SAVE VTR 150/K Installation instructions Document in original language | 254494 · v01 GB
© Copyright Systemair UAB All rights reserved E&OE Systemair UAB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications. Systemair is not liable or bound by warranty if these instructions are not adhered to during installation or service.
Contents 1 Overview ......................................................1 1.1 General Description ................................1 1.2 Warranty ..............................................1 1.3 Type label.............................................1 2 Important Safety Information .............................1 2.1 Intended Use.........................................1 2.2 Admonitions .........................................2 3 Technical Data ................................................2 3.
Overview | 1 Overview 1.1 General Description Read the instructions carefully and in its entirety. For description of advanced settings and installation of accessories see Service and Accessories Installation manual. All documents can be found in our online catalogue at www.systemair.com. 1.2 Warranty For the assertion of warranty claims, the products must be correctly connected and operated, and used in accordance with the data sheets.
2 | Technical Data • The system should operate continuously, and only be stopped for maintenance/service. • Do not connect tumble dryers to the ventilation system. • Make sure that filters are mounted before starting the unit. 2.
Technical Data | 3.2 Dimensions and Weight Fig. 2 Dimensions and weight, L model The unit weight is 85 kg.
4 | Technical Data 3.3 Connections Left and Right models Position Description R Right hand model (Supply air connection is situated on the right hand side of the unit viewed from the front) L Left hand model (Supply air connection panel is situated on the left hand side of the unit viewed from the front) Symbol 3.4 3.4.
Delivery, Transport, Storage | 3.4.2 Condensation outside of the unit When the unit is installed in warm humid areas (like laundry) together with low outdoor temperature there is a certain point where moisture can condense outside of the casing. The condensation relation to indoor relative humidity, room and outdoor temperature is shown diagram below. The condensation outside of the unit do not occur in zones bellow each curve.
6 | Installation 5.1 Where/how to install The SAVE VTR 150/K is to be mounted above a stove. A Minimum distance between cabinets (mm) 600 B SAVE VTR 150/K unit width (mm) 598 C, Electrical stove Minimum distance between stove surface and cooker hood (mm) 450 (Recommended 500) C, Gas stove Minimum distance between stove surface and cooker hood (mm) 650 Fig. 3 SAVE VTR 150/K in a kitchen environment 5.
Installation | C — concrete/bricks, W — wood block, G — gypsum, M — mineral wool X* — adaptable height according to needs. SAVE VTR 150/K should be installed more than 2,3 m above the floor (or any other needed height).
8 | Electrical connections Make sure the mounting bracket is completely level. Follow the ventilation drawing when connecting the unit to the duct system. 6.1 Ventilation Duct Connection and Insulation Important • Always cover the ventilation ducts during construction period. • Make sure there are no loose objects or impurities inside the ducts. Install the ducts, supply air diffusers and air intake grilles as shown in the ventilation drawing.
Electrical connections | Fig. 4 Main circuit board position 7.1 Main circuit board layout The SAVE VTR 150/K is equipped with built-in regulation and internal wiring. Fig.
10 | Electrical connections Position Description 8 Analog input 2 — Supply air sensor 9 Analog input 3 — Freely configurable 10 Analog input 4 — Freely configurable / Overheat temperature sensor (units with heater) 11 Analog input 5 — Freely configurable 12 Digital input 1 — Rotor guard sensor (only for VSR, VTR models) 13 Digital input 2 — Freely configurable / Cooker hood (VTR 150/K unit) 14 Analog output 2 — Freely configurable / Electrical heater controller (VTC 700 unit) 15 Analog out
Before Starting the System | Position Description UI1–5 Freely configurable universal input. Can be set as analog input (0–10 V) or a digital input (24 V). UI1 default configuration: Pressure guard UI2 default configuration: Cooker hood UI3 default configuration: Fire alarm UI4 default configuration: Refresh 24V Maximum current 200mA at 24VDC +-10%.
12 | Concluding Routines Set speed of supply and extract air fans for each level. When finished, review your settings. It is possible to go back to previous menus and make modifications. Choose heating type or none. Reset filter changer timer if necessary. Finish startup wizard with OK button. All additional changes post-startup wizard must be recorded in the Commissioning record. 10 Concluding Routines Perform the following procedures before leaving the site: 1.
EU Declaration of Conformity | 12 EU Declaration of Conformity Manufacturer EN 60529 Systemair UAB Linų st. 101 LT–20174 Ukmergė, LITHUANIA Office: +370 340 60165 Fax: +370 340 60166 www.systemair.com The manufacturer hereby confirms that SAVE VTR 150/K comply with all applicable requirements in the following directives and regulations.
Phone +370 340 60165 Fax +370 340 60166 www.systemair.com SAVE VTR 150/K · Installation instructions · 254494 · en_GB · 2021-02-19 · v01 Systemair UAB Linų st.