SAVE VTR 700 Service & Accessories Installation Manual GB Document in original language | · v01
© Copyright Systemair UAB All rights reserved E&OE Systemair UAB reserves the rights to change their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications. Systemair is not liable or bound by the warranty if these instructions are not adhered to during installation or service.
Contents 1 2 3 4 5 Overview ......................................................1 1.1 Warranty ..............................................1 1.2 Type label.............................................1 1.3 Disposal and recycling .............................1 Important Safety Information .............................1 2.1 Intended Use.........................................2 2.2 Admonitions .........................................2 Configuration .................................................
Overview | 1 Overview The key to proper and safe operating of the unit is to read this manual thoroughly, use the unit according to given guidelines and follow all safety requirements. 1.1 Warranty For the assertion of warranty claims, the products must be correctly connected and operated, and used in accordance with the data sheets. Further prerequisites are a completed maintenance plan with no gaps and a commissioning report. Systemair will require these in the case of a warranty claim. 1.
2 | Configuration • Do not allow children to play with the device. 2.1 Intended Use • Abide by the system-related conditions and requirements of the system manufacturer or plant constructor. • Keep all the warning signs on the device and in a legible condition. • The device is not to be used by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction.
Configuration | On and Off slider to activate or deactivate a function. White bubble — function is inactive, green bubble — function is active. Back button to return to a previous menu, located at the upper left corner Up arrow to increase a value CANCEL Button to cancel changes Down arrow to decrease a value SET/OK Buttons to confirm changes Some menus have more than one page. Touch page indicator in the top right corner to go to the next page.
4 | Configuration Icon Text Description AUTO Automatic airflow control. AUTO mode is available for selection when Demand Control, Week Schedule and/or external fan control functions are configured, otherwise AUTO mode icon won’t be visible in active user modes menu. AUTO mode activates Demand Control, Week Schedule and/or external fan control functions. Demand is available to choose as airflow setting in Week Schedule. Manual selection of airflow levels.
Configuration | Icon Text Description Configurable Digital Input 1 Configurable digital input for custom user function. Airflow levels for both fans are freely configurable. High–priority function. Configurable Digital Input 2 Configurable digital input for custom user function. Airflow levels for both fans are freely configurable. Mid–priority function. Configurable Digital Input 3 Configurable digital input for custom user function. Airflow levels for both fans are freely configurable.
6 | Configuration 3.3.2 Temperature settings Temperature can be set at SET TEMPERATURE menu accessible from the home screen by touching TEMPERATURE icon with thermometer. Default temperature value is 18°C (range 12–30°C). Use up and down arrows or a slider to change the value. Then touch the OK button to confirm changes. Temperature set point is for room air temperature, supply air temperature or for extract air temperature depending on which control mode is active.
Configuration | Use up and down arrows or a slider to change the airflow value. The airflow may be adjusted in these steps: Off/Low/Normal/High. These settings control output signals to the supply and extract fans. Important It is not recommended to set fan to Off in standard households. If manual fan stop is activated, the unit should be provided with dampers in exhaust and fresh air ducts to avoid cold draught and risk of condensation when the unit has been stopped.
8 | Configuration Icon 3.5 3.5.1 Text Description Cooling recovery Automatic cooling recovery is active when extract air temperature from apartment is lower than outdoor air temperature and there is a cooling demand (temperature setpoint is lower than outdoor air temperature). No cooling recovery with heating demand. If the outdoor air temperature is higher than then thee indoor air temperature and there is a heating demand, function Free heating is activated instead.
Configuration | 3.5.1.2 Sensors Values from sensors and load of fans (rpm). 3.5.1.3 Input Status Status of configured analog, digital and universal inputs. Connected component type and raw value (volts) is displayed. 3.5.1.4 Output Status Status of configured analog, digital and universal outputs. Connected component type and value (volts) is displayed. 3.5.1.5 Unit Version Unit model name, manufacturer number, serial number and unit software versions for Mainboard, HMI and IAM. 3.5.
10 | Configuration Alarm name Explanation Do the following Defrosting error Indicates failure of pre-heater to preheat the incoming outdoor air (in case Extra controller is configured as Preheater). Check the pre-heater reset button. Check the pre-heater cabling. Contact your installation company or place of purchase. Defrosting error may be caused by extremely low outdoor air temperatures or pre-heater failure. • Alarm stops the unit.
Configuration | Alarm name Explanation Do the following Rotor motor feedback Indicates a rotor malfunction. No feedback signal from the rotor motor for 180 seconds. If the rotating heat exchanger has stopped, check the rotor belt. Replace the belt if it is broken. If the heat exchanger is still not rotating check if the quick connector of the rotary heat exchanger motor is connected. If the alarm persists, the motor may be faulty. Contact your installation company or place of purchase.
12 | Configuration Alarm name Explanation Do the following Built-in extract air temperature sensor Indicates internal extract air temperature sensor malfunction. Active: measured temperature = 0°C Returned: measured temperature > 5°C Check that sensor is connected properly and cable is not damaged. Contact your installation company or place of purchase. Extra controller alarm Error from external device. Check if external device is connected properly and cable is not damaged.
Configuration | 3.5.3 Week Schedule The unit can be configured to operate at set airflow levels up to two time periods (00:00–23:59) on user selected days. Week Schedule is active only during AUTO mode. It is possible to activate or deactivate digital output for schedule and unscheduled periods. 3.5.3.1 Schedule Airflow Settings Touch settings icon to go to SCHEDULE AIRFLOW SETTINGS menu. In this menu set airflow level for scheduled and unscheduled periods.
14 | Configuration Set the time. Touch the START TIME or END TIME values to change time. Use arrow buttons decrease value. Confirm with OK button. and to increase or Note: Scheduled time can start but never end at midnight (00:00). The latest END TIME period is 23:59. Scheduled time cannot go to the next day. 12 or 24 hour time format can be changed in System Preferences menu. If necessary, activate second scheduled period and set up time.
Configuration | 3.5.6.1 Input Configuration of inputs Settings for analog, digital and universal input terminals on the main board and connection board, configuration of functionality. Table 1 Digital universal inputs available for selection User Modes Activation of specific user modes. Central Vacuum Cleaner Function Activation of Central vacuum cleaner function. Cooker Hood Function Activation of Cooker Hood function. External Stop Air handling unit is stopped by an external command.
16 | Configuration Table 3 Digital outputs available for selection Step Controller Y1 Heating Step Controller Y3 Cooling Step Controller Y4 Extra Controller Heater/Cooler/Extra controller control signals. Sum Alarm Fault indicating output. Outdoor-/Exhaust Air Damper Outdoor-/Exhaust air damper control signal. Secondary air Secondary air damper control. Activate Cooling Cooling mode activation signal to an external system.
Configuration | Range: 0–10 V / 2–10 V / 10–0 V / 10–2 V. Heater • Choose heater type. Each selection unlocks additional configuration options. Default setting is based on unit type. Available types: None / Electrical / Water / Change-over. • Set actuator type. Default value is 0–10 V. Range: 0–10 V / 2–10 V / 10–0 V / 10–2 V. • Set circulation pump temperature. Default setting is 10°C. This option is available if Water / Change-over heater type is selected. Range: 0–20°C. • Set circulation pump stop delay.
18 | Configuration 3.5.6.4 Control Regulation Configure how the system is controlled. Temperature Control • Configure temperature controller. Choose control mode: Available modes: Supply air temperature control / Room temperature control / Extract air temperature control Note: Room temperature control mode requires an accessory to measure room temperature. • Choose temperature unit. Default setting is Celsius. Available units: Celsius / Fahrenheit • Set P-band. Default setting is 20°C. Set I-time.
Configuration | Setting Manual RPM Pressure (VAV) Flow (CAV) External Pressure Sensors — configure sensor voltage relation to pressure. Set value at which fan alarm occurs. Default setting is None - - Supply air fan control sensor: Pressure at 0V: 0-500 Pa, default setting 0 Pa Pressure at 10V: 0-2500 Pa, default setting 500 Pa. Extract air fan control sensor: Pressure at 0V: 0-500 Pa, default setting 0 Pa.
20 | Configuration Setpoint, default setting is 45% humidity. Range: 1–100% RH. Set P-band, default setting is 4g/kg. Range: 1–100g/kg. Set I-time, default setting is Off. Range: Off/1–120 sec. Defrosting Control Note: Setting is available if heat exchanger type is set as Plate. The unit is equipped with an automatic defrost function that is activated when there is risk of icing in the area around the heat exchanger. • Select defrosting mode. Default setting is Normal.
Configuration | Fig. 4 Example speed for supply and extract air 4. Use this procedure to find fan speed for all airflow levels: MINIMUM LEVEL, LOW LEVEL, NORMAL LEVEL, HIGH LEVEL, MAXIMUM LEVEL. 5. Finally in the control panel go to Service menu, enter the password, then go to Control Regulation → Fan Control. Choose RPM as airflow type and in sub-menu Airflow Level Settings enter calculated fan speed values for each level. 3.5.6.5 User Modes Set airflow level, duration and offset for each user mode.
22 | Configuration Connecting the IAM to wireless network 1. If your wireless router does not support WPS, Wi-Fi connection should be set up manually. Therefore you need to find Wi-Fi name and add password using control panel. 2. In control panel go to Service -> Communication -> WLAN settings menu. 3. Press Scan for networks button. IAM will search for available Wi-Fi networks (should not take longer than one minute). 4.
Service | 3.5.7 Help FAQ, troubleshooting of alarms, contact information for support is provided in this menu. • Service partner — information about service partner. • Company • Telephone • Homepage • Email • User modes— detailed description of all user modes. • Functions— detailed description of different user functions. • Alarms— detailed description of all alarms. • Troubleshooting— information about all different possible malfunctions. 4 Service 4.
24 | Service 4.3 Internal Components Fig. 5 Components Position Description 1 Relative humidity sensor 2 External connections 3 Supply air sensor 4 Overheat protection sensor 5 Internal electrical re-heater 6 Extract air filter 7 Main circuit board 8 Supply air fan 9 Rotor motor and belt pulley 10 Rotating heat exchanger 11 Heat exchanger drive belt 12 Rotor sensor 13 Supply air filter 14 Extract air fan 15 Outdoor air sensor 16 Extract air sensor 4.3.
Service | 4.3.1.2 Filters The air filter captures dust, mold, pollen and other particulate matter. The filters need to be replaced when polluted. New sets of filters can be acquired from your installer or wholesaler. 4.3.1.3 Heat exchanger SAVE VTR 700 is equipped with a rotating heat exchanger. Required supply air temperature is therefore normally maintained without adding additional heat. The heat exchanger is removable for cleaning and maintenance, see “User Manual” for more information. 4.3.1.
26 | Service Fig.
Service | Fig. 8 External connection box and board Position Description 1 Connection to the main circuit board 2 Connection for external control panel (HMI) or Internet access module (IAM) 3 Modbus RS485 connection AI6–7 Freely configurable Analog input. None/Input type selection in HMI. DO1–4 Freely configurable digital output.
28 | Accessories 5. Check the airflow settings in the control panel. 6. Check week schedule settings (chapter 3.5.3). 7. Check filters. Is change of filters required? 8. Check diffusers/louvres. Is cleaning of diffusers/louvres required? 9. Check fans and heat exchange block. Is cleaning required? 10.Check if the buildings air intake and roof unit (exhaust) have been clogged. 11.Check visible duct runs for damage and/or build up of dust/pollution. 12.Check diffuser/louvre openings.
Accessories | 5.1.
30 | Accessories Note: The internet access module uses TCP port 8989. Make sure it is not blocked. Description A. Connect the Internet Access Module (IAM) to the Connection Board (CB) with included RJ10 cable. B. Power up the IAM with included power supply cable and adapter (230 V~). C. Enable access to the internet. Three options are available: • C1 — Activate WPS function on your router (if available) and press the button on the Internet Access Module for 5 seconds.
Accessories | • IAQ — indoor air quality sensor (CO2, RH and temperature) • CO2 — CO2 duct sensor • 1 — Outdoor air • 2 — Supply air • 3 — Extract air • 4 — Exhaust air Component/product — Article number: • Systemair-1 CO2 duct sensor — 14906 • Systemair-E CO2 sensor — 14904 • Room sensor 0-50C (temperature) — 211525 • Systemair-E CO2 RH Temperature — 211522 Installation and connection 1. Install IAQ sensor in the duct or the room depending on the transmitter type. 2.
32 | Accessories • ELH — Electrical heater • OHT — overheat protection sensor • 1 — Outdoor air • 2 — Supply air • 3 — Extract air • 4 — Exhaust air Component/product — Article number: • El. Reheater VTR 700 R 1,67kW (for right version model) — 141100 • El. Reheater VTR 700 L 1,67kW (for left version model) — 138100 Installation and connection 1 Remove cover plates from electrical connections (pos. 1) and heater (pos. 2) compartments by removing 4 screws from each plate at the front.
Accessories | Note: For more detailed information see a wiring diagram delivered with the unit. Configuration 1. Go to Service menu 2. Enter password (default 1111) 3. Go to Components menu, select Heater menu and select type as Electrical. Do advanced settings if necessary. 4. Configure overheat protection sensor. Go back to Input menu. Select ANALOG tab. Select the analog input to which the overheat protection sensor is connected.
34 | Accessories 3. Set the heater type: Components —> Extra Controller —>Extra Controller Mode —> Preheater. 4. Configure connection of the pre-heater. Go to Service menu. Select Output menu. In next menu select DIGITAL tab. Select the digital output to which the pre-heater is connected. Example if it is connected to DO3 on the connection board, then select DIGITAL OUTPUT 3 and select Step Controller Y4 Extra Controller from the output type list. 5.
Accessories | 2. Enter password (default 1111) 3. Set the heater type: Components > Extra Controller > Extra Controller Mode > Heating. 4. Configure connection of the heater. Go to Service menu. Select Output menu. In next menu select DIGITAL tab. Select the digital output to which the heater is connected. Example if it is connected to DO3 on the connection board, then select DIGITAL OUTPUT 3 and select Step Controller Y4 Extra Controller from the output type list. 5. Configure the installed sensor.
36 | Accessories Fig. 10 Water heater connections Configuration 1. Go to Service menu 2. Enter password (default 1111) 3. Activate the actuator. Go to Components menu, select Heater menu and select type as Water. Choose actuator voltage type. Do advanced settings if necessary. 4. Configure connection of the water heater. Go to Service menu. Select Output menu. In next menu select ANALOG tab. Select the analog output to which the water heater is connected.
Accessories | Installation and connection 1. Install water heater in the duct. Connect pipes, 2/3– way valve and actuator. Important Do NOT use 24V DC power output from the connection board for valve actuator. 2. Connect actuator (S) to any free analog output. Fig. 11 Water heater connections 3. The frost protection sensor (FPT) should be strapped on a surface on the return water pipe. Connect FPT sensor to any free analog input. 4.
38 | Accessories • WC — water cooling battery • SAT — supply air temperature sensor • S — valve actuator • 1 — Outdoor air • 2 — Supply air • 3 — Extract air • 4 — Exhaust air Component/product — Article number: • CWK 250-3-2,5 Duct cooler,circ — 30024 • RVAZ4 24A Actuator 0-10V (S) — 9862 • ZTV 15-1,6 2-way valve — 9824 • ZTR 15-1,6 valve 3-way — 9673 • Duct sensor -30-70C (SAT) — 211524 • Transformer 24V — 202692 Installation and connection 1. Install a duct water cooler in the duct.
Accessories | • GHT — Ground heat exchanger • ECT — extra controller temperature sensor • OAT — outdoor air duct temperature sensor • RL — relay • 1 — Outdoor air • 2 — Supply air • 3 — Extract air • 4 — Exhaust air Installation and connection 1. Install the ground heat exchanger (GE) at least 100 mm distance from the unit in the outdoor air duct. Relay (RL) is used to control the ground heat exchanger. Connect the relay to any free digital output on the connection board (CB). 2.
40 | Accessories • WH/WC — change-over coil • FPT — frost protection sensor (optional) • SAT — supply air temperature sensor • THS — thermostat for sensing if the temperature of heating/cooling fluid in the system is right (optional) • HP — heat pump (or other device for heating and cooling) • CWP — water pump • RL — relay • 1 — Outdoor air • 2 — Supply air • 3 — Extract air • 4 — Exhaust air Component/product — Article number: • Duct sensor -30-70C (SAT) — 211524 • Surface sensor -30-150C (FPT) — 211523 •
Accessories | 1. Go to Service menu 2. Enter password (default 1111) 3. Go to Components menu, select Heater menu and select type as Change-over. Do advanced settings if necessary. Go to Components menu, select Cooler menu and select type as Change-over. Do advanced settings if necessary. 4. Configure control signal of the heat pump or similar device. Go to Service menu. Select Output menu. In next menu select ANALOG tab. Select the analog output to which the control signal wire is connected.
42 | Accessories • RL — relay box • U- outdoor air damper • V — exhaust air damper • 1 — Outdoor air • 2 — Supply air • 3 — Extract air • 4 — Exhaust air Component/product — Article number: • EFD 250 + LF230 (U/V) — 6748 • TUNE-R-250-3-M4 (U/V) — 311971 • Relay kit: RMK — 153549 • Relay kit with a transformer for 24 VAC dampers: RMK–T — 153548 For all possible connection variations please see wiring diagram delivered with the relay mounting kit.
43 Accessories | 3. Configure control signal to the relay. Go to Output menu. Select DIGITAL tab. Select the digital output to which the relay is connected. Example if it is connected to DO3 on the connection board, then select DIGITAL OUTPUT 3 and select signal type as Outdoor-/Exhaust Air Damper from the output type list. 5.5.2 Pressure Guard A differential pressure switch is used to detect air pressure difference in a duct.
44 | Accessories Example if it is connected to UI1 on the connection board, then select option UNIVERSAL INPUT 1. Set signal type as Digital Input and select an option Pressure Guard from the input type list. 5.5.3 Multiple control panels Multiple control panels (up to 10) can be connected to one unit with the help of diverting plugs. A single diverting plug allows to connect two control panels.
Accessories | Address value Indication 9 Refresh mode LEDs are on 10 All LEDs are on 5.5.4 Presence detector A presence detector is used to activate one of required functions when someone is present in the room. Universal input can be easily re-configured to activate a different function. Component/product — Article number: • Presence detector/IR24 — 6995 Configuration 1. Go to Service menu 2. Enter password (default 1111) 3. Go to Input menu. Select UNIVERSAL tab. 4.
Phone +370 340 60165 Fax +370 340 60166 www.systemair.com SAVE VTR 700 · · · en_GB · 2021-05-04 · v01 Systemair UAB Linų st.