SAVE VTR 500 Installation instructions Document in original language | 254522 · v01 GB
© Copyright Systemair UAB All rights reserved E&OE Systemair UAB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications. Systemair is not liable or bound by warranty if these instructions are not adhered to during installation or service.
Contents 1 Overview ......................................................1 1.1 General Description ................................1 1.2 Warranty ..............................................1 1.3 Type label.............................................1 2 Important Safety Information .............................1 2.1 Intended Use.........................................1 2.2 Admonitions .........................................2 3 Technical Data ................................................2 3.
Overview | 1 Overview 1.1 General Description Read the instructions carefully and in its entirety. For description of advanced settings and installation of accessories see Service and Accessories Installation manual. All documents can be found in our online catalogue at www.systemair.com. 1.2 Warranty For the assertion of warranty claims, the products must be correctly connected and operated, and used in accordance with the data sheets.
2 | Technical Data • The system should operate continuously, and only be stopped for maintenance/service. • Do not connect tumble dryers to the ventilation system. • Make sure that filters are mounted before starting the unit. 2.
Technical Data | 3.1 Dimensions and Weight Fig.
4 | Technical Data Fig. 3 Dimensions and weight, R model * Water coil connections. ** Drainage. *** Height with mounting bracket. The unit weight is 85 kg. 3.
Delivery, Transport, Storage | Position Description R Right hand model (Supply air connection is situated on the right hand side of the unit viewed from the front) L Left hand model (Supply air connection panel is situated on the left hand side of the unit viewed from the front) Symbol 3.3 Description Symbol Description Supply air Outdoor air Exhaust air Extract air Installation recommendation regarding condensation 3.3.
6 | Prerequisites for Installation Important • Use the packaging exclusively as transport protection and not as a lifting aid. • Load and unload the air handling unit carefully. 4.2 Delivery/Unloading The appliance is delivered in one piece containing all necessary components, wrapped in plastic on a pallet for easy transportation. Checking delivery • Check the packaging and the air handling unit for transport damage. Any findings should be noted on the cargo manifest.
Installation | Note: The drainage connection is plugged in the bottom of the unit at delivery. To use the drainage: remove the rubber seal and connect the drainage pipe. Connect the drainage pipe to the sewer. The water can not be led straight to the sewer without a water trap. 5.
8 | Installation Make sure the mounting bracket is completely level. Follow the ventilation drawing when connecting the unit to the duct system. 6.1 Ventilation Duct Connection and Insulation Important • Always cover the ventilation ducts during construction period. • Make sure there are no loose objects or impurities inside the ducts. Install the ducts, supply air diffusers and air intake grilles as shown in the ventilation drawing.
Electrical connections | Do not install the ducts directly against structural building elements to avoid sound propagation. Use acoustic insulation and sound attenuators. Note: The type of ventilation ducts and insulation differ for each building and climate zone. If the ventilation drawing is not provided, please contact your installer or place of purchase for recommendations. 6.
10 | Electrical connections Position Description 10 Analog input 4 — Freely configurable / Overheat temperature sensor (units with heater) 11 Analog input 5 — Freely configurable 12 Digital input 1 — Rotor guard sensor (only for VSR, VTR models) 13 Digital input 2 — Freely configurable / Cooker hood (VTR 150/K unit) 14 Analog output 2 — Freely configurable / Electrical heater controller (VTC 700 unit) 15 Analog output 1 — Rotary heat exchanger control signal (for VSR, VTR type models) / Damper
Before Starting the System | 8 Before Starting the System When the installation is completed, check that: • The unit is installed in accordance with the instructions • Outdoor and exhaust air dampers and silencers are installed and that the duct system is correctly connected to the unit • All ducts are sufficiently insulated and installed according to local rules and regulations • Outdoor air intake is positioned with sufficient distance to pollution sources (kitchen ventilator exhaust, central vacuum sy
12 | Concluding Routines Set speed of supply and extract air fans for each level. When finished, review your settings. It is possible to go back to previous menus and make modifications. Choose heating type or none. Reset filter changer timer if necessary. Finish startup wizard with OK button. All additional changes post-startup wizard must be recorded in the Commissioning record. 10 Concluding Routines Perform the following procedures before leaving the site: 1.
EU Declaration of Conformity | 12 EU Declaration of Conformity Manufacturer EN 60529 Systemair UAB Linų st. 101 LT–20174 Ukmergė, LITHUANIA Office: +370 340 60165 Fax: +370 340 60166 www.systemair.com The manufacturer hereby confirms that SAVE VTR 500 comply with all applicable requirements in the following directives and regulations.
Phone +370 340 60165 Fax +370 340 60166 www.systemair.com SAVE VTR 500 · Installation instructions · 254522 · en_GB · 2021-03-22 · v01 Systemair UAB Linų st.