC(0=Blocked,1=Normal)
11MB_Carel_OnOffHeatpumpstatus(0=Off,1=On)
12MB_Carel_ChangeOverHeatpumpmode(0=Heating,1=Cooling)
HoldingRegisters
AddrScaleEXOLVariableDescription
010FixedSetPCoolRoomsetpointcooling(22-28°C)
110SetPointRC(1)Room1:Desiredtemp
210PTC_OccSetPHeat(1)Room1:Basesetpoint(18-26°)
310RegioSetpointOffsetPos(1)Room1:Setpointadjustment(+)
410RegioSetpointOffsetNeg(1)Room1:Setpointadjustment(-)
510SetPointRC(2)Room2:Desiredtemp
610PTC_OccSetPHeat(2)Room2:Basesetpoint(18-26°)
710RegioSetpointOffsetPos(2)Room2:Setpointadjustment(+)
810RegioSetpointOffsetNeg(2)Room2:Setpointadjustment(-)
910SetPointRC(3)Room3:Desiredtemp
1010PTC_OccSetPHeat(3)Room3:Basesetpoint(18-26°)
1110RegioSetpointOffsetPos(3)Room3:Setpointadjustment(+)
1210RegioSetpointOffsetNeg(3)Room3:Setpointadjustment(-)
1310SetPointRC(4)Room4:Desiredtemp
1410PTC_OccSetPHeat(4)Room4:Basesetpoint(18-26°)